A 3-phase star-connected 75 MVA, 25 kV 3-phase synchronous generator has a synchronous reactance of 1.0 p.u. The per unit value to a 90 MVA base and 30 kV is

(A) 2/15 p.u. (B) 5/6 p.u. (C) 1.0 p.u. (D) 1.2 p.u.

1 Answer

0 votes
by

A 3-phase star-connected 75 MVA, 25 kV 3-phase synchronous generator has a synchronous reactance of 1.0 p.u. The per unit value to a 90 MVA base and 30 kV is 5/6 p.u.

Related questions

0 answers 549 views

A 30 MVA, 15 KV, 1500 rpm, 3 phase synchronous generator connected to a power grid has a synchronous reactance of 9 ohm per phase. If the exciting voltage is 12 kV (line to neutral) and the system voltage is 17.3 kV (line to line), Calculate the maximum power that generator can deliver before it falls out of step (losses synchronous).  (A) 39.952 MW (B) 78.349 MW (C) 16.67 MW (D) 112.89 MW

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 40 views

A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is (A) 0.85 Ω (B) 3.63 Ω (C) 36.3 Ω (D) 252 Ω

asked Apr 28, 2018 in Power system by Shimroz123
1 answer 46 views

A 100 MVA, 11 KV, 3-phase, 50 Hz, 8—pole synchronous generator has an inertia constant H equal to 4 seconds. The stored energy in the rotor of the generator at synchronous speed will be  A) 100 MJ B) 400 MJ C) 800 MJ D) 12.5 MJ

asked May 20, 2018 in Synchronous machine by Shimroz123
1 answer 115 views

A 500 MVA, 11 KV synchronous generator has 0.2 p.u. synchronous reactance. The p.u. synchronous reactance on the base values of 100 MVA and 22 KV is  A) 0.16 B) 0.01 C) 4.0 D) 0.25

asked May 17, 2018 in Synchronous machine by Shimroz123
1 answer 26 views

A 500 MW, 3-phase, Y-connected synchronous generator has a rated voltage of 21.5 kV at 0.85 p.f. The line current when operating at full load rated conditions will be  (A) 13.43 kA (B) 15.79 kA (C) 23.25 kA (D) 27.36 kA

asked May 17, 2018 in Synchronous machine by Shimroz123
0 answers 189 views

A 30 MVA, 13.2 KV synchronous generator has a solidly grounded neutral. Its positive, negative and zero sequence impedances are 0.30, 0.40 and 0.05 pu respectively. What value of reactance must be placed in the generator neutral so that the fault current for a line to ground fault of zero fault impedance shall not exceed the rated line current.  (A) 4.416 ohm (B) 8.8 ohm (C) 2.08 ohm (D) 10.2 ohm 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 28 views

The maximum possible power of a 3-phase synchronous motor with synchronous reactance 0.8 p.u. connected to a bus-bar of 1.0 p.u. and excitation adjusted to 1.2 p.u. is (A) 0.5 p.u. (B) 0.96 p.u. (C) 1.5 p.u. (D) 1.8 p.u.

asked Apr 25, 2018 in Electrical Engineering by Shimroz123
1 answer 19 views

A 20-MVA, 6.6-kV, 3-phase alternator is connected to a 3-phase transmission line. The per unit positive-sequence, negative-sequence and zero-sequence impedances of the alternator are j0.1, j0.1 and j0.04 respectively. The neutral of the alternator is connected to ground through an inductive reactor of j0.05 p.u. The per unit positive-, ... The voltage of the alternator neutral with respect to ground during the fault is  (A) 513.8 V (B) 889.9 V (C) 1112.0 V (D) 642.2 V

asked May 25, 2018 in Power system by Shimroz123
0 answers 45 views

For a balanced three phase star connected load for which line voltage is 230V and per phase resistance and reactance is 6 Ohm and 8 Ohm respectively. Calculate: 1) phase voltage 2) line current 3) power factor 4) total power absorbed

asked Aug 12, 2018 in Basic electrical and electronics engineering by Quiz
1 answer 118 views

A 60 Hz, 4 pole turbo generator rated 100 MVA, 13.8 KV has an inertia constant of 10 MJ/MVA. Find the stored energy in the rotor at synchronous speed.  (A) 10 MJ (B) 100 J (C) 1000 J (D) 1000 MJ 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 62 views

The corona loss of a 3-phase transmission line is 100 kW at 60 kV/phase and 25 kW at 50 kV/phase. The disruptive critical voltage is (A) 40 kV (B) 43.6 kV (C) 49.6 kV (D) 50 kV

asked Apr 25, 2018 in Electrical Engineering by Shimroz123
0 answers 76 views

A 3-phase circuit breaker is rated at 1250 A, 2000 MVA, 33 kV, 4s. Its making current capacity will be   (a) 35 kA (b) 89 kA (c) 79 kA (d) 69 kA

asked Apr 10, 2018 in Electrical Engineering by Shimroz123
0 answers 20 views

A Phase shift transformer is designed to control 150 MVA on a 230 kV, 3 phase line. The phase angle is variable between zero and 15 deg. Calculate the approximate basic power rating of the transformer.  (A) 150 MVA (B) 56 MVA (C) 75 MVA (D) 750 MVA 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 26 views

A generator is connected through a 20 MVA, 13.8/138 kV step down transformer, to a transmission line. At the receiving end of the line a load is supplied through a step down transformer of 10 MVA, 138/69 kV rating. A 0.72 pu. load, evaluated on load side transformer ratings as base values , is supplied from the above system. For system base values of 10 MVA and 69 kV in load circuit, the value of the load (in per unit) in generator will be (A) 36 (B) 1.44 (C) 0.72 (D) 0.18

asked May 25, 2018 in Power system by Shimroz123
1 answer 12 views

In a certain three -wire Y -connected generator, the phase voltages are 2 kV. The magnitudes of the line voltages will be: A. 2,000 V B. 6,000 V C. 666 V D. 3,464 V

asked Apr 12, 2018 in Electrical Engineering by Shimroz123
1 answer 59 views

A three-phase, 33 kV oil circuit breaker is rated 1200 A, 2000 MVA, 3 s. The symmetrical breaking current is  (A) 1200 A (B) 3600 A (C) 35 kA (D) 104.8 kA

asked May 25, 2018 in Power system by Shimroz123
1 answer 79 views

A 3-phase voltage source inverter operates in 180° conduction mode with a star connected resistive load. If input dc voltage is 100 V, then the peak to peak output line voltage is :

asked Apr 30, 2018 in Electrical Engineering by Shimroz123
0 answers 15 views

A 3-phase, 2 pole, 11 kV, 10000 kVA alternator has earthed neutral through a resistance of 7.0Ω. The machine has current balance protection which operates if out of balance current exceeds 20% of full load. Determine %age of winding protected against earth fault (1) 10.6% (2) 11.6% (3) 10.9% (4) 11.2% 

asked Apr 11, 2018 in Electrical Engineering by Shimroz123
0 answers 19 views

Two 3-phase synchronous generators with reactance 60% and 40% feed a fault current of 1200 A up to short-circuit fault point. The short-circuit current is (A) 1200 A (B) 2400 A (C) 4000 A (D) 5000 A 

asked Jun 4, 2018 in Synchronous machine by Shimroz123
0 answers 16 views

A 3 Phase, 60 Hz generator connected in Y connection, generates a line to line voltage of 23900 V. Calculate the peak line voltage.  (A) 13800 V (B) 33800 V (C) 42300 V (D) 23900 V 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 14 views

A 3-phase 11 kV generator feeds power to a constant power unity power factor load of 100 MW through a 3-phase transmission line. The line-to line voltage at the terminals of the machine is maintained constant at 11 kV. The per unit positive sequence impedance of the line based on 100 MVA and 11 kV is j0.2. The line to line voltage at the ... load to increase the line-to-line voltage at the load terminals to 11 kV is  (A) 100 MVAR (B) 10.1 MVAR (C) -100 MVAR (D) -10.1 MVAR

asked May 25, 2018 in Power system by Shimroz123
1 answer 63 views

The inertia constant of a 100 MVA, 11 kV water wheel generator is 4. The energy stored in the rotor at the synchronous speed is: A) 400 Mega Joule B) 400 Kilo Joule C) 25 Mega Joule D) 25 Kilo Joule

asked Jun 4, 2018 in Power system by Shimroz123
1 answer 21 views

A 3~phase synchronous motor, connected to infinite bus, is operating at no load at normal excitation. The field excitation of the motor is first decreased to zero and then increased in the reverse direction. The armature current of the synchronous motor will:  (1) Remain constant. (2) First decrease and then increase, (3) Increases continuously (4) First increase and then decreased

asked Apr 9, 2018 in Electrical Engineering by Shimroz123
1 answer 80 views

The locked rotor current in a 3-phase, star connected 15 , kW 4 , pole 230 V , 50 Hz induction motor at rated conditions is 50 A. Neglecting losses and magnetizing current, the approximate locked rotor line current drawn when the motor is connected to a 236 , V 57 Hz supply is  (A) 58.5 A (B) 45.0 A (C) 42.7 A (D) 55.6 A

asked May 17, 2018 in Electrical Machine by Shimroz123
1 answer 137 views

A 3-phase, 11 kv, 50 Hz, 200 kW load has a power factor of 0.8 lag. A delta connected 3-phase capacitor is used to improve the power factor to unity. The capacitance perphase of the capacitor in micro-farads is?

asked Mar 27, 2018 in Power system by Shimroz123
0 answers 27 views

A Reactor having an inductive reactance of 4 ohm is connected to the terminals of a 120 V AC generator. Calculate the power associated with the reactor.  (A) 3.6 kvar (B) 30 kvar (C) 7.2 kvar (D) 4.16 kvar 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
0 answers 241 views

A three phase breaker is rated at 2000 MVA, 33 kV, its making current is  (A) 70 kA (B) 89 kA (C) 49 kA (D) 35 kA 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 11 views

The three non -inductive loads of 5 kW, 3 kW and 2 kW are connected in a star network between R, Y and B phases and neutral. The line voltage is 400 V. The current in the neutral wire is nearly (a) 11 A (b) 14 A (c) 17 A (d) 21 A

asked Apr 25, 2018 in Electrical Engineering by Shimroz123
1 answer 42 views

A 50 Hz, 4-pole, 500 MVA, 22 kV turbo-generator is delivering rated megavolt amperes at 0.8 power factor. Suddenly a fault occurs reducing in electric power output by 40%. Neglect losses and assume constant power input to the shaft. The accelerating torque in the generator in MNm at the time of fault will be  (A) 1.528 (B) 1.018 (C) 0.848 (D) 0.509

asked May 25, 2018 in Power system by Shimroz123
1 answer 91 views

A transmission line has 1 P.0 impedance on a base of 11 KV, 100 MVA. On a base of 55 KV. it will have a P.0 impedance of

asked May 3, 2018 in Electric Power Transmission by Shimroz123
0 answers 29 views

A star arrangement of resistances has branch resistance of 3 Ω. The equivalent delta arrangement will have resistance of values (1) 9 Ω (2) 6 Ω (3) 3 Ω (4) 1 Ω

asked Apr 11, 2018 in Electrical Engineering by Shimroz123
1 answer 23 views

Two 3-phase, Y-connected alternators are to be paralleled to a set of common busbars. The armature has a per phase synchronous reactance of 1.7 Ohm and negligible armature resistance. The line voltage of the first machine is adjusted to 3300 V and that of the second machine is adjusted to 3200 V. The machine voltages are in phase at the ... are paralleled. Under this condition, the synchronizing current per phase will be  (A) 16.98 A (B) 29.41 A (C) 33.96 A (D) 58.82 A

asked May 17, 2018 in Alternator by Shimroz123
0 answers 69 views

The magnetizing reactance of a 4 kV/ 400 V, 50 Hz single-phase transformer on low voltage side is 35 Ω. The magnetizing reactance on the high voltage side is (A) 0.35 Ω (B) 3.5 Ω (C) 350 Ω (D) 3500 Ω

asked Jun 4, 2018 in Single phase transformer by Shimroz123
0 answers 18 views

Three single phase transformers are connected in delta-delta to step down a line voltage of 138 kV to 4160 V to supply power to a production plant. The plant draws 21 MW at a lagging power factor of 86 %. Calculate the apparent power furnished by the HV line.  (A) 24.4 MVA (B) 48.8 MVA (C) 12.2 MVA (D) 6.1 MVA 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
0 answers 28 views

Three resistances of 3 Ω each are connected in delta. The value of the resistances in the equivalent star is : (A) 27 (B) 9 (C) 1.5 (D) 1 Ω

asked Mar 31, 2018 in Electrical Engineering by Shimroz123
1 answer 148 views

A 50 Hz, 4 pole turboalternator rated at 20 MVA. 13.2 KV has an inertia constant H = 4 KW sec/KVA. The K.E. stored in the rotor at synchronous speed is

asked May 3, 2018 in Electric Power Transmission by Shimroz123
1 answer 16 views

A 100 kVA, 415 V(line), star-connected synchronous machine generates rated open circuit voltage of 415 V at a field current of 15 A. The short circuit armature current at a field current of 10 A is equal to the rated armature current. The per unit saturated synchronous reactance is  (A) 1.731 (B) 1.5 (C) 0.666 (D) 0.577

asked May 17, 2018 in Synchronous machine by Shimroz123
0 answers 13 views

 A single phase, 2000V alternator has armature resistance and reactance of 0.8 ohm and 4.94 ohm respectively. The voltage regulation of the alternator at 100A, 0.8 leading pf is (A) 7% (B) - 8.9% (C) - 6.3% (D) 0%

asked Apr 14, 2018 in Electrical Engineering by Shimroz123
1 answer 17 views

A three-phase star -connected load is operating at a power factor angle ϕ  with ϕ being the angle between

asked Apr 25, 2018 in Electrical Engineering by Shimroz123
0 answers 108 views

A single phase transformer rated at 3000 kVA, 69 kV 4.16 kV, 60 Hz has a total internal impedance Zp of 127 ohm, referred to the primary side. Calculate the primary current if the secondary is accidentally short circuited.  (A) 43.5 A (B) 543 A (C) 9006 A (D) 721 A 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 49 views

A 3 -stage ripple counter has Flip Flop with propagation delay of 25 nsec and pulse width of strobe input 10 nsec. Then the maximum operating frequency at which counter operates reliably is

asked May 3, 2018 in Power Electronics by Shimroz123
1 answer 6 views

Electrical fault between two windings of same phase of a generator having double star winding can be detected by the following protection in a generator:

asked May 22, 2018 in Induction Machine by Shimroz123
0 answers 17 views

The starting torque of a V/f controlled inverter-fed 3-phase induction motor operating at 25 Hz as compared with the same motor operating at 50 Hz is (A) more (B) double (C) equal (D) less 

asked Jun 4, 2018 in Electrical Machine by Shimroz123
1 answer 13 views

A 3-phase delta connected squirrel cage induction motor when started with a DOL starter has a starting torque of 600 NM. Its starting torque when star delta starter is used:

asked May 22, 2018 in Induction Machine by Shimroz123
0 answers 22 views

The per unit impedance of a circuit element is 0.30. If the base kV and base MVA are halved, then the new value of the per unit impedance of the circuit element will be:  (A) 0.3 (B) 0.6 (C) 0.003 (D) 0.006 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
0 answers 21 views

A synchronous machine connected to a power system grid bus-bar is operating as a generator. To make the machine operate as a motor, the  (1) direction of rotation is to be reversed (2) phase sequence is to be changed (3) field excitation is to be decreased (4) mechanical input is to be less than the losses at the shaft

asked Apr 10, 2018 in Electrical Engineering by Shimroz123
0 answers 52 views

A 220 kV, 3 phase transmission line is 60 km long. The resistance is 0.15 ohm / km and the inductance is 1.4 mH / km. Use the short line model to find the power at the sending end when the line is supplying a three phase load of 300 MVA at 0.8 pf lagging at 220 kV.  (A) 5.58MW (B) 80MW (C) 85.58MW (D) 74.42 MW 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 8 views

A two-phase generator is connected to two 90Ω load resistors. Each coil generates 120 V ac. The value of current flowing through the common neutral line will be: A. 1.33 A B. 1.88 A C. 2.66 A D. 1.77 A

asked Apr 12, 2018 in Electrical Engineering by Shimroz123
1 answer 27 views

A 12 -pole, 440 V, 50 Hz, 3 -phase synchronous motor takes a line current of 100 A at 0.8 pf leading. Neglecting losses, the torque developed will be

asked Apr 25, 2018 in Electrical Engineering by Shimroz123
1 answer 28 views

A three-phase transformer, connected in star-delta, is composed of three single-phase transformers, each rated 127/ 13.2 kV. The line-to-line voltage ratio for the three-phase transformer is: A) 220 / 13.2 kV B) 127 / 13.2 kV C) 127 / 220 kV D) 220 / 220 kV

asked Jun 4, 2018 in Three phase transformers by Shimroz123

Welcome to electronics2electrical.com here you can ask questions related to electrical, electronics, mechanical, telecommunication, instrumentation, computer, mathematics, physics etc.
Be respectful to all the members. Do not copy and paste the answers from other websites which have copyright content. While asking question give full details about it.

Categories

Most popular tags

power motor dc circuit transformer voltage current used system phase resistance factor synchronous load ac energy induction electric generator series frequency between speed capacitor use electrical meter line difference control type mosfet transmission magnetic plant high single instrument bjt unit source advantages function diode and machine winding field define torque parallel amplifier supply shunt thyristor motors electricity arduino maximum time relay armature problem value on transformers types coil diagram state flow ratio material three formula starting direction theorem method emf operating efficiency digital wave microprocessor test instruments inductance loss measure operation connected signal low applications effect single-phase network temperature working constant losses different law wattmeter measuring compare controlled breaker drive device logic rc full switch flux wire resistivity disadvantages free of materials machines angle force converter conductor transistor gain open protection scr core measurement number bridge principle generators reactance circuits negative the friction iron loop short pole battery conservation steam resistors hysteresis computer using analog lines secondary station gate a rectifier inverter linear induced relays nuclear capacitance basic characteristics design direct work rotor electronics ammeter forces diesel damping rlc connection factors capacitors minimum insulation moving regulation running self systems air fault range main stability quality starter igbt eddy alternator ideal rl average 3-phase plants arc thermal error fuzzy biasing dielectric pressure balanced superposition errors copper rotation feedback impedance measured electronic electrons charge inductive transfer explain start off back curve over solar is three-phase tariff locomotive peak bias zener engineering commutator surge conductors rating universal potentiometer density permanent mechanical transducer capacity memory adc excitation two fuse pure harmonics application semiconductor inductor internal pmmc reaction welding resonance traction permeability breakers rms designed electromagnetic si generation brushes switching capacitive shaded rate 1 distribution resistor methods delta star oscillator reluctance simplification algebra 8085 boolean weston dynamometer insulating strength installation definition fuel heating earth units

8,450 questions

7,047 answers

132 comments

3,085 users

...