In a 3-insulator string voltage distribution system the ratio of capacitance between pin and earth to the self capacitance of each unit is 1/4. If the potential across the top unit is 8 kV, then the string voltage is

(A) 22.5 kV (B) 24 kV (C) 26 kV (D) 32.5 kV

1 Answer

0 votes
by

In a 3-insulator string voltage distribution system the ratio of capacitance between pin and earth to the self capacitance of each unit is 1/4. If the potential across the top unit is 8 kV, then the string voltage is 32.5 kV

Related questions

0 answers 35 views

A suspension insulator string has three units with ground capacitance of 0.2 C and self capacitance of C. Its string efficiency is (a) 75% (b) 78% (c) 80% (d) 85%

asked May 25, 2018 in Synchronous machine by Shimroz123
0 answers 65 views

What happens to the angle between current and voltage, when a small capacitance is added in series with a highly inductive circuit?  (A) Increases (B) Remains same as earlier angle (C) Decreases (D) Becomes indeterminant

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 19 views

A suspension type insulator has three units with self-capacitance C and ground capacitance of 0.2 C having a string efficiency of   (a) 80% (b) 82% (c)78% (d) 76% 

asked May 13, 2018 in Power system by Shimroz123
0 answers 41 views

A suspension type insulator has 2 units with self capacitance C and ground capacitance of 0.2 C. Each unit can withstand for a maximum voltage of 11 kV. Its string efficiency is  (A) 78% (B) 82% (C) 80% (D) 84%

asked Apr 28, 2018 in Power system by Shimroz123
1 answer 18 views

 To a highly inductive circuit, a small capacitance is added in series. The angle between voltage and current will _____.

asked May 29, 2018 in Capacitance by Shimroz123
1 answer 10 views

The non-uniform distribution of voltage across the units in a string of suspension type insulators is due to?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 10 views

In a string of suspension insulators, the voltage distribution across the different units of a string could be made uniform by the use of a grading ring, because it?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 19 views

A lightening arrester connected between the line and earth in a power system  (1) protects the terminal equipment against travelling surges (2) protects the transmission line against direct lightening strokes (3) suppresses high frequency oscillations in the line (4) reflects back the travelling wave approaching it

asked Apr 29, 2018 in Switchgear And Protection by Shimroz123
1 answer 23 views

The permissible voltage variation in transmission and distribution system is:  (A) ± 0.1% (B) ± 1% (C) ±10% (D) ± 25%

asked May 8, 2018 in Electrical Engineering by Shimroz123
1 answer 35 views

The number of insulator discs (each rated 11 kV) required in a suspension type insulator string of 220 kV line is 

asked May 8, 2018 in Electric Power Transmission by Shimroz123
1 answer 12 views

The third generation relays - digital relays - are the basis of distribution system automation because of their: a. Self fault diagnostic capabilities b. Computing capabilities c. Easy interface for remote communication d. All of the above

asked Sep 1, 2018 by Shimroz123
1 answer 21 views

At a particular instant, the R-phase voltage of a balanced 3-phase system is + 30 V, and the Y-phase voltage is – 90 V. The voltage of B-phase at that instant is (A) + 120 V (B) – 120 V (C) – 60 V (D) + 60 V

asked Apr 25, 2018 in Electrical Engineering by Shimroz123
1 answer 16 views

In a 3-phase 4-wire distribution system three unbalanced but equal magnitude impedances are connected between respective lines and neutral. The magnitude of current in the neutral conductor for RYB and RBY phase sequences are (A) zero (B) same (C) different (D) same in magnitude but differs in phase.

asked Apr 25, 2018 in Electrical Engineering by Shimroz123
1 answer 11 views

The three non -inductive loads of 5 kW, 3 kW and 2 kW are connected in a star network between R, Y and B phases and neutral. The line voltage is 400 V. The current in the neutral wire is nearly (a) 11 A (b) 14 A (c) 17 A (d) 21 A

asked Apr 25, 2018 in Electrical Engineering by Shimroz123
0 answers 12 views

The ratio of the primary to secondary voltage of a transformer is 2:1. The saving in the turns of weight of copper required if an autotransformer is used instead of two winding transformer is (1) 50% (2) 33.33% (3) 66.67% (4) 97% 

asked Apr 11, 2018 in Electrical Engineering by Shimroz123
1 answer 190 views

With neat diagram explain use of “reactive power controller” to reduce technical losses in transmission and distribution system.

asked Sep 22, 2018 in Energy Conservation And Audit by Shimroz123
1 answer 27 views

Two wattmeters are used to measure the power in a 3 -phase balanced system. What is the power factor of the load when one wattmeter reads twice the other ?  (a) 0 (b) 0.5 (c) 0.866 (d) 1

asked Apr 23, 2018 in Electrical Engineering by Zeeshan
1 answer 28 views

 A transformer has maximum efficiency at 3/4 full load. The ratio of its iron losses and full load copper loss is : -  a) 16/9 b) 4 / 3 c) 3/4 d) 9 /16

asked Apr 11, 2018 in Electrical Engineering by Shimroz123
1 answer 65 views

In a Y -connected circuit, between each line -voltage and the nearest phase - voltage, there is a phase -angle of: A. 0° B. 30° C. 60° D. 120°

asked Apr 12, 2018 in Electrical Engineering by Shimroz123
1 answer 27 views

A string of five resistors connected in series is connected across a 6 V battery. Zero voltage is measured across all the resistors except the third resistor. The voltage across the third resistor is: A. 0 V B. 1.2V C. 6V D. 0.6V

asked Apr 12, 2018 in Electrical Engineering by Shimroz123
0 answers 13 views

For a desirable transient response of a second order system, the damping ratio must be between (a) 0.4 and 0.8 (b) 0.8 and 1.0 (c) 0.3 and 0.5 (d) 0.2 and 0.4

asked May 25, 2018 in Control System by Shimroz123
1 answer 10 views

What happens to the capacitance if mica is inserted between the plates of an air capacitor? A) The capacitance increases B) The capacitance decreases C) The capacitance remains the same D) The capacitance becomes zero

asked Apr 29, 2018 in Electrical Engineering by Shimroz123
0 answers 63 views

What is the difference between a line voltage and low voltage control system?

asked Mar 10, 2018 in High voltage engineering by Quiz
1 answer 29 views

What is the difference between an insulator and a dielectric?

asked Mar 11, 2018 in Utilization of electrical energy by Quiz
1 answer 52 views

Explain following techniques related to energy conservation in transmission and distribution system. (i) By balancing phase currents (ii) Variable technical losses (I2R losses).

asked Sep 22, 2018 in Energy Conservation And Audit by Shimroz123
1 answer 11 views

Two wattmeter method is employed to measure power in a 3 -phase balanced system with the current coil connected in the A and C lines. The phase sequence is ABC. If the wattmeter with its current coil in A -phase line reads zero, then the power factor of the 3 -phase load will be

asked Apr 23, 2018 in Electrical Engineering by Shimroz123
1 answer 24 views

In a battery, the difference between the no-load voltage and the measured voltage output is called ________ A) Internal voltage B) Internal resistance C) External resistance D) All the above

asked Apr 29, 2018 in Electrical Engineering by Shimroz123
1 answer 74 views

The power consumed in a circuit element will be least when the phase difference between the current and voltage is?

asked Mar 24, 2018 in Electrical Engineering by Shimroz123
1 answer 659 views

State the working principle and operation of Automatic power factor controller used in Transmission and Distribution system.

asked Oct 3, 2018 in Energy Conservation And Audit by Shimroz123
1 answer 17 views

Two metallic blocks having masses in the ratio 2:3 are made to slide down a frictionless inclined plane starting from rest position. When the blocks reach the bottom of the inclined plane, they will have their kinetic energies in the ratio : (A) 2:3 (B) 3:5 (C) 3:2 (D) 7:4

asked Jun 14, 2018 in Mechanical Engineering by Shimroz123
0 answers 16 views

A 3 Phase, 60 Hz generator connected in Y connection, generates a line to line voltage of 23900 V. Calculate the peak line voltage.  (A) 13800 V (B) 33800 V (C) 42300 V (D) 23900 V 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 19 views

The function of the earth wire in an extra high voltage line is to?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 15 views

Explain the following energy conservation techniques: (i) By reducing I2R losses in Trans. system (ii) By optimizing distribution voltage.

asked Oct 3, 2018 in Energy Conservation And Audit by Shimroz123
0 answers 12 views

Earth resistance comprises of   A. Resistance of soil away from electrode.   B. Contact resistance between electrode and soil.   C. Resistance of metal electrode   (a) A only  (b) A and B only   (c) A and C only  (d) A, B and C together 

asked Apr 10, 2018 in Electrical Engineering by Shimroz123
1 answer 24 views

A single-phase transformer has a turns ratio of 1 :2 and is connected to a purely resistive load as shown in the figure. The magnetizing current drawn is 1A, and the secondary current is 1A. Ifcore losses and leakage reactances are neglected, the primary current is  A)1.41A B)2A C) 2.24A D)3A

asked May 20, 2018 in Transformer by Shimroz123
0 answers 11 views

If 27 J of energy is expended in moving 3 C of charge between two points, how much voltage is there between those two points? 

asked Jul 1 by Shimroz123
2 answers 68 views

Explain how technical losses can be reduced by use of energy efficient transformer in Transmission and Distribution system.

asked Oct 3, 2018 in Energy Conservation And Audit by Shimroz123
1 answer 13 views

In case of a 3-phase short-circuit fault in a system, the power fed into the system is   (a) Mostly reactive (b) Reactive only (c) Mostly active (d) Active and Reactive both equal 

asked May 13, 2018 in Electrical Engineering by Shimroz123
1 answer 458 views

List out the different technical losses that takes place in Transmission and Distribution system.

asked Oct 3, 2018 in Energy Conservation And Audit by Shimroz123
1 answer 30 views

A dot matrix printer takes 3 msec to point a character, and 1 msec for a space between two consecutive characters. If it prints 100 characters per line, its printing speed specifications in characters per second (cps) and time to print a line of characters are respectively  (a) 100 cps and 400 msec (b) 2500 cps and 0.04 sec (c) 250 cps and 40 msec (d) 250 cps and 0.4 sec

asked May 15, 2018 in Microprocessors and Microcontrollers by Shimroz123
1 answer 10 views

The rated voltage of a 3-phase power system is given as  A) rms phase voltage B) Peak phase voltage C) rms line to line voltage D) Peak line to line voltage

asked May 20, 2018 in Power system by Shimroz123
1 answer 152 views

For a 15-bus power system with 3 voltage controlled buses, the size of Jacobian matrix is

asked Apr 27, 2018 in Switchgear And Protection by Shimroz123
1 answer 18 views

A moving coil meter has a resistance of 3 Ω and gives full scale deflection with 30 mA. To measure voltage up to 300 V, the external resistance to be connected in series with the instrument is (A) 9997 Ω (B) 10000 Ω (C) 997 Ω (D) 10003 Ω

asked Apr 28, 2018 in Power Electronic Controlled Drives by Shimroz123
0 answers 96 views

The ‘transportation delays’ occurring in distribution system are detrimental to stability because they produce (a) attenuation (b) phase lag (c) both (a) and (b) (d) transients 

asked May 25, 2018 in Electric Power Distribution by Shimroz123
1 answer 446 views

A single core cable is designed to work for a single phase system with a peak voltage of 220 kV. The maximum permissible stress in the dielectric is not to exceed 20 kV/mm. For economical size, the overall core diameter of the cable is (A) 28.2 mm (B) 26.4 mm (C) 24.4 mm (D) 22.0 mm

asked Apr 28, 2018 in Electrical Engineering by Shimroz123
1 answer 84 views

The skin effect in conductors is due to non uniform distribution of current in it and major portion of current is near the _______ of conductor.  (1) Surface (2) Center (3) Complete cross section area (4) Axis

asked Apr 30, 2018 in Power system by Shimroz123
1 answer 51 views

The typical ratio of latching current to holding current in a 20A thyristor is : (A) 5.0 (B) 2.0 (C) 1.0 (D) 0.5

asked Apr 14, 2018 in Electrical Engineering by Shimroz123

Welcome to electronics2electrical.com here you can ask questions related to electrical, electronics, mechanical, telecommunication, instrumentation, computer, mathematics, physics etc.
Be respectful to all the members. Do not copy and paste the answers from other websites which have copyright content. While asking question give full details about it.

Categories

Most popular tags

power motor dc circuit transformer voltage current used system phase resistance factor synchronous load ac energy induction electric generator series frequency between speed capacitor use electrical meter line difference control type mosfet transmission magnetic plant high single instrument bjt unit source advantages function diode and machine winding field define torque parallel amplifier supply shunt thyristor motors electricity arduino maximum time relay armature problem value on transformers types coil diagram state flow ratio material three formula starting direction theorem method emf operating efficiency digital wave microprocessor test instruments inductance loss measure operation connected signal low applications effect single-phase network temperature working constant losses different law wattmeter measuring compare controlled breaker drive device logic rc full switch flux wire resistivity disadvantages free of materials machines angle force converter conductor transistor gain open protection scr core measurement number bridge principle generators reactance circuits negative the friction iron loop short pole battery conservation steam resistors hysteresis computer using analog lines secondary station gate a rectifier inverter linear induced relays nuclear capacitance basic characteristics design direct work rotor electronics ammeter forces diesel damping rlc connection factors capacitors minimum insulation moving regulation running self systems air fault range main stability quality starter igbt eddy alternator ideal rl average 3-phase plants arc thermal error fuzzy biasing dielectric pressure balanced superposition errors copper rotation feedback impedance measured electronic electrons charge inductive transfer explain start off back curve over solar is three-phase tariff locomotive peak bias zener engineering commutator surge conductors rating universal potentiometer density permanent mechanical transducer capacity memory adc excitation two fuse pure harmonics application semiconductor inductor internal pmmc reaction welding resonance traction permeability breakers rms designed electromagnetic si generation brushes switching capacitive shaded rate 1 distribution resistor methods delta star oscillator reluctance simplification algebra 8085 boolean weston dynamometer insulating strength installation definition fuel heating earth units
...