Forward and reverse motor control panel

46 views
in Synchronous machine by
A 100 MVA, 11 KV, 3-phase, 50 Hz, 8—pole synchronous generator has an inertia constant H equal to 4 seconds. The stored energy in the rotor of the generator at synchronous speed will be 

A) 100 MJ B) 400 MJ C) 800 MJ D) 12.5 MJ

Your answer

Thanks for your contribution. Feel free to answer this question. Please avoid short answer. Your answer is most welcome. Be genuine.

Upload image or document:

Your name to display (optional):
Privacy: Your email address will only be used for sending these notifications.
Anti-spam verification:
Are you a robot ? (Y = Yes / N = No)
To avoid this verification in future, please log in or register.

1 Answer

0 votes
by

A 100 MVA, 11 KV, 3-phase, 50 Hz, 8—pole synchronous generator has an inertia constant H equal to 4 seconds. The stored energy in the rotor of the generator at synchronous speed will be 400 MJ

Related questions

1 answer 118 views

A 60 Hz, 4 pole turbo generator rated 100 MVA, 13.8 KV has an inertia constant of 10 MJ/MVA. Find the stored energy in the rotor at synchronous speed.  (A) 10 MJ (B) 100 J (C) 1000 J (D) 1000 MJ 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 148 views

A 50 Hz, 4 pole turboalternator rated at 20 MVA. 13.2 KV has an inertia constant H = 4 KW sec/KVA. The K.E. stored in the rotor at synchronous speed is

asked May 3, 2018 in Electric Power Transmission by Shimroz123
1 answer 64 views

The inertia constant of a 100 MVA, 11 kV water wheel generator is 4. The energy stored in the rotor at the synchronous speed is: A) 400 Mega Joule B) 400 Kilo Joule C) 25 Mega Joule D) 25 Kilo Joule

asked Jun 4, 2018 in Power system by Shimroz123
1 answer 137 views

A 3-phase, 11 kv, 50 Hz, 200 kW load has a power factor of 0.8 lag. A delta connected 3-phase capacitor is used to improve the power factor to unity. The capacitance perphase of the capacitor in micro-farads is?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 27 views

A 12 -pole, 440 V, 50 Hz, 3 -phase synchronous motor takes a line current of 100 A at 0.8 pf leading. Neglecting losses, the torque developed will be

asked Apr 25, 2018 in Electrical Engineering by Shimroz123
1 answer 14 views

A 3-phase 11 kV generator feeds power to a constant power unity power factor load of 100 MW through a 3-phase transmission line. The line-to line voltage at the terminals of the machine is maintained constant at 11 kV. The per unit positive sequence impedance of the line based on 100 MVA and 11 kV is j0.2. The line to line voltage at the ... load to increase the line-to-line voltage at the load terminals to 11 kV is  (A) 100 MVAR (B) 10.1 MVAR (C) -100 MVAR (D) -10.1 MVAR

asked May 25, 2018 in Power system by Shimroz123
1 answer 42 views

A 50 Hz, 4-pole, 500 MVA, 22 kV turbo-generator is delivering rated megavolt amperes at 0.8 power factor. Suddenly a fault occurs reducing in electric power output by 40%. Neglect losses and assume constant power input to the shaft. The accelerating torque in the generator in MNm at the time of fault will be  (A) 1.528 (B) 1.018 (C) 0.848 (D) 0.509

asked May 25, 2018 in Power system by Shimroz123
1 answer 115 views

A 500 MVA, 11 KV synchronous generator has 0.2 p.u. synchronous reactance. The p.u. synchronous reactance on the base values of 100 MVA and 22 KV is  A) 0.16 B) 0.01 C) 4.0 D) 0.25

asked May 17, 2018 in Synchronous machine by Shimroz123
0 answers 552 views

A 30 MVA, 15 KV, 1500 rpm, 3 phase synchronous generator connected to a power grid has a synchronous reactance of 9 ohm per phase. If the exciting voltage is 12 kV (line to neutral) and the system voltage is 17.3 kV (line to line), Calculate the maximum power that generator can deliver before it falls out of step (losses synchronous).  (A) 39.952 MW (B) 78.349 MW (C) 16.67 MW (D) 112.89 MW

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 15 views

A 3-phase star-connected 75 MVA, 25 kV 3-phase synchronous generator has a synchronous reactance of 1.0 p.u. The per unit value to a 90 MVA base and 30 kV is (A) 2/15 p.u. (B) 5/6 p.u. (C) 1.0 p.u. (D) 1.2 p.u.

asked Apr 25, 2018 in Electrical Engineering by Shimroz123
1 answer 16 views

The synchronous speed for the seventh space harmonic mmf wave of a 3-phase, 8-pole, 50 Hz induction machine is  (A) 107.14 rpm in forward direction (B) 107.14 rpm in reverse direction (C) 5250 rpm in forward direction (D) 5250 rpm in reverse direction

asked May 17, 2018 in Induction Machine by Shimroz123
1 answer 26 views

A 500 MW, 3-phase, Y-connected synchronous generator has a rated voltage of 21.5 kV at 0.85 p.f. The line current when operating at full load rated conditions will be  (A) 13.43 kA (B) 15.79 kA (C) 23.25 kA (D) 27.36 kA

asked May 17, 2018 in Synchronous machine by Shimroz123
0 answers 15 views

A 3-phase, 2 pole, 11 kV, 10000 kVA alternator has earthed neutral through a resistance of 7.0Ω. The machine has current balance protection which operates if out of balance current exceeds 20% of full load. Determine %age of winding protected against earth fault (1) 10.6% (2) 11.6% (3) 10.9% (4) 11.2% 

asked Apr 11, 2018 in Electrical Engineering by Shimroz123
1 answer 62 views

If the inertia constant H of a machine of 200 MVA is 2 p.u., its value corresponding to 400 MVA will be   (a) 4 p.u. (b) 2 p.u. (c) 1.0 p.u. (d) 0.5 p.u. 

asked May 13, 2018 in Electrical Engineering by Shimroz123
1 answer 95 views

A transmission line has 1 P.0 impedance on a base of 11 KV, 100 MVA. On a base of 55 KV. it will have a P.0 impedance of

asked May 3, 2018 in Electric Power Transmission by Shimroz123
0 answers 52 views

A dominant pole compensated op-amp has openloop gain of 100 dB and -3 dB bandwidth of 50 Hz. If it is connected as inverting amplifier for a gain of 20 dB the -3 dB bandwidth is about  A) 500 kHz B) 50 kHz C) 5 kHz D) 500 Hz

asked Apr 5, 2018 in Electronics Engineering by Shimroz123
2 answers 58 views

The synchronous speed of an 8 pole induction motor supplied power from a 50 Hz source will be ?

asked Dec 31, 2017 in Electrical Engineering by Quiz
1 answer 29 views

A 3 phase, 400 volts, 50 Hz, 100 kW, 4 pole squirrel cage induction motor with a rated slip of 2% will have a rotor speed of: (A) 1500 rpm (B) 1470 rpm (C) 1530 rpm (D) 1570 rpm

asked Apr 11, 2018 in Computer Engineering by Shimroz123
0 answers 189 views

A 30 MVA, 13.2 KV synchronous generator has a solidly grounded neutral. Its positive, negative and zero sequence impedances are 0.30, 0.40 and 0.05 pu respectively. What value of reactance must be placed in the generator neutral so that the fault current for a line to ground fault of zero fault impedance shall not exceed the rated line current.  (A) 4.416 ohm (B) 8.8 ohm (C) 2.08 ohm (D) 10.2 ohm 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 34 views

A balanced three-phase, 50 Hz voltage is applied to a 3 phase, 4 pole, induction motor. When the motor is delivering rated output, the slip is found to be 0.05. The speed of the rotor m.m.f. relative to the rotor structure is: (A) 1500 r.p.m. (B) 1425 r.p.m. (C) 25 r.p.m. (D) 75 r.p.m

asked Apr 11, 2018 in Electrical Engineering by Shimroz123
1 answer 26 views

A generator is connected through a 20 MVA, 13.8/138 kV step down transformer, to a transmission line. At the receiving end of the line a load is supplied through a step down transformer of 10 MVA, 138/69 kV rating. A 0.72 pu. load, evaluated on load side transformer ratings as base values , is supplied from the above system. For system base values of 10 MVA and 69 kV in load circuit, the value of the load (in per unit) in generator will be (A) 36 (B) 1.44 (C) 0.72 (D) 0.18

asked May 25, 2018 in Power system by Shimroz123
1 answer 40 views

A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is (A) 0.85 Ω (B) 3.63 Ω (C) 36.3 Ω (D) 252 Ω

asked Apr 28, 2018 in Power system by Shimroz123
1 answer 62 views

The corona loss of a 3-phase transmission line is 100 kW at 60 kV/phase and 25 kW at 50 kV/phase. The disruptive critical voltage is (A) 40 kV (B) 43.6 kV (C) 49.6 kV (D) 50 kV

asked Apr 25, 2018 in Electrical Engineering by Shimroz123
1 answer 15 views

A three phase, salient pole synchronous motor is connected to an infinite bus. It is operated at no load a normal excitation. The field excitation of the motor is first reduced to zero and then increased in reverse direction gradually. Then the armature current.  (A) Increases continuously (B) First increases and then decreases steeply (C) First decreases and then increases steeply (D) Remains constant

asked May 17, 2018 in Synchronous machine by Shimroz123
1 answer 80 views

The locked rotor current in a 3-phase, star connected 15 , kW 4 , pole 230 V , 50 Hz induction motor at rated conditions is 50 A. Neglecting losses and magnetizing current, the approximate locked rotor line current drawn when the motor is connected to a 236 , V 57 Hz supply is  (A) 58.5 A (B) 45.0 A (C) 42.7 A (D) 55.6 A

asked May 17, 2018 in Electrical Machine by Shimroz123
1 answer 14 views

A solar cell of 350 V is feeding power to an ac supply of 440 V, 50 Hz through a 3-phase fully controlled bridge converter. A large inductance is connected in the dc circuit to maintain the dc current at 20 A. If the solar cell resistance is 0.5 Ohm ,then each thyristor will be reverse biased for a period of  (A) 125o (B) 120o (C) 60o (D) 55o

asked May 18, 2018 in Power electronics converters by Shimroz123
1 answer 19 views

A 20-MVA, 6.6-kV, 3-phase alternator is connected to a 3-phase transmission line. The per unit positive-sequence, negative-sequence and zero-sequence impedances of the alternator are j0.1, j0.1 and j0.04 respectively. The neutral of the alternator is connected to ground through an inductive reactor of j0.05 p.u. The per unit positive-, ... The voltage of the alternator neutral with respect to ground during the fault is  (A) 513.8 V (B) 889.9 V (C) 1112.0 V (D) 642.2 V

asked May 25, 2018 in Power system by Shimroz123
0 answers 20 views

A Phase shift transformer is designed to control 150 MVA on a 230 kV, 3 phase line. The phase angle is variable between zero and 15 deg. Calculate the approximate basic power rating of the transformer.  (A) 150 MVA (B) 56 MVA (C) 75 MVA (D) 750 MVA 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
0 answers 15 views

A 50 Hz, 3—phase induction motor has a full load speed of 1440 rpm. The number of poles of the motor is:   (A)4 (8)6 (0)12  (D)8

asked Apr 9, 2018 in Electrical Engineering by Shimroz123
1 answer 29 views

A separately excited d.c. machine is coupled to a 50 Hz, three-phase, 4-pole induction machine as shown in the figure. The Dc machine is energized first and the machines rotate at 1 600 1pm. Subsequently the induction machine is also connected to a 50 Hz, three phase source, the phase sequence being consistent with the direction of rotation. In steady state

asked May 20, 2018 in DC machine by Shimroz123
0 answers 19 views

The power input to the rotor of a 400V, 50 Hz 6 pole three phase induction motor is 20kW. The slip is 3%. The frequency of rotor currents is: (A) 1 Hz (B) 1.5 Hz (C) 2 Hz (D) 1 2 Hz

asked Apr 14, 2018 in Electrical Engineering by Shimroz123
1 answer 29 views

An 8-pole, 50Hz, three-phase induction motor is running at 705rpm and has a rotor copper loss of 5kW. Its rotor input is (A) 5.06 kW (B) 0.3 kW (C) 100 kW (D) 83.33 kW

asked Apr 28, 2018 in Electrical Machine by Shimroz123
1 answer 12 views

 An 8 pole lap wound DC shunt generator is supplying 295A to a load. The field current of the generator is 5A. The current per parallel path is: -  a) 300A b) 200A c) 150A d) 37.5A

asked Apr 11, 2018 in Electrical Engineering by Shimroz123
1 answer 59 views

A three-phase, 33 kV oil circuit breaker is rated 1200 A, 2000 MVA, 3 s. The symmetrical breaking current is  (A) 1200 A (B) 3600 A (C) 35 kA (D) 104.8 kA

asked May 25, 2018 in Power system by Shimroz123
0 answers 77 views

A 3-phase circuit breaker is rated at 1250 A, 2000 MVA, 33 kV, 4s. Its making current capacity will be   (a) 35 kA (b) 89 kA (c) 79 kA (d) 69 kA

asked Apr 10, 2018 in Electrical Engineering by Shimroz123
0 answers 19 views

Two 3-phase synchronous generators with reactance 60% and 40% feed a fault current of 1200 A up to short-circuit fault point. The short-circuit current is (A) 1200 A (B) 2400 A (C) 4000 A (D) 5000 A 

asked Jun 4, 2018 in Synchronous machine by Shimroz123
0 answers 16 views

A 3 Phase, 60 Hz generator connected in Y connection, generates a line to line voltage of 23900 V. Calculate the peak line voltage.  (A) 13800 V (B) 33800 V (C) 42300 V (D) 23900 V 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
0 answers 69 views

The magnetizing reactance of a 4 kV/ 400 V, 50 Hz single-phase transformer on low voltage side is 35 Ω. The magnetizing reactance on the high voltage side is (A) 0.35 Ω (B) 3.5 Ω (C) 350 Ω (D) 3500 Ω

asked Jun 4, 2018 in Single phase transformer by Shimroz123
0 answers 17 views

A three phase 50 Hz, 400 kV transmission line is 300 km long. The line inductance is 0.97 mH/km per phase and capacitance is 0.0115 mF/km per phase. Assume a loss less line. Determine the line wavelength (a line phase constant).  (A) 1250 km (B) 6578 km (C) 4990 km (D) 2445 km 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 42 views

 An 8-pole alternator runs at 750 rpm and supplies power to a 6-pole induction motor which has a full load slip of 3 percent. The full load speed of the induction motor will be: A) 1000 rpm B) 920 rpm C) 950 rpm D) 970 rpm

asked Jun 4, 2018 in Alternator by Shimroz123
1 answer 14 views

In a two -channel oscilloscope operating in x -y mode, two in -phase 50 Hz sinusoidal waveforms of equal amplitude are fed to the two channels. What will be the resultant pattern on the screen ? (a) An ellipse (b) A parabola (c) Straight line inclined at 45° with respect to x-axis (d) A circle

asked Apr 23, 2018 in Electrical Engineering by Shimroz123
1 answer 24 views

A 230 V, 50 Hz phase controlled single-phase full-controlled SCR bridge converter draws 15 A constant dc current. If the source inductance is 3 mH, the drop in dc output voltage is (A) 4.5 V (B) 6.75 V (C) 9 V (D) 13.5 V

asked Apr 28, 2018 in Power Electronics by Shimroz123
1 answer 33 views

A 400 V, 50 Hz 30 hp, three-phase induction motor is drawing 50 A current at 0.8 power factor lagging. The stator and rotor copper losses are 1.5 kW and 900 W respectively. The friction and windage losses are 1050 W and the core losses are 1200 W. The air-gap power of the motor will be (A) 23.06 kW (B) 24.11 kW (C) 25.01 kW (D) 26.21 kW

asked May 17, 2018 in Electrical Machine by Shimroz123
1 answer 16 views

A 400 V, 15 kW, 4-pole, 50 Hz, Y-connected induction motor has full load slip of 4%. The output torque of the machine at full load is  (A) 1.66 Nm (B) 95.50 Nm (C) 99.47 Nm (D) 624.73 Nm

asked May 17, 2018 in Induction Machine by Shimroz123
1 answer 13 views

A 8-pole, DC generator has a simplex wave-wound armature containing 32 coils of 6 turns each. Its flux per pole is 0.06 Wb. The machine is running at 250 rpm. The induced armature voltage is  (A) 96 V (B) 192 V (C) 384 V (D) 768 V

asked May 17, 2018 in DC generator by Shimroz123
1 answer 27 views

A synchronous motor has better power factor as compared to that of an equivalent induction motor. This is mainly because?

asked Mar 20, 2018 in Synchronous machine by Shimroz123
1 answer 14 views

A 4-pole induction motor, supplied by a slightly unbalanced three-phase 50 Hz source, is rotating at 1440 rpm. The electrical frequency in Hz of the induced negative sequence current in the rotor is  (A) 100 (B) 98 (C) 52 (D) 48

asked May 17, 2018 in Induction Machine by Shimroz123
1 answer 12 views

A single phase transformer is designed to operate from 50 Hz, 1100 V supply and to have an output voltage of 240 V at no load. The core has mean area of 30 cm2 and the flux density has not to exceed 1.3T. The number of secondary turns will be (a) 1270 (b) 1017 (c) 768 (d) 277  

asked May 25, 2018 in Single phase transformer by Shimroz123
1 answer 34 views

An 8 pole wound rotor induction motor operating on 60 Hz supply is driven at 1800 r.p.m. by a prime mover in the opposite direction of revolving magnetic field. The frequency of the rotor current is (a) 30 Hz (b) 60 Hz (c) 120 Hz (d) 180 Hz 

asked May 25, 2018 in Induction Machine by Shimroz123
0 answers 108 views

A single phase transformer rated at 3000 kVA, 69 kV 4.16 kV, 60 Hz has a total internal impedance Zp of 127 ohm, referred to the primary side. Calculate the primary current if the secondary is accidentally short circuited.  (A) 43.5 A (B) 543 A (C) 9006 A (D) 721 A 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123

Welcome to electronics2electrical.com here you can ask questions related to electrical, electronics, mechanical, telecommunication, instrumentation, computer, mathematics, physics etc.
Be respectful to all the members. Do not copy and paste the answers from other websites which have copyright content. While asking question give full details about it.

Categories

Most popular tags

power motor dc circuit transformer voltage current used system phase resistance factor synchronous load ac energy induction electric generator series frequency between speed capacitor use electrical meter line difference control type mosfet transmission magnetic plant high single instrument bjt unit source advantages function diode and machine winding field define torque parallel amplifier supply shunt thyristor motors electricity arduino maximum time relay armature problem value on transformers types coil diagram state flow ratio material three formula starting direction theorem method emf operating efficiency digital wave microprocessor test instruments inductance loss measure operation connected signal low applications effect single-phase network temperature working constant losses different law wattmeter measuring compare controlled breaker drive device logic rc full switch flux wire resistivity disadvantages free of materials machines angle force converter conductor transistor gain open protection scr core measurement number bridge principle generators reactance circuits negative the friction iron loop short pole battery conservation steam resistors hysteresis computer using analog lines secondary station gate a rectifier inverter linear induced relays nuclear capacitance basic characteristics design direct work rotor electronics ammeter forces diesel damping rlc connection factors capacitors minimum insulation moving regulation running self systems air fault range main stability quality starter igbt eddy alternator ideal rl average 3-phase plants arc thermal error fuzzy biasing dielectric pressure balanced superposition errors copper rotation feedback impedance measured electronic electrons charge inductive transfer explain start off back curve over solar is three-phase tariff locomotive peak bias zener engineering commutator surge conductors rating universal potentiometer density permanent mechanical transducer capacity memory adc excitation two fuse pure harmonics application semiconductor inductor internal pmmc reaction welding resonance traction permeability breakers rms designed electromagnetic si generation brushes switching capacitive shaded rate 1 distribution resistor methods delta star oscillator reluctance simplification algebra 8085 boolean weston dynamometer insulating strength installation definition fuel heating earth units

8,471 questions

7,069 answers

134 comments

3,088 users

...