In a certain three -wire Y -connected generator, the phase voltages are 2 kV. The magnitudes of the line voltages will be: A. 2,000 V B. 6,000 V C. 666 V D. 3,464 V

Your answer

Thanks for your contribution. Feel free to answer this question. Please avoid short answer. Your answer is most welcome. Be genuine.

Upload image or document:

Your name to display (optional):
Privacy: Your email address will only be used for sending these notifications.
Anti-spam verification:
Are you a robot ? (Y = Yes / N = No)
To avoid this verification in future, please log in or register.

1 Answer

0 votes
by

In a certain three -wire Y -connected generator, the phase voltages are 2 kV. The magnitudes of the line voltages will be: 3,464 V

Related questions

1 answer 26 views

A 500 MW, 3-phase, Y-connected synchronous generator has a rated voltage of 21.5 kV at 0.85 p.f. The line current when operating at full load rated conditions will be  (A) 13.43 kA (B) 15.79 kA (C) 23.25 kA (D) 27.36 kA

asked May 17, 2018 in Synchronous machine by Shimroz123
2 answers 95 views

The sending end and receiving end voltages of a three-phase transmission line are 10 kV/ph and 9.5 kV/ph, respectively. If the resistance drop is 150 V/ph and receiving end power factor is 0.8, the sending end power factor is (A) 0.745 lagging (B) 0.775 lagging (C) 0.8 lagging (D) 0.85 lagging

asked Apr 28, 2018 in Power system by Shimroz123
0 answers 18 views

Three single phase transformers are connected in delta-delta to step down a line voltage of 138 kV to 4160 V to supply power to a production plant. The plant draws 21 MW at a lagging power factor of 86 %. Calculate the apparent power furnished by the HV line.  (A) 24.4 MVA (B) 48.8 MVA (C) 12.2 MVA (D) 6.1 MVA 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 11 views

The three non -inductive loads of 5 kW, 3 kW and 2 kW are connected in a star network between R, Y and B phases and neutral. The line voltage is 400 V. The current in the neutral wire is nearly (a) 11 A (b) 14 A (c) 17 A (d) 21 A

asked Apr 25, 2018 in Electrical Engineering by Shimroz123
0 answers 17 views

A 3 Phase, 60 Hz generator connected in Y connection, generates a line to line voltage of 23900 V. Calculate the peak line voltage.  (A) 13800 V (B) 33800 V (C) 42300 V (D) 23900 V 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
0 answers 24 views

The sending and receiving end voltages of a three phase transmission line at 100 MW load are equal at 230 KV. The phase line impedance is j14 ohm. Calculate the maximum steady state power that can be transmitted over the line.  (A) 3778.5 MW (B) 2234.56 MW (C) 1784.19 MW (D) 512.37 MW

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 19 views

In a 3-phase 4-wire distribution system three unbalanced but equal magnitude impedances are connected between respective lines and neutral. The magnitude of current in the neutral conductor for RYB and RBY phase sequences are (A) zero (B) same (C) different (D) same in magnitude but differs in phase.

asked Apr 25, 2018 in Electrical Engineering by Shimroz123
1 answer 68 views

In a Y -connected circuit, between each line -voltage and the nearest phase - voltage, there is a phase -angle of: A. 0° B. 30° C. 60° D. 120°

asked Apr 12, 2018 in Electrical Engineering by Shimroz123
0 answers 145 views

The phase voltages across a certain load are given as Va = (176 - j132) V, Vb = (-128-j96) V and Vc = (- 160 +j100) V. Compute positive sequence component of voltage.  (A) 0 (B) 163.24-j35.1 V (C) 50.1-j53.9 V (D) 25.1-j53.9 V 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 15 views

A 3-phase star-connected 75 MVA, 25 kV 3-phase synchronous generator has a synchronous reactance of 1.0 p.u. The per unit value to a 90 MVA base and 30 kV is (A) 2/15 p.u. (B) 5/6 p.u. (C) 1.0 p.u. (D) 1.2 p.u.

asked Apr 25, 2018 in Electrical Engineering by Shimroz123
0 answers 46 views

For a balanced three phase star connected load for which line voltage is 230V and per phase resistance and reactance is 6 Ohm and 8 Ohm respectively. Calculate: 1) phase voltage 2) line current 3) power factor 4) total power absorbed

asked Aug 12, 2018 in Basic electrical and electronics engineering by Quiz
0 answers 17 views

A three phase 50 Hz, 400 kV transmission line is 300 km long. The line inductance is 0.97 mH/km per phase and capacitance is 0.0115 mF/km per phase. Assume a loss less line. Determine the line wavelength (a line phase constant).  (A) 1250 km (B) 6578 km (C) 4990 km (D) 2445 km 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
0 answers 107 views

Three materials X, Y and Z having relative permittivity 2.5, 3.0 and 4.0 respectively are used in a single core cable. The materials on inner most and outer most layer respectively should be (a) X and Y (b) Y and Z (c) X and Z (d) Z and X 

asked May 25, 2018 in Physics by Shimroz123
0 answers 557 views

A 30 MVA, 15 KV, 1500 rpm, 3 phase synchronous generator connected to a power grid has a synchronous reactance of 9 ohm per phase. If the exciting voltage is 12 kV (line to neutral) and the system voltage is 17.3 kV (line to line), Calculate the maximum power that generator can deliver before it falls out of step (losses synchronous).  (A) 39.952 MW (B) 78.349 MW (C) 16.67 MW (D) 112.89 MW

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 18 views

Three equal impedances are first connected in delta across a 3 -phase balanced supply. If the same impedances are connected in star across the same supply then,

asked Apr 23, 2018 in Electrical Engineering by Zeeshan
1 answer 26 views

A generator is connected through a 20 MVA, 13.8/138 kV step down transformer, to a transmission line. At the receiving end of the line a load is supplied through a step down transformer of 10 MVA, 138/69 kV rating. A 0.72 pu. load, evaluated on load side transformer ratings as base values , is supplied from the above system. For system base values of 10 MVA and 69 kV in load circuit, the value of the load (in per unit) in generator will be (A) 36 (B) 1.44 (C) 0.72 (D) 0.18

asked May 25, 2018 in Power system by Shimroz123
1 answer 23 views

Two 3-phase, Y-connected alternators are to be paralleled to a set of common busbars. The armature has a per phase synchronous reactance of 1.7 Ohm and negligible armature resistance. The line voltage of the first machine is adjusted to 3300 V and that of the second machine is adjusted to 3200 V. The machine voltages are in phase at the ... are paralleled. Under this condition, the synchronizing current per phase will be  (A) 16.98 A (B) 29.41 A (C) 33.96 A (D) 58.82 A

asked May 17, 2018 in Alternator by Shimroz123
0 answers 29 views

Draw the Delta connected three phase system showing all the voltages and currents. Write the power equation.

asked Aug 11, 2018 in Basic electrical and electronics engineering by Quiz
1 answer 19 views

A 20-MVA, 6.6-kV, 3-phase alternator is connected to a 3-phase transmission line. The per unit positive-sequence, negative-sequence and zero-sequence impedances of the alternator are j0.1, j0.1 and j0.04 respectively. The neutral of the alternator is connected to ground through an inductive reactor of j0.05 p.u. The per unit positive-, ... The voltage of the alternator neutral with respect to ground during the fault is  (A) 513.8 V (B) 889.9 V (C) 1112.0 V (D) 642.2 V

asked May 25, 2018 in Power system by Shimroz123
1 answer 13 views

In a Y-connected circuit, the magnitude of each line current is? A.one-third the phase current B.three times the corresponding phase current C.equal to the corresponding phase current D.zero

asked May 15, 2018 in Basic concepts by Shimroz123
0 answers 38 views

A balanced Delta connected load supplied with 440 V 50 Hz three phase AC supply has R=10 Ohm and L=0.6 mH in is each arm. Calculate line and phase current, active power.

asked Aug 12, 2018 in Basic electrical and electronics engineering by Quiz
1 answer 13 views

In a three phase half wave rectifier feeding resistive load, if the input source is a three phase 4 wire system and line to line voltage is 100 V. The supply frequency is 400 Hz. The ripple frequency at the output is: (1) 400 Hz (2) 800 Hz (3) 1200 Hz (4) None of these

asked May 22, 2018 in Electrical Engineering by Shimroz123
1 answer 16 views

The conductor of a 10 km long, single phase, two wire line are separated by a distance of 1.5 m. The diameter of each conductor is 1 cm, If the conductors are of copper, the inductance of the circuit is

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 11 views

Three capacitors 15µf, 18µf and 12µf are connected in a circuit. Find equivalent capacitance when they are connected in – 1) Series 2) Parallel

asked Sep 2, 2018 by Shimroz123
0 answers 20 views

A 3-phase, 2 pole, 11 kV, 10000 kVA alternator has earthed neutral through a resistance of 7.0Ω. The machine has current balance protection which operates if out of balance current exceeds 20% of full load. Determine %age of winding protected against earth fault (1) 10.6% (2) 11.6% (3) 10.9% (4) 11.2% 

asked Apr 11, 2018 in Electrical Engineering by Shimroz123
1 answer 63 views

The corona loss of a 3-phase transmission line is 100 kW at 60 kV/phase and 25 kW at 50 kV/phase. The disruptive critical voltage is (A) 40 kV (B) 43.6 kV (C) 49.6 kV (D) 50 kV

asked Apr 25, 2018 in Electrical Engineering by Shimroz123
1 answer 12 views

Polyphase generators produce simultaneous multiple sinusoidal voltages that are separated by certain constant: A. Phase -angles B. Frequency C. Voltage D. Current

asked Apr 12, 2018 in Electrical Engineering by Shimroz123
0 answers 189 views

A 30 MVA, 13.2 KV synchronous generator has a solidly grounded neutral. Its positive, negative and zero sequence impedances are 0.30, 0.40 and 0.05 pu respectively. What value of reactance must be placed in the generator neutral so that the fault current for a line to ground fault of zero fault impedance shall not exceed the rated line current.  (A) 4.416 ohm (B) 8.8 ohm (C) 2.08 ohm (D) 10.2 ohm 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
0 answers 85 views

Three single phase transformers each with 10 kVA rating are connected in a closed delta arrangement. If one transformer is taken out, the output capacity of the system will be (a) 20 kVA (b) 8.66 kVA (c) 17.32 kVA (d) 10 kVA

asked May 25, 2018 in Single phase transformer by Shimroz123
1 answer 187 views

For a 66 kV line having span of 200 meters between towers the approximate sag will be 2 m. If the span is double the sag will be:  (A) 1 m (B) 2 m (C) 4m (D) 8m

asked May 8, 2018 in Electric Power Distribution by Shimroz123
1 answer 21 views

Two single-phase 150 kVA, 7200/ 600 volt transformers are connected in open-delta. The maximum three-phase load that they can carry is: A) 300 kVA B) 75 kVA C) 259 kVA D) 249 kVA

asked Jun 4, 2018 in Single phase transformer by Shimroz123
1 answer 13 views

In a three-phase system, when the loads are perfectly balanced, the value of neutral current is equal to: A. Zero B. One-third of the maximum value C. Two -third of the maximum value D. The maximum value

asked Apr 12, 2018 in Electrical Engineering by Shimroz123
0 answers 52 views

A 220 kV, 3 phase transmission line is 60 km long. The resistance is 0.15 ohm / km and the inductance is 1.4 mH / km. Use the short line model to find the power at the sending end when the line is supplying a three phase load of 300 MVA at 0.8 pf lagging at 220 kV.  (A) 5.58MW (B) 80MW (C) 85.58MW (D) 74.42 MW 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
0 answers 20 views

A Phase shift transformer is designed to control 150 MVA on a 230 kV, 3 phase line. The phase angle is variable between zero and 15 deg. Calculate the approximate basic power rating of the transformer.  (A) 150 MVA (B) 56 MVA (C) 75 MVA (D) 750 MVA 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 16 views

The power delivered to a three-phase load can be measured by the use of 2 wattmeter only when the A. Load is balanced B. 3 -phase load is connected to the source through 3 wires C. Load is unbalanced D. 3 -phase load is connected to the source through 4 wires

asked Apr 12, 2018 in Electrical Engineering by Shimroz123
1 answer 9 views

A two-phase generator is connected to two 90Ω load resistors. Each coil generates 120 V ac. The value of current flowing through the common neutral line will be: A. 1.33 A B. 1.88 A C. 2.66 A D. 1.77 A

asked Apr 12, 2018 in Electrical Engineering by Shimroz123
2 answers 28 views

Three lamps are connected in parallel across a 120 Volt source. If one lamp burns out, the remaining two will be: A. Glow dimmer B. Glow brighter C. Not light D. Glow with the same brightness as before

asked Apr 12, 2018 in Electrical Engineering by Shimroz123
1 answer 116 views

A 500 MVA, 11 KV synchronous generator has 0.2 p.u. synchronous reactance. The p.u. synchronous reactance on the base values of 100 MVA and 22 KV is  A) 0.16 B) 0.01 C) 4.0 D) 0.25

asked May 17, 2018 in Synchronous machine by Shimroz123
1 answer 28 views

Two light bulbs are connected in series across a 120 V battery. Bulb 1 uses 40 W of power and Bulb 2 uses 20 W of power. If bulb 1 alone is connected to the 120 V source, then it will consume (A) 90 W (B) 80 W (C) 60 W (D) 180 W

asked Apr 25, 2018 in Electrical Engineering by Shimroz123
0 answers 51 views

If the stator winding of a three-phase induction motor is delta connected, the rotor winding   (a) should be delta connected (b) should be star connected (c) should not be delta connected (d) may be delta or star connected 

asked Apr 10, 2018 in Electrical Engineering by Shimroz123
1 answer 12 views

A three phase induction motor is driving full -load torque which is independent of speed. If the line voltage drops to 90% of the rated value, % increase in motor copper losses  (a) 23% (b) -18% (c) 123% (d) None of these

asked Apr 25, 2018 in Electrical Engineering by Shimroz123
1 answer 24 views

A single-phase transformer has a turns ratio of 1 :2 and is connected to a purely resistive load as shown in the figure. The magnetizing current drawn is 1A, and the secondary current is 1A. Ifcore losses and leakage reactances are neglected, the primary current is  A)1.41A B)2A C) 2.24A D)3A

asked May 20, 2018 in Transformer by Shimroz123
3 answers 140 views

Three resistors of 4 Ω, 6 Ω and 9 Ω are connected in parallel. Which resistor consumes the maximum power?  (A) 4 Ω (B) 6 Ω (C) 9 Ω (D) 17 Ω

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
0 answers 35 views

Three resistances of 3 Ω each are connected in delta. The value of the resistances in the equivalent star is : (A) 27 (B) 9 (C) 1.5 (D) 1 Ω

asked Mar 31, 2018 in Electrical Engineering by Shimroz123
0 answers 243 views

A three phase breaker is rated at 2000 MVA, 33 kV, its making current is  (A) 70 kA (B) 89 kA (C) 49 kA (D) 35 kA 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 12 views

Alternating voltages and currents are represented by straight line with an arrow to represent the magnitude and direction. This representation is called

asked May 14, 2018 in Electrical Engineering by Shimroz123
1 answer 19 views

In a DC generator the windings of interpoles are connected :  (A) in series with main field winding, to create a pole,of same polarity as the main pole ahead in the direction of rotation.  (B) in series with main field winding, to create a pole of opposite polarity as the main pole ahead in the direction of ... in the direction of rotation.  (D) in series with the armature winding, to create a pole of opposite polarity as the main pole ahead in the direction of rotation.

asked Apr 29, 2018 in Electrical Machine by Shimroz123
0 answers 20 views

The zero sequence current of a generator for line to ground fault is j 2.4 p.u. The current through the neutral during the fault is (a) j 0.8 p.u (b) j 2.4 p.u. (c) j 0.24 p.u. (d) j 7.2 p.u. 

asked May 25, 2018 in Power system by Shimroz123
1 answer 11 views

In a dc-ac 3-phase MOSFET bridge inverter circuit, the switches are marked in a sequence as 1, 2, 3 in the top-half and 4, 5, 6 in the bottom half of the bridge. The triggering sequence of switches that gives balanced output voltage is (A) 1, 2, 3, 4, 5, 6 (B) 1, 5, 3, 4, 2, 6 (C) 1, 6, 2, 4, 3, 5 (D) 1, 4, 2, 5, 3, 6

asked Apr 25, 2018 in Electrical Engineering by Shimroz123

Welcome to electronics2electrical.com here you can ask questions related to electrical, electronics, mechanical, telecommunication, instrumentation, computer, mathematics, physics etc.
Be respectful to all the members. Do not copy and paste the answers from other websites which have copyright content. While asking question give full details about it.

Categories

Most popular tags

power motor dc circuit transformer voltage current used system phase resistance factor synchronous load ac energy induction electric generator series frequency between speed capacitor use electrical meter line difference control type mosfet transmission magnetic plant high single instrument bjt unit source advantages function diode and machine winding field define torque parallel amplifier supply shunt thyristor motors electricity arduino maximum time relay armature problem value on transformers types coil diagram state flow ratio material three formula starting direction theorem method emf operating efficiency digital wave microprocessor test instruments inductance loss measure operation connected signal low applications effect single-phase network temperature working constant losses different law wattmeter measuring compare controlled breaker drive device logic rc full switch flux wire resistivity disadvantages free of materials machines angle force converter conductor transistor gain open protection scr core measurement number bridge principle generators reactance circuits negative the friction iron loop short pole battery conservation steam resistors hysteresis computer using analog lines secondary station gate a rectifier inverter linear induced relays nuclear capacitance basic characteristics design direct work rotor electronics ammeter forces diesel damping rlc connection factors capacitors minimum insulation moving regulation running self systems air fault range main stability quality starter igbt eddy alternator ideal rl average 3-phase plants arc thermal error fuzzy biasing dielectric pressure balanced superposition errors copper rotation feedback impedance measured electronic electrons charge inductive transfer explain start off back curve over solar is three-phase tariff locomotive peak bias zener engineering commutator surge conductors rating universal potentiometer density permanent mechanical transducer capacity memory adc excitation two fuse pure harmonics application semiconductor inductor internal pmmc reaction welding resonance traction permeability breakers rms designed electromagnetic si generation brushes switching capacitive shaded rate 1 distribution resistor methods delta star oscillator reluctance simplification algebra 8085 boolean weston dynamometer insulating strength installation definition fuel heating earth units

8,530 questions

7,129 answers

135 comments

3,090 users

...