In a balanced 3 -phase 200 V circuit, the line current is 115.5 A. When the power is measured by two wattmeter method, one of the wattmeters reads 20 kW and the other one reads zero. What is the power factor of the load ?
in Electrical Engineering by
← Prev Question Next Question →
Advertisements

Please log in or register to answer this question.

1 Answer

In a balanced 3 -phase 200 V circuit, the line current is 115.5 A. When the power is measured by two wattmeter method, one of the wattmeters reads 20 kW and the other one reads zero. What is the power factor of the load ? 

0.5