16 views
in Transformer by
In a transformer, zero voltage regulation at full load is 

 (a)Not possible 

 (b) Possible at unity power factor load 

 (c) Possible at leading power factor load 

 (d) Possible at lagging power factor load

Your answer

Thanks for your contribution. Feel free to answer this question. Please avoid short answer. Your answer is most welcome. Be genuine.

Upload image or document:

Your name to display (optional):
Privacy: Your email address will only be used for sending these notifications.
Anti-spam verification:
Are you a robot ? (Y = Yes / N = No)
To avoid this verification in future, please log in or register.

1 Answer

0 votes
by

In a transformer, zero voltage regulation at full load is Possible at leading power factor load 

Related questions

1 answer 20 views

In a transformer the voltage regulation will be zero when it operates at (A) unity p.f. (B) leading p.f. (C) lagging p.f. D) zero p.f. leading.

asked May 22, 2018 in Transformer by Shimroz123
1 answer 30 views

A two -winding single phase transformer has a voltage regulation of 4.5% at full - load and unity power -factor. At full -load and 0.80 lagging power-factor, the voltage regulation will be: (A) 4.5% (B) less than 4.5% (C) more than 4.5% (D) none of the above

asked Apr 11, 2018 in Electrical Engineering by Shimroz123
1 answer 16 views

The dc motor, which can provide zero speed regulation at full load without any controller is  (A) series (B) shunt (C) cumulative compound (D) differential compound

asked May 17, 2018 in DC motor by Shimroz123
1 answer 21 views

Full load copper loss in a transformer is 1600 watts. At half load the copper loss will be: A) 6400 watt B) 1600 watt C) 800 watt D) 400 watt

asked Jun 4, 2018 in Transformer by Shimroz123
0 answers 30 views

The voltage regulation of a transformer, with ohmic drop 2% and reactance drop 5% of the voltage at 0.8 lagging power factor, will be (a) 7% (b) 5.6% (c) 5.3% (d) 4.6%

asked May 25, 2018 in Transformer by Shimroz123
0 answers 5 views

Transformer zero voltage regulation occurs at (1) Unity power factor (2) Leading power factor (3) Lagging power factor (4) Zero power factor leading 

asked Apr 11, 2018 in Electrical Engineering by Shimroz123
1 answer 17 views

A simple phase transformer has a maximum efficiency of 90% at full load and unity power factor. Efficiency at half load at the same power factor is  (A) 86.7% (B) 88.26% (C) 88.9% (D) 87.8%

asked May 17, 2018 in Transformer by Shimroz123
1 answer 17 views

A single-phase, 50 kVA, 250 V/500 V two winding transformer has an efficiency of 95% at full load, unity power factor. If it is re-configured as a 500 V/750 V auto-transformer, its efficiency at its new rated load at unity power factor will be  (A) 95.752% (B) 97.851% (C) 98.276% (D) 99.241%

asked May 17, 2018 in Transformer by Shimroz123
1 answer 27 views

A transformer has negative voltage regulation when its load power factor is   (1) Zero (2) Unity (3) Leading (4) Lagging

asked Apr 30, 2018 in Power system by Shimroz123
1 answer 13 views

A good voltage regulation of a transformer means?

asked Mar 19, 2018 in Transformer by Shimroz123
1 answer 15 views

Negative voltage regulation is indicative that the load is?

asked Mar 19, 2018 in Transformer by Shimroz123
1 answer 21 views

Minimum voltage regulation occurs when the power factor of the load is?

asked Mar 19, 2018 in Transformer by Shimroz123
1 answer 13 views

A 500 kVA, 3-phase transformer has iron losses of 300 W and full load copper losses of 600 W. The percentage load at which the transformer is expected to have maximum efficiency is  (A) 50.0% (B) 70.7% (C) 141.4% (D) 200.0%

asked May 17, 2018 in Transformer by Shimroz123
1 answer 15 views

In a given transformer for a given applied voltage, losses which remain constant irrespective of load changes are?

asked Mar 19, 2018 in Transformer by Shimroz123
1 answer 32 views

A transformer operates 24 hours day at full -load. It's full -load efficiency is :  (A) equal all day efficiency (B) more than all -day efficiency (C) less than all -day efficiency (D) equal to maximum efficiency

asked Apr 30, 2018 in Electrical Engineering by Shimroz123
0 answers 19 views

The efficiency of a transformer at full load 0.8 p.f lagging is 90%. Its efficiency at full load 0.8 p.f leading will be (1) Less than 90% (2) More than 90% (3) 90% (4) None of these 

asked Apr 11, 2018 in Electrical Engineering by Shimroz123
1 answer 28 views

 A transformer has maximum efficiency at 3/4 full load. The ratio of its iron losses and full load copper loss is : -  a) 16/9 b) 4 / 3 c) 3/4 d) 9 /16

asked Apr 11, 2018 in Electrical Engineering by Shimroz123
2 answers 73 views

 The no-load current drawn by transformer is usually what per cent of the full-load current ?

asked Mar 27, 2018 in Transformer by Shimroz123
1 answer 43 views

For a short transmission line with r/x ratio of is 1.0, the regulation will be zero when the load power factor is

asked Apr 30, 2018 in Electrical Engineering by Shimroz123
1 answer 13 views

If the secondary turns of a transformer are doubled and at the same time primary voltage is reduced to half then the secondary voltage will

asked May 15, 2018 in Transformer by Shimroz123
1 answer 42 views

At full -load of a transformer, the iron loss and copper loss are 3000 W and 4000 W respectively. Then total loss at maximum efficiency is :  (A) 7000 W (B) 6000 W (C) 8000 W (D) 4000 W

asked Apr 30, 2018 in Electrical Engineering by Shimroz123
1 answer 200 views

A 400/200 volts transformer has pu impedance of 0.05. The HV side voltage required to circulate full load current during short circuit test is

asked Apr 25, 2018 in Electrical Engineering by Shimroz123
1 answer 11 views

A ferro resonant transformer regulation is also known as?

asked Mar 19, 2018 in Transformer by Shimroz123
1 answer 23 views

For a constant load current, transformer maximum efficiency occurs at   (a) any power factor (b) zero power factor leading (c) zero power factor lagging (d) unity power factor 

asked May 13, 2018 in Transformer by Shimroz123
1 answer 30 views

For a transformer, operating at constant load current, maximum efficiency will occur at?

asked Mar 19, 2018 in Transformer by Shimroz123
2 answers 38 views

The inrush current of a transformer at no load is maximum if the supply voltage is switched on  (1) at peak voltage value (2) at zero voltage value (3) at half voltage value (4) at 0.866 time voltage value

asked Apr 30, 2018 in Switchgear And Protection by Shimroz123
0 answers 13 views

The voltage regulation for 0.95 lead pf is zero for an alternator. If so, the voltage regulation for 0.9 lead pf with all other conditions remaining same will be (A) Positive (B) Negative (C) Zero (D) Insufficient data

asked Apr 14, 2018 in Electrical Engineering by Shimroz123
1 answer 24 views

A single-phase transformer has a turns ratio of 1 :2 and is connected to a purely resistive load as shown in the figure. The magnetizing current drawn is 1A, and the secondary current is 1A. Ifcore losses and leakage reactances are neglected, the primary current is  A)1.41A B)2A C) 2.24A D)3A

asked May 20, 2018 in Transformer by Shimroz123
1 answer 25 views

In a step-down transformer, there is a change of 15 A in the load current. This results in change of supply current of?

asked Mar 19, 2018 in Transformer by Shimroz123
1 answer 5 views

What will be the efficiency when the transformer operates at unity power factor and 60% of full load 

asked Sep 1, 2018 by Shimroz123
1 answer 8 views

If the no load voltage of a certain generator is 220V and the rated load voltage is 200V, then the voltage regulation is: a. 1% b. 10% c. 20V d. 9%

asked Sep 1, 2018 by Shimroz123
0 answers 26 views

The maximum flux in a transformer is φm when primary voltage is V and the frequency is f. If the primary voltage is 2 V and frequency is f/2, the flux will be (a) 4 φm (b) 0.25 φm (c) φm (d) 0.5 φm

asked May 25, 2018 in Transformer by Shimroz123
1 answer 13 views

In a transformer, low voltage winding is placed near the core in case of concentric windings so as to  1. Reduce the leakage flux 2. Reduce the insulation requirement 3. Reduce the risk of voltage shock in case of insulation breakdown 4. Reduce the core loss   From these, the correct answer is (a) 1, 2, 3 (b) 2, 3, 4 (c) 1, 2, 3, 4 (d) 2, 3

asked May 13, 2018 in Transformer by Shimroz123
1 answer 15 views

In a 2 kW, 200 V, 1000 rpm. DC series motor the torque at full load was found to be 0.3 N -m. The torque at half full load in N -m is :

asked Apr 29, 2018 in Electrical Machine by Shimroz123
1 answer 37 views

A 150 kW electric motor has an efficiency of 92 %, when it operates at full load. Calculate the losses in the machine.  (A) 92 kW (B) 150 kW (C) 163 kW (D) 13 kW 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 18 views

A synchronous generator is feeding a zero power factor (lagging) load at rated current. The armature reaction is  (A) magnetizing (B) demagnetizing (C) cross-magnetizing (D) ineffective

asked May 17, 2018 in Synchronous machine by Shimroz123
1 answer 4 views

Which losses in a transformer varies significantly with load  a. Hysteresis losses b. Eddy current losses c. Copper losses d. Core losses 

asked May 17, 2018 in Transformer by Shimroz123
1 answer 19 views
1 answer 15 views

In a full wave rectifier circuit using centre tapped transformer, the peak voltage across half of the secondary winding is 30 V. Then PIV is: (1) 30 V (2) 60 V (3) 15 V (4) 10 V

asked May 28, 2018 in Electronics Engineering by Shimroz123
0 answers 23 views

The output voltage of a battery drops from 100 V with zero load current to 80 V when load current is 2 A. The internal resistance of the battery is (a) 10 Ω (b) 20 Ω (c) 40 Ω (d) 50 Ω

asked May 25, 2018 in Battery by Shimroz123
1 answer 9 views

Identify the increasing order of voltage regulation of the following dc generators a same load :  (A) differential compound, shunt and under compound  (B) shunt, differential compound and under compound  (C) under compound, shunt and differential compound  (D) shunt, under compound and differential compound

asked Apr 30, 2018 in Electrical Machine by Shimroz123
0 answers 24 views

A single phase 230 V/ 150 V , 1 kVA, 50 Hz transformer is supplied by 230 V AC supply. Find the full load primary and secondary current. 

asked Sep 1, 2018 by Quiz

Welcome to electronics2electrical.com here you can ask questions related to electrical, electronics, mechanical, telecommunication, instrumentation, computer, mathematics, physics etc.
Be respectful to all the members. Do not copy and paste the answers from other websites which have copyright content. While asking question give full details about it.

Categories

Most popular tags

power motor dc circuit transformer voltage current used system phase resistance factor synchronous load ac energy induction electric generator series frequency between speed capacitor use electrical meter line difference control type mosfet transmission magnetic plant high single instrument bjt unit source advantages function diode and machine winding field define torque parallel amplifier supply shunt thyristor motors electricity arduino maximum time relay armature problem value on transformers types coil diagram state flow ratio material three formula starting direction theorem method emf operating efficiency digital wave microprocessor test instruments inductance loss measure operation connected signal low applications effect single-phase network temperature working constant losses different law wattmeter measuring compare controlled breaker drive device logic rc full switch flux wire resistivity disadvantages free of materials machines angle force converter conductor transistor gain open protection scr core measurement number bridge principle generators reactance circuits negative the friction iron loop short pole battery conservation steam resistors hysteresis computer using analog lines secondary station gate a rectifier inverter linear induced relays nuclear capacitance basic characteristics design direct work rotor electronics ammeter forces diesel damping rlc connection factors capacitors minimum insulation moving regulation running self systems air fault range main stability quality starter igbt eddy alternator ideal rl average 3-phase plants arc thermal error fuzzy biasing dielectric pressure balanced superposition errors copper rotation feedback impedance measured electronic electrons charge inductive transfer explain start off back curve over solar is three-phase tariff locomotive peak bias zener engineering commutator surge conductors rating universal potentiometer density permanent mechanical transducer capacity memory adc excitation two fuse pure harmonics application semiconductor inductor internal pmmc reaction welding resonance traction permeability breakers rms designed electromagnetic si generation brushes switching capacitive shaded rate 1 distribution resistor methods delta star oscillator reluctance simplification algebra 8085 boolean weston dynamometer insulating strength installation definition fuel heating earth units

8,471 questions

7,069 answers

134 comments

3,088 users

...