A 1100 kVA, 11 kV/1.1 kV conventional two-winding transformer is connected as a 12.1 kV/11 kV step-down auto-transformer. The rating of the auto-transformer is

(A) 1000 kVA (B) 1100 kVA (C) 11000 kVA (D) 12100 kVA

Your answer

Thanks for your contribution. Feel free to answer this question. Please avoid short answer. Your answer is most welcome. Be genuine.

Upload image or document:

Your name to display (optional):
Privacy: Your email address will only be used for sending these notifications.
Anti-spam verification:
Are you a robot ? (Y = Yes / N = No)
To avoid this verification in future, please log in or register.

1 Answer

0 votes
by

A 1100 kVA, 11 kV/1.1 kV conventional two-winding transformer is connected as a 12.1 kV/11 kV step-down auto-transformer. The rating of the auto-transformer is 12100 kVA

Related questions

1 answer 40 views

A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is (A) 0.85 Ω (B) 3.63 Ω (C) 36.3 Ω (D) 252 Ω

asked Apr 28, 2018 in Power system by Shimroz123
1 answer 26 views

A generator is connected through a 20 MVA, 13.8/138 kV step down transformer, to a transmission line. At the receiving end of the line a load is supplied through a step down transformer of 10 MVA, 138/69 kV rating. A 0.72 pu. load, evaluated on load side transformer ratings as base values , is supplied from the above system. For system base values of 10 MVA and 69 kV in load circuit, the value of the load (in per unit) in generator will be (A) 36 (B) 1.44 (C) 0.72 (D) 0.18

asked May 25, 2018 in Power system by Shimroz123
0 answers 18 views

Three single phase transformers are connected in delta-delta to step down a line voltage of 138 kV to 4160 V to supply power to a production plant. The plant draws 21 MW at a lagging power factor of 86 %. Calculate the apparent power furnished by the HV line.  (A) 24.4 MVA (B) 48.8 MVA (C) 12.2 MVA (D) 6.1 MVA 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 12 views

A 400V/100 V, 10 KVA two-winding transformer is reconnected as an auto-transformer across a suitable voltage source. The maximum rating of such an arrangement could be  A) 50 KVA B) 15 KVA C) 12.5 KVA D) 8.75 KVA

asked May 20, 2018 in Autotransformer by Shimroz123
1 answer 7 views

A single-phase, 230 V, 50 Hz ac mains fed step down transformer (4:1) is supplying power to a half-wave uncontrolled ac-dc converter used for charging a battery (12 V dc) with the series current limiting resistor being 19.04 Ohm. The charging current is  (A) 2.43 A (B) 1.65 A (C) 1.22 A (D) 1.0 A

asked May 18, 2018 in Power electronics converters by Shimroz123
0 answers 15 views

A 3-phase, 2 pole, 11 kV, 10000 kVA alternator has earthed neutral through a resistance of 7.0Ω. The machine has current balance protection which operates if out of balance current exceeds 20% of full load. Determine %age of winding protected against earth fault (1) 10.6% (2) 11.6% (3) 10.9% (4) 11.2% 

asked Apr 11, 2018 in Electrical Engineering by Shimroz123
1 answer 17 views

A single-phase, 50 kVA, 250 V/500 V two winding transformer has an efficiency of 95% at full load, unity power factor. If it is re-configured as a 500 V/750 V auto-transformer, its efficiency at its new rated load at unity power factor will be  (A) 95.752% (B) 97.851% (C) 98.276% (D) 99.241%

asked May 17, 2018 in Transformer by Shimroz123
0 answers 17 views

A transformer when supplying a load, maintained at 11 kV across load terminals. When the load was switched off, the terminal voltage becomes 11550 V, what is the voltage regulation at this load? (1) 11.55 % (2) 5.5% (3) 5% (4) 55%  

asked Apr 11, 2018 in Electrical Engineering by Shimroz123
1 answer 593 views

In a step-up or step-down transformer, electrical power is transferred from one circuit to another without change in

asked May 14, 2018 in Transformer by Shimroz123
1 answer 25 views

In a step-down transformer, there is a change of 15 A in the load current. This results in change of supply current of?

asked Mar 19, 2018 in Transformer by Shimroz123
0 answers 108 views

A single phase transformer rated at 3000 kVA, 69 kV 4.16 kV, 60 Hz has a total internal impedance Zp of 127 ohm, referred to the primary side. Calculate the primary current if the secondary is accidentally short circuited.  (A) 43.5 A (B) 543 A (C) 9006 A (D) 721 A 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 36 views

Step-down transformer converts high voltage and low current into:  (A) How voltage and high current (B) High voltage and low current (C) Low voltage and high current (D) None of the above

asked May 8, 2018 in Electrical Engineering by Shimroz123
1 answer 95 views

A transmission line has 1 P.0 impedance on a base of 11 KV, 100 MVA. On a base of 55 KV. it will have a P.0 impedance of

asked May 3, 2018 in Electric Power Transmission by Shimroz123
0 answers 20 views

One 200 V, 100 W bulb is connected in series with primary of a 200 V, 10 kVA transformer. If its secondary is kept open circuited, then the bulb would have (1) Full brightness (2) Poor brightness (3) A little less than full brightness (4) More than full brightness 

asked Apr 11, 2018 in Electrical Engineering by Shimroz123
1 answer 16 views

When two transformer of different kVA rating are connected in parallel they share the load in proportion to their respective kVA rating only when their:

asked May 22, 2018 in Transformer by Shimroz123
1 answer 24 views

A single-phase transformer has a turns ratio of 1 :2 and is connected to a purely resistive load as shown in the figure. The magnetizing current drawn is 1A, and the secondary current is 1A. Ifcore losses and leakage reactances are neglected, the primary current is  A)1.41A B)2A C) 2.24A D)3A

asked May 20, 2018 in Transformer by Shimroz123
0 answers 17 views

A 1:5 step-up transformer has 120V across the primary and 600 ohms resistance across the secondary. Assuming 100% efficiency, the primary current will be:  (A) 0.2 Amp. (B) 5 Amps. (C)10 Amps. (D) 20 Amps

asked Apr 9, 2018 in Electrical Engineering by Shimroz123
0 answers 10 views

How much energy is expended, in joules, if a voltage of 12 V moves 1.25 C of charge between two points?

asked Jul 1 by Shimroz123
1 answer 15 views

If a 220/440 V, 50 Hz, 5 KVA, single-phase transformer operates on 220V, 40Hz supply with secondary winding open circuited: (A) both the eddy current and the hysteresis losses will decrease (B) both the eddy current and the hysteresis losses will increase (C) eddy current losses will remain the same but the hysteresis losses will increase (D) eddy current losses will increase but the hysteresis losses will remain the same

asked Apr 11, 2018 in Computer Engineering by Shimroz123
0 answers 24 views

A single phase 230 V/ 150 V , 1 kVA, 50 Hz transformer is supplied by 230 V AC supply. Find the full load primary and secondary current. 

asked Sep 1, 2018 by Quiz
0 answers 14 views

One 200 KVA transformer has an iron loss of 1 KW and full load Cu loss of 2 KW. Its load KVA corresponding to maximum efficiency is:  (A) 100 KVA (B) 141.4 KVA (C) 50 KVA (D) 200 KVA 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 30 views

A two -winding single phase transformer has a voltage regulation of 4.5% at full - load and unity power -factor. At full -load and 0.80 lagging power-factor, the voltage regulation will be: (A) 4.5% (B) less than 4.5% (C) more than 4.5% (D) none of the above

asked Apr 11, 2018 in Electrical Engineering by Shimroz123
2 answers 55 views

An Auto-transformer (which has only one winding) may be used as a ______ .  (A) Both Step-Up and Step-Down transformer (B) Step-Down Transformer (C) Step-Up Transformer (D) None of these

asked May 8, 2018 in Electrical Engineering by Shimroz123
1 answer 12 views

A single phase transformer is designed to operate from 50 Hz, 1100 V supply and to have an output voltage of 240 V at no load. The core has mean area of 30 cm2 and the flux density has not to exceed 1.3T. The number of secondary turns will be (a) 1270 (b) 1017 (c) 768 (d) 277  

asked May 25, 2018 in Single phase transformer by Shimroz123
2 answers 22 views

Ripple in output current of a step-down chopper feeding RLE load is maximum, when duty cycle is equal to:  (1) 1 (2) 0.5 (3) 0.75 (4) 0.33

asked May 22, 2018 in Electronics Engineering by Shimroz123
1 answer 13 views

The low voltage winding of a 400/230 V, 1-phase, 50 Hz transformer is to be connected to a 25 Hz, the supply voltage should be

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 64 views

The inertia constant of a 100 MVA, 11 kV water wheel generator is 4. The energy stored in the rotor at the synchronous speed is: A) 400 Mega Joule B) 400 Kilo Joule C) 25 Mega Joule D) 25 Kilo Joule

asked Jun 4, 2018 in Power system by Shimroz123
1 answer 28 views

Two light bulbs are connected in series across a 120 V battery. Bulb 1 uses 40 W of power and Bulb 2 uses 20 W of power. If bulb 1 alone is connected to the 120 V source, then it will consume (A) 90 W (B) 80 W (C) 60 W (D) 180 W

asked Apr 25, 2018 in Electrical Engineering by Shimroz123
1 answer 40 views

When 7/0.029 V.I.R cable is carrying 20 A, a drop of 1 V occurs every 12 m. The voltage drop in a 100 m run of this cable when it is carrying 10 A is nearly  (a) 4.2 V (b) 3.2 V (c) 1.2 V (d) 0.42 V

asked Apr 25, 2018 in Electrical Engineering by Shimroz123
0 answers 22 views

The distance between two coil sides which are connected to the same commutator segment is called as  (1) winding pitch (2) back pitch (3) front pitch (4) full pitch

asked Apr 10, 2018 in Electrical Engineering by Shimroz123
1 answer 21 views

A step-down chopper, fed from a 120 volt DC source, operates a DC motor whose armature e.m.f. and armature resistance are 100 volt and 0.5Ω respectively. With the magnitude control ratio 0.6, the quadrant of operation DC motor is  (a) First (b) Second (c) Third (d) Fourth

asked May 15, 2018 in Power Electronic Controlled Drives by Shimroz123
1 answer 21 views

Two single-phase 150 kVA, 7200/ 600 volt transformers are connected in open-delta. The maximum three-phase load that they can carry is: A) 300 kVA B) 75 kVA C) 259 kVA D) 249 kVA

asked Jun 4, 2018 in Single phase transformer by Shimroz123
1 answer 5 views

As shown in the figure, 1 ohm resistance is connected across a source that has a load line v + i = 100. The current through the resistance is A) 25 A B) 50 A C) 100 A D) 200A

asked May 20, 2018 in Network Analysis by Shimroz123
1 answer 14 views

A 3-phase 11 kV generator feeds power to a constant power unity power factor load of 100 MW through a 3-phase transmission line. The line-to line voltage at the terminals of the machine is maintained constant at 11 kV. The per unit positive sequence impedance of the line based on 100 MVA and 11 kV is j0.2. The line to line voltage at the ... load to increase the line-to-line voltage at the load terminals to 11 kV is  (A) 100 MVAR (B) 10.1 MVAR (C) -100 MVAR (D) -10.1 MVAR

asked May 25, 2018 in Power system by Shimroz123
1 answer 46 views

A 100 MVA, 11 KV, 3-phase, 50 Hz, 8—pole synchronous generator has an inertia constant H equal to 4 seconds. The stored energy in the rotor of the generator at synchronous speed will be  A) 100 MJ B) 400 MJ C) 800 MJ D) 12.5 MJ

asked May 20, 2018 in Synchronous machine by Shimroz123
1 answer 115 views

A 500 MVA, 11 KV synchronous generator has 0.2 p.u. synchronous reactance. The p.u. synchronous reactance on the base values of 100 MVA and 22 KV is  A) 0.16 B) 0.01 C) 4.0 D) 0.25

asked May 17, 2018 in Synchronous machine by Shimroz123
1 answer 35 views

The number of insulator discs (each rated 11 kV) required in a suspension type insulator string of 220 kV line is 

asked May 8, 2018 in Electric Power Transmission by Shimroz123
1 answer 137 views

A 3-phase, 11 kv, 50 Hz, 200 kW load has a power factor of 0.8 lag. A delta connected 3-phase capacitor is used to improve the power factor to unity. The capacitance perphase of the capacitor in micro-farads is?

asked Mar 27, 2018 in Power system by Shimroz123
0 answers 6 views

Two two-port networks are connected in cascade. The combination is to be represented as a single two-port network. The parameters of the network are obtained by multiplying the individual a. z-parameter matrix b. h-parameter matrix c. y-parameter matrix d. ABCD-parameter matrix

asked May 24, 2018 in Network Analysis by Shimroz123
1 answer 16 views

A 3 stack stepper motor with 12 number of rotor teeth has a step angle of: (A) 12° (B) 8° (C) 24° (D) 10°

asked Apr 11, 2018 in Computer Engineering by Shimroz123
0 answers 43 views

If 5000 kW power is transmitted at 220 kV in place of 11 kV, reduction in the value of electric current will be (a) 90% (b) 95% (c) 5% (d) 10% 

asked May 26, 2018 in Electric Power Transmission by Shimroz123
2 answers 12 views

How the two winding transformer is linked ?

asked Aug 9, 2017 in Electrical Machine by Zeeshan
0 answers 20 views

A Phase shift transformer is designed to control 150 MVA on a 230 kV, 3 phase line. The phase angle is variable between zero and 15 deg. Calculate the approximate basic power rating of the transformer.  (A) 150 MVA (B) 56 MVA (C) 75 MVA (D) 750 MVA 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 14 views

Two resistance 100Ω ± 5Ω ± 15Ω are connected in series. If the errors are specified as standard deviations, the resultant error will be

asked Apr 1, 2018 in Electrical Engineering by Shimroz123
1 answer 15 views

 The number of parallel paths in the armature winding of a 4 -pole, wave connected d.c. machine having 28 coilside is : -  a) 28 b) 14 c) 4 d) 2

asked Apr 11, 2018 in Electrical Engineering by Shimroz123
0 answers 51 views

If the stator winding of a three-phase induction motor is delta connected, the rotor winding   (a) should be delta connected (b) should be star connected (c) should not be delta connected (d) may be delta or star connected 

asked Apr 10, 2018 in Electrical Engineering by Shimroz123
1 answer 148 views

A 50 Hz, 4 pole turboalternator rated at 20 MVA. 13.2 KV has an inertia constant H = 4 KW sec/KVA. The K.E. stored in the rotor at synchronous speed is

asked May 3, 2018 in Electric Power Transmission by Shimroz123
1 answer 15 views

A 3-phase star-connected 75 MVA, 25 kV 3-phase synchronous generator has a synchronous reactance of 1.0 p.u. The per unit value to a 90 MVA base and 30 kV is (A) 2/15 p.u. (B) 5/6 p.u. (C) 1.0 p.u. (D) 1.2 p.u.

asked Apr 25, 2018 in Electrical Engineering by Shimroz123

Welcome to electronics2electrical.com here you can ask questions related to electrical, electronics, mechanical, telecommunication, instrumentation, computer, mathematics, physics etc.
Be respectful to all the members. Do not copy and paste the answers from other websites which have copyright content. While asking question give full details about it.

Categories

Most popular tags

power motor dc circuit transformer voltage current used system phase resistance factor synchronous load ac energy induction electric generator series frequency between speed capacitor use electrical meter line difference control type mosfet transmission magnetic plant high single instrument bjt unit source advantages function diode and machine winding field define torque parallel amplifier supply shunt thyristor motors electricity arduino maximum time relay armature problem value on transformers types coil diagram state flow ratio material three formula starting direction theorem method emf operating efficiency digital wave microprocessor test instruments inductance loss measure operation connected signal low applications effect single-phase network temperature working constant losses different law wattmeter measuring compare controlled breaker drive device logic rc full switch flux wire resistivity disadvantages free of materials machines angle force converter conductor transistor gain open protection scr core measurement number bridge principle generators reactance circuits negative the friction iron loop short pole battery conservation steam resistors hysteresis computer using analog lines secondary station gate a rectifier inverter linear induced relays nuclear capacitance basic characteristics design direct work rotor electronics ammeter forces diesel damping rlc connection factors capacitors minimum insulation moving regulation running self systems air fault range main stability quality starter igbt eddy alternator ideal rl average 3-phase plants arc thermal error fuzzy biasing dielectric pressure balanced superposition errors copper rotation feedback impedance measured electronic electrons charge inductive transfer explain start off back curve over solar is three-phase tariff locomotive peak bias zener engineering commutator surge conductors rating universal potentiometer density permanent mechanical transducer capacity memory adc excitation two fuse pure harmonics application semiconductor inductor internal pmmc reaction welding resonance traction permeability breakers rms designed electromagnetic si generation brushes switching capacitive shaded rate 1 distribution resistor methods delta star oscillator reluctance simplification algebra 8085 boolean weston dynamometer insulating strength installation definition fuel heating earth units

8,471 questions

7,069 answers

134 comments

3,088 users

...