One single-phase energy meter operating on 230 V and 5 A for 5 hours makes 1940 revolutions. Meter constant is 400 rev/kWh. The power factor of the load is

Your answer

Thanks for your contribution. Feel free to answer this question. Please avoid short answer. Your answer is most welcome. Be genuine.

Upload image or document:

Your name to display (optional):
Privacy: Your email address will only be used for sending these notifications.
Anti-spam verification:
Are you a robot ? (Y = Yes / N = No)
To avoid this verification in future, please log in or register.

1 Answer

0 votes
by

One single-phase energy meter operating on 230 V and 5 A for 5 hours makes 1940 revolutions. Meter constant is 400 rev/kWh. The power factor of the load is 0.8

Related questions

1 answer 24 views

What is the power factor when a single phase watt meter operating on 200 V and 5 A for 5 hours makes 2016 revolutions and the meter constant in revolution is 420? A) 0.04 B) 1.04 C) 0.96 D) None of these

asked Apr 29, 2018 in Electrical Engineering by Shimroz123
1 answer 16 views

The meter constant of a single-phase 230 V induction watt hour meter is 400 revolutions per kWh. The speed of the meter disc for a current of 10 A of 0.9 pf lagging will be

asked Apr 23, 2018 in Electrical Engineering by Shimroz123
1 answer 29 views

The disc of a single phase Induction-type energy meter makes 60 revolutions in 6 minutes. Meter Constant is 1200 rev/kWh. Power consumption in the load is (A) 1.2 kW (B) 1 kW (C) 600 W (D) 500 W

asked Apr 25, 2018 in Instrumentation and control by Shimroz123
1 answer 41 views

A 230 V/460 V single-phase transformer operating at 20 A and unity power factor has primary referred resistance of 0.2 Ω and reactance of 0.5 Ω. The approximate primary induced emf is (A) 216 V (B) 226 V (C) 234 V (D) 236 V

asked Apr 28, 2018 in Electrical Engineering by Shimroz123
0 answers 34 views

A meter whose constant is 600 revolutions/kWh makes 5 revolutions in 20 seconds. Calculate the load in kW. (1) 0.5 kW (2) 1 kW (3) 1.5 kW (4) 2 kW  

asked Apr 11, 2018 in Electrical Engineering by Shimroz123
0 answers 53 views

The meter constant of a single phase 240 V induction watt hour meter is 400 revolutions per KWhr. The speed of the meter disc for a current of 10 A of 0.8 pf, lagging will be  (A) 12.8 rpm (B) 16.02 rpm (C) 18.2 rpm (D) 21.1 rpm 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 38 views

In a 230 V, 50 Hz single-phase SCR bridge converter operating at a firing delay angle, α and with large R-L load, the input source current is (A) sinusoidal current (B) constant dc current (C) continuous rectangular pulses (D) alternating rectangular pulses

asked Apr 28, 2018 in Power Electronics by Shimroz123
0 answers 41 views

If an energy meter disc makes 10 revolutions in 100 seconds when a load of 450W is connected to it, the meter constant in revolutions per kWh is  A) 1000 B) 500 C) 1600 D) 800

asked Apr 9, 2018 in Electrical Engineering by Shimroz123
0 answers 64 views

An energy meter has a constant of 600 rev/kWh. If the meter makes 10 revolutions in 20 s, what is the load in kW?  (A) 0.75 kW (B) 1.5 kW (C) 3 kW (D) 6 kW 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 18 views

What is the slip (as a percentage) when a 6 pole single phase induction motor operating on 220 V and 60 Hz is rotating at speed of 1140 rpm? A) 60% B) 5% C) 10% D) None of these

asked Apr 29, 2018 in Electrical Engineering by Shimroz123
1 answer 17 views

The current coil of a single-phase energy meter is wound on (a) One limb of the laminated core (b) Both the limbs of the laminated core with same number of turns (c) Both the limbs of the laminated core with different number of turns (d) The centre of the limb on the laminated core

asked Apr 23, 2018 in Electrical Engineering by Shimroz123
0 answers 24 views

A single phase 230 V/ 150 V , 1 kVA, 50 Hz transformer is supplied by 230 V AC supply. Find the full load primary and secondary current. 

asked Sep 1, 2018 by Quiz
1 answer 15 views

If a 220/440 V, 50 Hz, 5 KVA, single-phase transformer operates on 220V, 40Hz supply with secondary winding open circuited: (A) both the eddy current and the hysteresis losses will decrease (B) both the eddy current and the hysteresis losses will increase (C) eddy current losses will remain the same but the hysteresis losses will increase (D) eddy current losses will increase but the hysteresis losses will remain the same

asked Apr 11, 2018 in Computer Engineering by Shimroz123
1 answer 25 views

A consumer finds that after running 10 kVA equipment on full load for six hours, his energy consumption was 48 kWH. It can be concluded that (A) The load factor of consumer for the day was unity. (B) The maximum demand of consumer is 10 kW. (C) The equipment was drawing only reactive power. (D) The power factor of equipment was 0.8. 

asked May 13, 2018 in Electrical Engineering by Shimroz123
1 answer 7 views

A single-phase, 230 V, 50 Hz ac mains fed step down transformer (4:1) is supplying power to a half-wave uncontrolled ac-dc converter used for charging a battery (12 V dc) with the series current limiting resistor being 19.04 Ohm. The charging current is  (A) 2.43 A (B) 1.65 A (C) 1.22 A (D) 1.0 A

asked May 18, 2018 in Power electronics converters by Shimroz123
1 answer 24 views

A 230 V, 50 Hz phase controlled single-phase full-controlled SCR bridge converter draws 15 A constant dc current. If the source inductance is 3 mH, the drop in dc output voltage is (A) 4.5 V (B) 6.75 V (C) 9 V (D) 13.5 V

asked Apr 28, 2018 in Power Electronics by Shimroz123
0 answers 31 views

A single phase energy meter has a constant of 1200 revolution/kWh. When a load of 200 W is connected, the disc rotates at 4.2 revolutions per min. If the load is on for 10 hours, the meter records an excess of   (a) 0.1 kWh (b) 0.2 kWh (c) 1.0 kWh (d) 2.0 kWh 

asked Apr 10, 2018 in Electrical Engineering by Shimroz123
0 answers 14 views

A single phase motor draws a current of 5 A from a 120 V, 60 Hz line. The power factor of the motor is 65%. Calculate the active power absorbed by the motor.  (A) 600 W (B) 390 W (C) 456 W (D) 650 W 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 19 views

A 200 V, 5 A d.c. energy meter is tested at its marked ratings. The resistance of the pressure circuit is 8000 Ω and that of current coil is 0.1 Ω. The power consumed when testing the meter with phantom loading with current circuit excited by a 6 V battery is (A) 2.5 W (B) 5 W (C) 32.5 W (D) 35 W

asked Apr 28, 2018 in Electrical Measurements and Instrumentation by Shimroz123
1 answer 21 views

a single phase full wave midpoint thyristor converter uses a 230/200V transformer with centre tap on the secondary side. The P.I.V per thyristor is   (A) 100V (B)141.4V (C)200V (D)282.8V

asked May 17, 2018 in Power electronics converters by Shimroz123
1 answer 36 views

What is the frequency of an alternator which has 2 poles and makes 3600 revolutions per minute? A) 3600 HZ B) 60 Hz C) 120 Hz D) None of these

asked Apr 29, 2018 in Electrical Engineering by Shimroz123
1 answer 41 views

The hysteresis and eddy current losses of a single phase transformer working on 200 V, 50 Hz supply are Ph and Pe respectively. The percentage decrease in these when operated on a 160 V, 40 Hz supply are   (a) 32, 36 (b) 20, 36 (c) 25, 50 (d) 40, 80 

asked May 13, 2018 in Transformer by Shimroz123
1 answer 9 views

In a single phase induction energy meter, in order to obtain true value of energy, the shunt magnetic flux should lag behind the applied voltage by   (a) 90o (b) 0o (c) 45o (d) 60o

asked May 13, 2018 in Instrumentation and control by Shimroz123
1 answer 18 views

Draw a neat sketch of 1-ph induction type energy meter and write operating principle of it. 

asked Sep 6, 2018 by Shimroz123
1 answer 22 views

What is the charge on each capacitor when a 150 V is applied across two capacitors with values 5 μF and 10 μF, connected in series? A) 500 μC B) 0.5 μC C) 0.5 C D) None of these

asked Apr 29, 2018 in Electrical Engineering by Shimroz123
1 answer 12 views

A d.c. voltage of 230 V is imposed on an unloaded 230 V, 50 Hz transformer, it will (A) give high secondary voltage (B) burn out (C) give secondary voltage as per k (D) None of these

asked May 13, 2018 in Electrical Engineering by Shimroz123
1 answer 20 views

A single-phase ac voltage source has 200 V rms and a system connected consumes an active power of 300 W. What is the reactive power consumed by the system if 2.5 A rms current is drawn ?  (a) 100 VAR (b) 200 VAR (c) 300 VAR (d) 400 VAR

asked Apr 23, 2018 in Electrical Engineering by Zeeshan
0 answers 42 views

We wish to build a 135 V, 20 A, DC power supply using a single phase bridge rectifier and an inductive filter. The peak to peak current ripple should be about 10%. If a 60 Hz AC source is available; Calculate the peak to peak current ripple.  (A) 19 A (B) 20 A (C) 2 A (D) 1 A 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 13 views

Three 60 W bulbs are in parallel across the 230 V power line. If one bulb burns out

asked May 14, 2018 in Electrical Engineering by Shimroz123
1 answer 19 views

A 100-watt light bulb turned on for 8 hours uses :  (A) 800 Wh (B) 0.8 kWh (C) 8 kWh (D) None of the above

asked May 8, 2018 in Electrical Engineering by Shimroz123
0 answers 69 views

The magnetizing reactance of a 4 kV/ 400 V, 50 Hz single-phase transformer on low voltage side is 35 Ω. The magnetizing reactance on the high voltage side is (A) 0.35 Ω (B) 3.5 Ω (C) 350 Ω (D) 3500 Ω

asked Jun 4, 2018 in Single phase transformer by Shimroz123
1 answer 15 views

A single-phase fully controlled thyristor bridge ac-dc converter is operating at a firing angle of 25o and an overlap angle of 10o with constant dc output current of 20 A. The fundamental power factor (displacement factor) at input ac mains is  (A) 0.78 (B) 0.827 (C) 0.866 (D) 0.9

asked May 18, 2018 in Power electronics converters by Shimroz123
1 answer 150 views

The Lamp resistance of a mini-torch light, operating on 1.5 volts is classified as _____________resistance. A. Low B. Medium C. High D. None of these 

asked Apr 12, 2018 in Electrical Engineering by Shimroz123
0 answers 20 views

A Phase shift transformer is designed to control 150 MVA on a 230 kV, 3 phase line. The phase angle is variable between zero and 15 deg. Calculate the approximate basic power rating of the transformer.  (A) 150 MVA (B) 56 MVA (C) 75 MVA (D) 750 MVA 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
0 answers 17 views

A DC shunt generator supplies 450 A at 230 V. The resistances of shunt field and armature are 50 Ω and 0.025 Ω respectively. What will be the armature voltage drop?  (A) 11.24 V (B) 22.7 V (C) 31.6 V (D) 38.4 V 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 14 views

The values of L and C for a low pass filter with cut off frequency of 2.5 KHz and operating with a terminated load resistance of 450 Ohm are given by  (a) 57.3 mH; 0.283 μF (b) 28.66 μH; 0.14 μF (c) 114.64 mH; 0.566 mF (d) 50.23 mH; 0.632 mF

asked May 16, 2018 in Electronics Engineering by Shimroz123
1 answer 20 views

In a single-phase induction motor, the operating direction is determined by the ________ A) Rotor B) Stator C) Starting circuit D) None of these

asked Apr 29, 2018 in Electrical Engineering by Shimroz123
0 answers 21 views

A single phase fully controlled thyristor bridge ac -dc converter is operating at a firing angle of 25 degree and an overlap angle 10 degree with constant dc output current of 20A. The fundamental power factor (displacement factor) at input ac mains is : (A) 0.78 (B) 0.827 (C) 0.866 (0) 0.9

asked Apr 14, 2018 in Electrical Engineering by Shimroz123
0 answers 50 views

A single phase transmission line and a telephone line are both symmetrically strung one below the other, in horizontal configurations, on a common tower, The shortest and longest distances between the phase and telephone conductors are 2.5 m and 3 m respectively. The voltage (volt/km) induced in the telephone circuit, due to 50 Hz current of 100 amps in the power circuit is (A) 4.81 (B) 3.56 (C) 2.29 (D) 1.27

asked May 25, 2018 in Power system by Shimroz123
1 answer 18 views

Comparing the total copper cross sections in terms of current-carrying capacity for a single-phase and a three-phase 120 V system with effective load resistance of 15Ω, will yield: A. single-phase 32 A; three-phase 16 A B. single-phase 16 A; three-phase 8 A C. single-phase 8 A; three-phase 4 A D. single-phase 16 A; three-phase 0 A

asked Apr 12, 2018 in Electrical Engineering by Shimroz123
1 answer 12 views

A single phase transformer is designed to operate from 50 Hz, 1100 V supply and to have an output voltage of 240 V at no load. The core has mean area of 30 cm2 and the flux density has not to exceed 1.3T. The number of secondary turns will be (a) 1270 (b) 1017 (c) 768 (d) 277  

asked May 25, 2018 in Single phase transformer by Shimroz123
1 answer 80 views

The locked rotor current in a 3-phase, star connected 15 , kW 4 , pole 230 V , 50 Hz induction motor at rated conditions is 50 A. Neglecting losses and magnetizing current, the approximate locked rotor line current drawn when the motor is connected to a 236 , V 57 Hz supply is  (A) 58.5 A (B) 45.0 A (C) 42.7 A (D) 55.6 A

asked May 17, 2018 in Electrical Machine by Shimroz123
1 answer 13 views

The low voltage winding of a 400/230 V, 1-phase, 50 Hz transformer is to be connected to a 25 Hz, the supply voltage should be

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 24 views

In a balanced 3 -phase 200 V circuit, the line current is 115.5 A. When the power is measured by two wattmeter method, one of the wattmeters reads 20 kW and the other one reads zero. What is the power factor of the load ?

asked Apr 23, 2018 in Electrical Engineering by Zeeshan
0 answers 26 views

A d.c. ampere-hour meter is rated at 5A, 250 V. The declared constant is 5 A sec/revolution. The constant in revolution/kwh will be (a) 2880 (b) 2680 (c) 2480 (d) 2280

asked May 25, 2018 in Electrical Measurements and Instrumentation by Shimroz123
1 answer 41 views

The primary turns of a 444 V/222 V, 50 Hz single-phase transformer with a core cross-sectional area of 100 cm2, and a maximum flux density of 1.0 T is (A) 100 (B) 200 (C) 222 (D) 400

asked Apr 25, 2018 in Electrical Engineering by Shimroz123
1 answer 6 views

Problem on electrical power and energy 5

asked May 16 by Shimroz123

Welcome to electronics2electrical.com here you can ask questions related to electrical, electronics, mechanical, telecommunication, instrumentation, computer, mathematics, physics etc.
Be respectful to all the members. Do not copy and paste the answers from other websites which have copyright content. While asking question give full details about it.

Categories

Most popular tags

power motor dc circuit transformer voltage current used system phase resistance factor synchronous load ac energy induction electric generator series frequency between speed capacitor use electrical meter line difference control type mosfet transmission magnetic plant high single instrument bjt unit source advantages function diode and machine winding field define torque parallel amplifier supply shunt thyristor motors electricity arduino maximum time relay armature problem value on transformers types coil diagram state flow ratio material three formula starting direction theorem method emf operating efficiency digital wave microprocessor test instruments inductance loss measure operation connected signal low applications effect single-phase network temperature working constant losses different law wattmeter measuring compare controlled breaker drive device logic rc full switch flux wire resistivity disadvantages free of materials machines angle force converter conductor transistor gain open protection scr core measurement number bridge principle generators reactance circuits negative the friction iron loop short pole battery conservation steam resistors hysteresis computer using analog lines secondary station gate a rectifier inverter linear induced relays nuclear capacitance basic characteristics design direct work rotor electronics ammeter forces diesel damping rlc connection factors capacitors minimum insulation moving regulation running self systems air fault range main stability quality starter igbt eddy alternator ideal rl average 3-phase plants arc thermal error fuzzy biasing dielectric pressure balanced superposition errors copper rotation feedback impedance measured electronic electrons charge inductive transfer explain start off back curve over solar is three-phase tariff locomotive peak bias zener engineering commutator surge conductors rating universal potentiometer density permanent mechanical transducer capacity memory adc excitation two fuse pure harmonics application semiconductor inductor internal pmmc reaction welding resonance traction permeability breakers rms designed electromagnetic si generation brushes switching capacitive shaded rate 1 distribution resistor methods delta star oscillator reluctance simplification algebra 8085 boolean weston dynamometer insulating strength installation definition fuel heating earth units

8,471 questions

7,069 answers

134 comments

3,088 users

...