The sending end and receiving end voltages of a three-phase transmission line are 10 kV/ph and 9.5 kV/ph, respectively. If the resistance drop is 150 V/ph and receiving end power factor is 0.8, the sending end power factor is

(A) 0.745 lagging (B) 0.775 lagging

(C) 0.8 lagging (D) 0.85 lagging
in Power system by

2 Answers

0 like 0 dislike

The sending end and receiving end voltages of a three-phase transmission line are 10 kV/ph and 9.5 kV/ph, respectively. If the resistance drop is 150 V/ph and receiving end power factor is 0.8, the sending end power factor is 0.775 lagging

by
0 like 0 dislike
Vscos¢s-Vrcos¢r=IR