A transmission line has 1 P.0 impedance on a base of 11 KV, 100 MVA. On a base of 55 KV. it will have a P.0 impedance of

1 Answer

0 votes
by

A transmission line has 1 P.0 impedance on a base of 11 KV, 100 MVA. On a base of 55 KV. it will have a P.0 impedance of 0.02 P.U

Related questions

1 answer 122 views

A 50Ω transmission line is terminated in an impedance of 20-j50. What will be the reflection coefficient? A) 0.69 B) 1.69 C) 6.9 D) 16.9 

asked Jun 18, 2018 in Electrical Engineering by Shimroz123
1 answer 43 views

For a short transmission line with r/x ratio of is 1.0, the regulation will be zero when the load power factor is

asked Apr 30, 2018 in Electrical Engineering by Shimroz123
1 answer 115 views

In a transmission line if booster transformers are to be used, preferred location will be  (A) At the receiving end (B) At the sending end (C) At the intermediate point (D) Anywhere in the line 

asked May 8, 2018 in Electric Power Transmission by Shimroz123
2 answers 95 views

The sending end and receiving end voltages of a three-phase transmission line are 10 kV/ph and 9.5 kV/ph, respectively. If the resistance drop is 150 V/ph and receiving end power factor is 0.8, the sending end power factor is (A) 0.745 lagging (B) 0.775 lagging (C) 0.8 lagging (D) 0.85 lagging

asked Apr 28, 2018 in Power system by Shimroz123
1 answer 30 views

Stability of a transmission line can be increased by

asked May 8, 2018 in Electric Power Transmission by Shimroz123
1 answer 19 views

A transmission line of 200 km has a certain A, B, C and D parameters. If the length is reduced to 60 km

asked Apr 29, 2018 in Electrical Engineering by Shimroz123
1 answer 22 views

The surge impedance for over head line is taken as  (1) 10-20 ohms (2) 50-60 ohms (3) 100-200 ohms (4) 1000-2000 ohms

asked May 1, 2018 in Switchgear And Protection by Shimroz123
1 answer 27 views

The sag of a transmission line is least affected by (A) Self weight of the conductor. (B) Temperature of the surrounding air. (C) Current through the conductor. (D) Ice deposited on the conductor.

asked May 8, 2018 in Electrical Engineering by Shimroz123
1 answer 23 views

Transmission efficiency of a transmission line increases with the

asked Apr 26, 2018 in Switchgear And Protection by Shimroz123
1 answer 115 views

A 500 MVA, 11 KV synchronous generator has 0.2 p.u. synchronous reactance. The p.u. synchronous reactance on the base values of 100 MVA and 22 KV is  A) 0.16 B) 0.01 C) 4.0 D) 0.25

asked May 17, 2018 in Synchronous machine by Shimroz123
0 answers 14 views

What are the losses in a transmission line?

asked Mar 10, 2018 in High voltage engineering by Quiz
1 answer 27 views

Series capacitive compensation in EHV transmission line is used to

asked Apr 29, 2018 in Power system by Shimroz123
1 answer 43 views

what is mean by medium transmission line ?

asked Aug 18, 2017 in Electrical Engineering by Zeeshan
1 answer 41 views

what is mean by short transmission line ?

asked Aug 18, 2017 in Electrical Engineering by Zeeshan
1 answer 41 views

what is mean by long transmission line ?

asked Aug 18, 2017 in Electrical Engineering by Zeeshan
1 answer 55 views

How many insulator disc used for 33 kV transmission voltage line?

asked Dec 5, 2017 in Electric Power Transmission by Quiz
1 answer 39 views

The rotor impedance of a slip ring induction motor is (0.1 + j0.6)Ohm/ ph . The resistance/ph to be inserted into rotor to get maximum torque at starting should be

asked May 3, 2018 in Electrical machine design by Shimroz123
0 answers 22 views

The per unit impedance of a circuit element is 0.30. If the base kV and base MVA are halved, then the new value of the per unit impedance of the circuit element will be:  (A) 0.3 (B) 0.6 (C) 0.003 (D) 0.006 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 21 views

An 800 kV transmission line has a maximum power transfer capacity of P. If it is operated at 400 kV with the series reactance unchanged, the new maximum power transfer capacity is approximately (A) P (B) 2P (C) P / 2 (D) P / 4

asked May 25, 2018 in Power system by Shimroz123
1 answer 46 views

A 100 MVA, 11 KV, 3-phase, 50 Hz, 8—pole synchronous generator has an inertia constant H equal to 4 seconds. The stored energy in the rotor of the generator at synchronous speed will be  A) 100 MJ B) 400 MJ C) 800 MJ D) 12.5 MJ

asked May 20, 2018 in Synchronous machine by Shimroz123
0 answers 430 views

The base kV and base MVA are halved and the per unit impedance new value is 0.5. The per unit impedance of the original circuit element is (A) 0.25 (B) 0.5 (C) 0.625 (D) 1.0 

asked Jun 4, 2018 in Power system by Shimroz123
1 answer 20 views

Which of the following is true for a bus impedance matrix ?  (A) It is sparse  (B) It has diagonally dominant elements  (C) It is the inverse of the bus admittance matrix  (D) Each element of it is the reciprocal of the corresponding element in admittance matrix

asked Apr 29, 2018 in Electric Power Transmission by Shimroz123
1 answer 50 views

If 3000 kW power is to be transmitted over a distance of 30 km, the desirable transmission voltage will be.  (A) 11 kV (B) 33 kV (C) 66 kV (D) 132 kV

asked May 8, 2018 in Electric Power Transmission by Shimroz123
1 answer 40 views

A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is (A) 0.85 Ω (B) 3.63 Ω (C) 36.3 Ω (D) 252 Ω

asked Apr 28, 2018 in Power system by Shimroz123
1 answer 18 views

For 11 kV line the capacitance per km per phase will be of the order of:  (A) 1 Farad (B) 0.1 Farad (C) 0.01 Farad (D) 0.01 microF

asked May 8, 2018 in Electric Power Transmission by Shimroz123
1 answer 63 views

The inertia constant of a 100 MVA, 11 kV water wheel generator is 4. The energy stored in the rotor at the synchronous speed is: A) 400 Mega Joule B) 400 Kilo Joule C) 25 Mega Joule D) 25 Kilo Joule

asked Jun 4, 2018 in Power system by Shimroz123
1 answer 23 views

For 11kV line the inductance per km per phase will be of the order of:  (A) 1 H (B) 0.1 H (C) 1 mH (D) 0.1 mH

asked May 8, 2018 in Electric Power Transmission by Shimroz123
1 answer 32 views

A 60 Hz, 320 km lossless line has Bending end voltage 1.0 p.u, The receiving end voltage on no load is?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 189 views

A 10 km long line has a characteristic impedance of 400 ohms. If line length is 100 km, the characteristic impedance is: (1) 4000 Ω (2) 400 Ω (3) 40 Ω (4) 4 Ω

asked May 28, 2018 in Electric Power Transmission by Shimroz123
1 answer 26 views

A 500 MW, 3-phase, Y-connected synchronous generator has a rated voltage of 21.5 kV at 0.85 p.f. The line current when operating at full load rated conditions will be  (A) 13.43 kA (B) 15.79 kA (C) 23.25 kA (D) 27.36 kA

asked May 17, 2018 in Synchronous machine by Shimroz123
1 answer 25 views

lf a travelling-wave travelling along a loss-less overhead line does not result in any reflection after it has reached the far end, then the far end of the line is

asked Apr 26, 2018 in Switchgear And Protection by Shimroz123
0 answers 22 views

An overhead transmission line has a span of 260 m. The weight of the conductor is 0.68 kg/m. The maximum allowable tension in the line is 1550 kg. Maximum sag of the line should be (a) 5.8 m (b) 4.6 m (c) 2.7 m (d) 3.7 m 

asked May 25, 2018 in Electric Power Transmission by Shimroz123
0 answers 15 views

Voltages phasors at the two terminals of a transmission line of length 70 km have a magnitude of 1.0 per unit but are 180 degree out of phase. Assuming that the maximum load current in the line is 1/5th of minimum 3-phase fault current. Which one of the following transmission line protection schemes ... pick up at 1.25 times the maximum load current (C) Pilot relaying system with directional comparison scheme (D) Pilot relaying system with segregated phase comparison scheme

asked May 25, 2018 in Power system by Shimroz123
1 answer 118 views

A 60 Hz, 4 pole turbo generator rated 100 MVA, 13.8 KV has an inertia constant of 10 MJ/MVA. Find the stored energy in the rotor at synchronous speed.  (A) 10 MJ (B) 100 J (C) 1000 J (D) 1000 MJ 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
0 answers 42 views

If 5000 kW power is transmitted at 220 kV in place of 11 kV, reduction in the value of electric current will be (a) 90% (b) 95% (c) 5% (d) 10% 

asked May 26, 2018 in Electric Power Transmission by Shimroz123
1 answer 15 views

The p.u. parameter for a 500 MVA machine on its own base are: inertia, M = 20 p.u. ; reactance, X = 2 p.u. The p.u. values of inertia and reactance on 100 MVA common base, respectively, are (A) 4, 0.4 (B) 100, 10 (C) 4, 10 (D) 100, 0.4

asked May 25, 2018 in Power system by Shimroz123
0 answers 56 views

A power system network with a capacity of 100 MVA has a source impedance of 10% at a point. The fault level at that point is (a) 1500 MVA (b) 1000 MVA (c) 500 MVA (d) 100 MVA

asked May 25, 2018 in Power system by Shimroz123
1 answer 137 views

A 3-phase, 11 kv, 50 Hz, 200 kW load has a power factor of 0.8 lag. A delta connected 3-phase capacitor is used to improve the power factor to unity. The capacitance perphase of the capacitor in micro-farads is?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 391 views

In which of the following transmission lines, the value of the Shunt admittance should be approximated to zero ? (A) A 66 kV 35 km long line (B) A 132 kV 200 km long line (C) A 220 kV 300 km long line (D) A 400 kV 500 km long line

asked May 8, 2018 in Electric Power Transmission by Shimroz123
1 answer 70 views

In case the height of transmission tower is increased, which of the following parameter is likely to change?  (A) Resistance (B) Inductance (C) Capacitance (D) None of the above

asked May 8, 2018 in Electric Power Transmission by Shimroz123
1 answer 82 views

The purpose of guard ring in transmission lines is to  (1) reduce the earth capacitance of the lowest unit. (2) increase the earth capacitance of the lowest unit. (3) reduce the transmission lines losses. (4) reduce the reactance of the line

asked May 1, 2018 in Electric Power Transmission by Shimroz123
1 answer 148 views

A 50 Hz, 4 pole turboalternator rated at 20 MVA. 13.2 KV has an inertia constant H = 4 KW sec/KVA. The K.E. stored in the rotor at synchronous speed is

asked May 3, 2018 in Electric Power Transmission by Shimroz123
1 answer 16 views

In a series resonant circuit, the impedance of the circuit is?

asked Mar 24, 2018 in Electrical Engineering by Shimroz123
1 answer 19 views

A 20-MVA, 6.6-kV, 3-phase alternator is connected to a 3-phase transmission line. The per unit positive-sequence, negative-sequence and zero-sequence impedances of the alternator are j0.1, j0.1 and j0.04 respectively. The neutral of the alternator is connected to ground through an inductive reactor of j0.05 p.u. The per unit positive-, ... The voltage of the alternator neutral with respect to ground during the fault is  (A) 513.8 V (B) 889.9 V (C) 1112.0 V (D) 642.2 V

asked May 25, 2018 in Power system by Shimroz123
1 answer 26 views

A generator is connected through a 20 MVA, 13.8/138 kV step down transformer, to a transmission line. At the receiving end of the line a load is supplied through a step down transformer of 10 MVA, 138/69 kV rating. A 0.72 pu. load, evaluated on load side transformer ratings as base values , is supplied from the above system. For system base values of 10 MVA and 69 kV in load circuit, the value of the load (in per unit) in generator will be (A) 36 (B) 1.44 (C) 0.72 (D) 0.18

asked May 25, 2018 in Power system by Shimroz123

Welcome to electronics2electrical.com here you can ask questions related to electrical, electronics, mechanical, telecommunication, instrumentation, computer, mathematics, physics etc.
Be respectful to all the members. Do not copy and paste the answers from other websites which have copyright content. While asking question give full details about it.

Categories

Most popular tags

power motor dc circuit transformer voltage current used system phase resistance factor synchronous load ac energy induction electric generator series frequency between speed capacitor use electrical meter line difference control type mosfet transmission magnetic plant high single instrument bjt unit source advantages function diode and machine winding field define torque parallel amplifier supply shunt thyristor motors electricity arduino maximum time relay armature problem value on transformers types coil diagram state flow ratio material three formula starting direction theorem method emf operating efficiency digital wave microprocessor test instruments inductance loss measure operation connected signal low applications effect single-phase network temperature working constant losses different law wattmeter measuring compare controlled breaker drive device logic rc full switch flux wire resistivity disadvantages free of materials machines angle force converter conductor transistor gain open protection scr core measurement number bridge principle generators reactance circuits negative the friction iron loop short pole battery conservation steam resistors hysteresis computer using analog lines secondary station gate a rectifier inverter linear induced relays nuclear capacitance basic characteristics design direct work rotor electronics ammeter forces diesel damping rlc connection factors capacitors minimum insulation moving regulation running self systems air fault range main stability quality starter igbt eddy alternator ideal rl average 3-phase plants arc thermal error fuzzy biasing dielectric pressure balanced superposition errors copper rotation feedback impedance measured electronic electrons charge inductive transfer explain start off back curve over solar is three-phase tariff locomotive peak bias zener engineering commutator surge conductors rating universal potentiometer density permanent mechanical transducer capacity memory adc excitation two fuse pure harmonics application semiconductor inductor internal pmmc reaction welding resonance traction permeability breakers rms designed electromagnetic si generation brushes switching capacitive shaded rate 1 distribution resistor methods delta star oscillator reluctance simplification algebra 8085 boolean weston dynamometer insulating strength installation definition fuel heating earth units
...