If the fault current is 6000 A, the relay plug setting is 150% and the CT ratio is 400/5, the plug setting multiplier will be

Please log in or register to answer this question.

1 Answer

0 votes
answered by

If the fault current is 6000 A, the relay plug setting is 150% and the CT ratio is 400/5, the plug setting multiplier will beĀ 10