A 500 MW, 3-phase, Y-connected synchronous generator has a rated voltage of 21.5 kV at 0.85 p.f. The line current when operating at full load rated conditions will be 

(A) 13.43 kA (B) 15.79 kA (C) 23.25 kA (D) 27.36 kA

Know someone who can answer this question ? Share this on Facebook, Twitter, Whatsapp

← Prev Question Next Question →

1 Answer

0 like 0 dislike
by

A 500 MW, 3-phase, Y-connected synchronous generator has a rated voltage of 21.5 kV at 0.85 p.f. The line current when operating at full load rated conditions will be 15.79 kA