Can you help by answering this question?

Why starter is required for starting an induction motor?

29 views
in Switchgear And Protection by
If the fault current is 6000 A, the relay plug setting is 150% and the CT ratio is 400/5, the plug setting multiplier will be

Your answer

Thanks for your contribution. Feel free to answer this question. Please avoid short answer. Your answer is most welcome. Be genuine.

Upload image or document:

Your name to display (optional):
Privacy: Your email address will only be used for sending these notifications.
Anti-spam verification:
Are you a robot ? (Y = Yes / N = No)
To avoid this verification in future, please log in or register.

1 Answer

0 votes
by

If the fault current is 6000 A, the relay plug setting is 150% and the CT ratio is 400/5, the plug setting multiplier will be 10

Related questions

1 answer 19 views

If the fault current is 2000 A, the relay setting is 50% and CT ratio is 400:5, the plug setting multiplier will be

asked Apr 29, 2018 in Power system by Shimroz123
1 answer 31 views

A relay has a rating of 5 A, 2.2 sec IDMT and a relay setting of 125% TMS = 0.6. It is connected to a supply circuit through a C.T. 400/5 ratio. The fault current is 4000 A. The operating current of the relay is

asked May 3, 2018 in Switchgear And Protection by Shimroz123
1 answer 42 views

If the % reactance upto the fault point is 20%, then the short circuit current will be

asked May 8, 2018 in Switchgear And Protection by Shimroz123
1 answer 21 views

In which fault the maximum short circuit current occurs?

asked Mar 19, 2018 in Switchgear And Protection by Shimroz123
1 answer 11 views

Current ratio

asked Jun 11 by Shimroz123
1 answer 67 views

Define: 1) voltage ratio, 2) current ratio, 3) transformation ratio of transformer.

asked Aug 12, 2018 in Basic electrical and electronics engineering by Quiz
1 answer 32 views

The eddy current loss in a dc generator is 400 W at 40 Hz frequency of reversal and constant flux density. When frequency is increased to 50 Hz., eddy current loss is :  (A) 256 W (B) 320 W (C) 500 W (D) 625 W

asked Apr 30, 2018 in Switchgear And Protection by Shimroz123
1 answer 16 views

Mention the precautions to be taken while connecting CT and PT in the circuit. 

asked Sep 6, 2018 by Shimroz123
1 answer 36 views

With fault clearing time, the transient stability of a power system

asked Apr 27, 2018 in Switchgear And Protection by Shimroz123
1 answer 21 views

Which is the most common type of fault?

asked Mar 19, 2018 in Switchgear And Protection by Shimroz123
1 answer 11 views

Write any four differences between CT and PT.

asked Sep 6, 2018 by Shimroz123
1 answer 30 views

If an unsymmetrical line to ground fault occurs at the secondary terminals of a delta/star, ungrounded transformer, then  (A) zero sequence currents are present on both sides of the transformer  (B) zero sequence currents are absent on both sides of the transformer  (C) zero sequence currents are present on the secondary side but not on the primary side  (D) zero sequence currents are present on the primary side but not on the secondary side

asked Apr 29, 2018 in Power system by Shimroz123
1 answer 86 views

To protect the power transformer (Y-Y with neutral grounded) against fault, what type of connection do the CTs have ?

asked Apr 27, 2018 in Switchgear And Protection by Shimroz123
1 answer 19 views

Given a unity feedback system with G(s)=k/s (s+4), the value of k for damping ratio of 0.5 is

asked May 8, 2018 in Control System by Zeeshan
2 answers 18 views

Why CT is never operated with an open secondary ?

asked Sep 6, 2018 by Shimroz123
1 answer 22 views

In the induction type directional over current relay, when a short-circuit occurs in the circuit (A) power flows in reverse direction (B) power flows in normal direction (C) directional power element does not operate (D) over current element is not energized

asked Apr 28, 2018 in Switchgear And Protection by Shimroz123
1 answer 16 views

If Poisson's ratio of a resistance wire strain gauge is 1.8, then neglecting piezo-resistive effects, its Gauge factor is :  (A) 2.8 (B) 2.6 (C) 4.6 (D) 3.6

asked Apr 30, 2018 in Electrical Engineering by Shimroz123
2 answers 38 views

The inrush current of a transformer at no load is maximum if the supply voltage is switched on  (1) at peak voltage value (2) at zero voltage value (3) at half voltage value (4) at 0.866 time voltage value

asked Apr 30, 2018 in Switchgear And Protection by Shimroz123
1 answer 21 views

A shunt fault is characterized by (A) Increase in current, frequency and pf (B) Increase in current, reduction in frequency and pf (C) Increase in current and frequency, reduction in pf (D) Decrease in current and frequency

asked Apr 28, 2018 in Power system by Shimroz123
1 answer 16 views

Plug Setting Multiplier (PSM) is the ratio of (a) secondary current/relay current (b) secondary current/primary current (c) secondary current/relay current setting (d) none of these

asked Apr 14, 2018 in Electrical Engineering by Shimroz123
1 answer 36 views

The ratio of limiting friction and normal reaction is known as?

asked Mar 22, 2018 in Engineering Mechanics by Shimroz123
0 answers 22 views

An IDMT relay of rating 5A, 2.2s and having a relay setting of 125% is connected to a supply circuit through a CT having a ratio of 400/5. The plug setting multiplier of IDMT relay in the event of fault current of 4000 A will be a. 5 b. 8 c. 10 d. 125

asked May 24, 2018 in Switchgear And Protection by Shimroz123
1 answer 11 views

If a relay fails to operate for a fault within its reach, it is said to

asked May 12, 2018 in Switchgear And Protection by Shimroz123
1 answer 78 views

 If the base current of a BJT is 250 µA and emitter current is 15 mA, then the common base current gain will be A) 0.98 B) 0.41 C) 59 D) 55  

asked Jun 18, 2018 in Bipolar Junction Transistor by Shimroz123
1 answer 20 views

Auto-transformer makes effective saving on copper and copper losses, when its transformation ratio is?

asked Mar 19, 2018 in Transformer by Shimroz123
1 answer 39 views

A dc chopper is fed from a constant voltage mains the duty ratio of chopper is progressively increased while the chopper feeds an RL load. The per unit current ripple would  (1) increase progressively  (2) decrease progressively  (3) decrease to a minimum value at α = 0.5 and then increase  (4) increase to a maximum value at α = 0.5 and then decrease

asked Apr 30, 2018 in Power Electronics by Shimroz123
1 answer 12 views

The Eb/V ratio of a d.c. motor is an indication of its?

asked Mar 26, 2018 in DC motor by Shimroz123
1 answer 20 views

The voltage transformation ratio of a transformer is equal to the ratio of?

asked Mar 19, 2018 in Transformer by Shimroz123
1 answer 28 views

ln HRC fuse the time between cut-off and final current zero is called

asked Apr 26, 2018 in Switchgear And Protection by Shimroz123
1 answer 91 views

Two bulbs of 500 W and 200 W rated at 250 V will have resistance ratio as?

asked Mar 25, 2018 in Basic concepts by Shimroz123
1 answer 32 views

Ratio of the rotor reactance X to the rotor resistance R for a two-phase servo motor (A) is equal to that of a normal induction motor (B) is less than that of a normal induction motor (C) is greater than that of a normal induction motor (D) may be less or greater than that of a normal induction motor

asked Apr 28, 2018 in Electronics Engineering by Shimroz123
1 answer 22 views

The operating point of a protective current transformer is near the

asked May 8, 2018 in Switchgear And Protection by Shimroz123
1 answer 83 views

The ratio of the width to the height of the picture frame is called as A) Rastar B) Aspect Ratio C) Length Ratio D) Efficiency  

asked Jun 18, 2018 in Electrical Engineering by Shimroz123
1 answer 13 views

The ratio of full -load volt-amperes to short-circuit volt-amperes is equal to :

asked Apr 30, 2018 in Electrical Engineering by Shimroz123
1 answer 27 views

Specific energy consumption of an electric train is the ratio between (A) Specific energy output at driving wheels and efficiency of the traction motor (B) Specific energy output at driving wheels and efficiency of the transmission gear (C) Specific energy output of driving motor and efficiency of the driving wheels (D) Specific energy output at driving wheels and efficiency of the (motor + transmission gear)

asked Apr 28, 2018 in Power Electronic Controlled Drives by Shimroz123
1 answer 21 views

The ratio of mass of proton to that of electron is nearly?

asked Mar 25, 2018 in Basic concepts by Shimroz123
1 answer 41 views

The ratio of active power to apparent power is known as____ factor.

asked Mar 25, 2018 in Electrical Engineering by Shimroz123
1 answer 24 views

Use of auto-transformer is economical when the transformation ratio is?

asked Mar 19, 2018 in Transformer by Shimroz123
1 answer 49 views
1 answer 69 views

In a biased differential relay, the bias is defined as the ratio of  A) Number of turns of restraining coil and operating coil B) Operating coil current and restraining coil current C) Faulteurrent and operating coil current D) Fault current and restraining coil current

asked May 20, 2018 in Switchgear And Protection by Shimroz123
1 answer 43 views

Voltage ratio

asked Jun 11 by Shimroz123

Welcome to electronics2electrical.com here you can ask questions related to electrical, electronics, mechanical, telecommunication, instrumentation, computer, mathematics, physics etc.
Be respectful to all the members. Do not copy and paste the answers from other websites which have copyright content. While asking question give full details about it.

Categories

Most popular tags

power motor dc circuit transformer voltage current used system phase resistance factor synchronous load ac energy induction electric generator series frequency between speed capacitor use electrical meter line difference control type mosfet transmission magnetic plant high single instrument bjt unit source advantages function diode and machine winding field define torque parallel amplifier supply shunt thyristor motors electricity arduino maximum time relay armature problem value on transformers types coil diagram state flow ratio material three formula starting direction theorem method emf operating efficiency digital wave microprocessor test instruments inductance loss measure operation connected signal low applications effect single-phase network temperature working constant losses different law wattmeter measuring compare controlled breaker drive device logic rc full switch flux wire resistivity disadvantages free of materials machines angle force converter conductor transistor gain open protection scr core measurement number bridge principle generators reactance circuits negative the friction iron loop short pole battery conservation steam resistors hysteresis computer using analog lines secondary station gate a rectifier inverter linear induced relays nuclear capacitance basic characteristics design direct work rotor electronics ammeter forces diesel damping rlc connection factors capacitors minimum insulation moving regulation running self systems air fault range main stability quality starter igbt eddy alternator ideal rl average 3-phase plants arc thermal error fuzzy biasing dielectric pressure balanced superposition errors copper rotation feedback impedance measured electronic electrons charge inductive transfer explain start off back curve over solar is three-phase tariff locomotive peak bias zener engineering commutator surge conductors rating universal potentiometer density permanent mechanical transducer capacity memory adc excitation two fuse pure harmonics application semiconductor inductor internal pmmc reaction welding resonance traction permeability breakers rms designed electromagnetic si generation brushes switching capacitive shaded rate 1 distribution resistor methods delta star oscillator reluctance simplification algebra 8085 boolean weston dynamometer insulating strength installation definition fuel heating earth units

8,483 questions

7,081 answers

134 comments

3,088 users

...