Can you help by answering this question?

Define absolute zero and absolute temperature

21 views
in Power system by
An 800 kV transmission line has a maximum power transfer capacity of P. If it is operated at 400 kV with the series reactance unchanged, the new maximum power transfer capacity is approximately (A) P (B) 2P (C) P / 2 (D) P / 4

1 Answer

0 votes
by

An 800 kV transmission line has a maximum power transfer capacity of P. If it is operated at 400 kV with the series reactance unchanged, the new maximum power transfer capacity is approximately P / 4

Related questions

1 answer 48 views

If voltage at the two ends of a transmission line is 132 kV and its reactance is 40 Ohms, the capacity of the line will be: (A) 435.6 MW (B) 217.8 MW(C) 251.5 MW (D) 500 MW

asked Apr 11, 2018 in Computer Engineering by Shimroz123
1 answer 20 views

A 800 kV transmission line is having per phase line inductance of 1.1 mH/km and per phase line capacitance of 11.68 nF/km. Ignoring the length of the line, its ideal power transfer capability in MW is (A) 1204 MW (B) 1504 MW (C) 2085 MW (D) 2606 MW

asked May 25, 2018 in Power system by Shimroz123
1 answer 42 views

A 100 km long transmission line is loaded at 110 kV.if the loss of line is 5 MW and the load is 150 MVA, the resistance of the line is?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 89 views

A transmission line has 1 P.0 impedance on a base of 11 KV, 100 MVA. On a base of 55 KV. it will have a P.0 impedance of

asked May 3, 2018 in Electric Power Transmission by Shimroz123
0 answers 56 views

A power system network with a capacity of 100 MVA has a source impedance of 10% at a point. The fault level at that point is (a) 1500 MVA (b) 1000 MVA (c) 500 MVA (d) 100 MVA

asked May 25, 2018 in Power system by Shimroz123
1 answer 26 views

A 500 MW, 3-phase, Y-connected synchronous generator has a rated voltage of 21.5 kV at 0.85 p.f. The line current when operating at full load rated conditions will be  (A) 13.43 kA (B) 15.79 kA (C) 23.25 kA (D) 27.36 kA

asked May 17, 2018 in Synchronous machine by Shimroz123
0 answers 22 views

An overhead transmission line has a span of 260 m. The weight of the conductor is 0.68 kg/m. The maximum allowable tension in the line is 1550 kg. Maximum sag of the line should be (a) 5.8 m (b) 4.6 m (c) 2.7 m (d) 3.7 m 

asked May 25, 2018 in Electric Power Transmission by Shimroz123
0 answers 17 views

A three phase 50 Hz, 400 kV transmission line is 300 km long. The line inductance is 0.97 mH/km per phase and capacitance is 0.0115 mF/km per phase. Assume a loss less line. Determine the line wavelength (a line phase constant).  (A) 1250 km (B) 6578 km (C) 4990 km (D) 2445 km 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 31 views

A voltage of 1000 kV is applied to an overhead line with its receiving end open. If the surge impedance of the line is 500 ohm, then the total surge power in the line ill

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 73 views

The X:R ratio of 220 kV line as compared to 400 kV line is?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 21 views

The line conductor of a transmission line has an overall diameter of 19.53 mm, weight 0.844 kg/m and an ultimate breaking strength of 7950 kg. If the factor of safety is to be 2, when conductor has an ice of 1 kg/m and a horizontal wind pressure of 1.5 kg/m. What is the vertical sag, corresponding to this loading for a 300 m span level supports?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 62 views

The corona loss of a 3-phase transmission line is 100 kW at 60 kV/phase and 25 kW at 50 kV/phase. The disruptive critical voltage is (A) 40 kV (B) 43.6 kV (C) 49.6 kV (D) 50 kV

asked Apr 25, 2018 in Electrical Engineering by Shimroz123
1 answer 115 views

A 100 km transmission line is designed for a nominal voltage of 132 kV and consists of one conductor per phase. The line reactance is 0.726 ohm/km. The static transmission capacity of the line, in MW, would be   (a) 240 (b) 132 (c) 416 (d) 720

asked Mar 27, 2018 in Power system by Shimroz123
2 answers 95 views

The sending end and receiving end voltages of a three-phase transmission line are 10 kV/ph and 9.5 kV/ph, respectively. If the resistance drop is 150 V/ph and receiving end power factor is 0.8, the sending end power factor is (A) 0.745 lagging (B) 0.775 lagging (C) 0.8 lagging (D) 0.85 lagging

asked Apr 28, 2018 in Power system by Shimroz123
1 answer 19 views

A 20-MVA, 6.6-kV, 3-phase alternator is connected to a 3-phase transmission line. The per unit positive-sequence, negative-sequence and zero-sequence impedances of the alternator are j0.1, j0.1 and j0.04 respectively. The neutral of the alternator is connected to ground through an inductive reactor of j0.05 p.u. The per unit positive-, ... The voltage of the alternator neutral with respect to ground during the fault is  (A) 513.8 V (B) 889.9 V (C) 1112.0 V (D) 642.2 V

asked May 25, 2018 in Power system by Shimroz123
1 answer 189 views

A 10 km long line has a characteristic impedance of 400 ohms. If line length is 100 km, the characteristic impedance is: (1) 4000 Ω (2) 400 Ω (3) 40 Ω (4) 4 Ω

asked May 28, 2018 in Electric Power Transmission by Shimroz123
1 answer 29 views

If an unsymmetrical line to ground fault occurs at the secondary terminals of a delta/star, ungrounded transformer, then  (A) zero sequence currents are present on both sides of the transformer  (B) zero sequence currents are absent on both sides of the transformer  (C) zero sequence currents are present on the secondary side but not on the primary side  (D) zero sequence currents are present on the primary side but not on the secondary side

asked Apr 29, 2018 in Power system by Shimroz123
0 answers 18 views

If the transmission line is loaded with leading reactive volt amperes, there will be rise of voltage at the receiving end and this (a) increases (b) decreases (c) remains same with the increase in the length of line (d) none of these

asked Apr 14, 2018 in Electrical Engineering by Shimroz123
1 answer 16 views

An overhead transmission line has a span of 240m between level supports. What is the maximum sag if the conductor weight 727 kg/km and has a breaking strength of 6880 kg? Allow the factor of safety of 2. Neglecting wind and ice loading.

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 15 views

Choose two appropriate auxiliary components of a HVDC transmission system from the following P. D.C line inductor Q. A.C line inductor R. Reactive power sources S. Distance relays on D.C line T. Series capacitance on A.C. line  (A) P and Q (B) P and R (C) Q and S (D) S and T

asked May 25, 2018 in Power system by Shimroz123
1 answer 13 views

For a transmission line with negligible losses, the lagging reactive power (VAR) delivered at The receiving end, for a given receiving end voltage, is directly proportional to the?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 21 views

For an existing ac transmission line, the string efficiency is 80%, if dc voltage is supplied for the same setup, the string efficiency will be?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 20 views

At an industrial sub-station with a 4 MW load, a capacitor of 2 MVAR is installed to maintain the load power factor at 0.97 lagging. If the capacitor goes out of service, the load power factor becomes (A) 0.85 (B) 1.00 (C) 0.80 lag (D) 0.90 lag

asked May 25, 2018 in Power system by Shimroz123
1 answer 52 views

A 40 kVA transformer has a core loss of 400 W and a full load copper loss of 800 W. The proportion of full load at maximum efficiency is

asked May 8, 2018 in Electric Power Transmission by Shimroz123
1 answer 26 views

A generator is connected through a 20 MVA, 13.8/138 kV step down transformer, to a transmission line. At the receiving end of the line a load is supplied through a step down transformer of 10 MVA, 138/69 kV rating. A 0.72 pu. load, evaluated on load side transformer ratings as base values , is supplied from the above system. For system base values of 10 MVA and 69 kV in load circuit, the value of the load (in per unit) in generator will be (A) 36 (B) 1.44 (C) 0.72 (D) 0.18

asked May 25, 2018 in Power system by Shimroz123
1 answer 32 views

A 60 Hz, 320 km lossless line has Bending end voltage 1.0 p.u, The receiving end voltage on no load is?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 17 views

A generating station has a maximum demand of 50 Mw, a load factor of 60%, a plant capacity factor of 45% and if the plant while running as per schedule, were fully loaded. The daily energy produced will be

asked Mar 27, 2018 in Power system by Shimroz123
0 answers 20 views

A synchronous condenser is used at the receiving end of a transmission line for (A) supplying lagging kVA (B) voltage control (C) frequency control (D) maintaining a higher voltage than at the sending end 

asked Jun 4, 2018 in Power system by Shimroz123
1 answer 40 views

A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is (A) 0.85 Ω (B) 3.63 Ω (C) 36.3 Ω (D) 252 Ω

asked Apr 28, 2018 in Power system by Shimroz123
1 answer 26 views

To increase power transfer capability of a long transmission line, we should:  (1) Increase line resistance (2) Increase transmission voltage (3) Decrease line reactance (4) Both (2) & (3)

asked May 22, 2018 in Electric Power Transmission by Shimroz123
1 answer 17 views

If it takes 400 ms to use 12,000 J of energy, the power is? A.30 kW B.30 W C.3 W D.300 kW

asked May 15, 2018 in Basic concepts by Shimroz123
0 answers 15 views

A commutator with a diameter of 50 cm rotates at 1000 r.p.m. If brush width is 1.5 cm, the time of commutation will be (a) 0.168 m sec (b) 0.374 m sec (c) 0.481 m sec (d) 0.573 m sec

asked May 25, 2018 in Electrical Machine by Shimroz123
1 answer 19 views

A transmission line of 200 km has a certain A, B, C and D parameters. If the length is reduced to 60 km

asked Apr 29, 2018 in Electrical Engineering by Shimroz123
0 answers 15 views

Voltages phasors at the two terminals of a transmission line of length 70 km have a magnitude of 1.0 per unit but are 180 degree out of phase. Assuming that the maximum load current in the line is 1/5th of minimum 3-phase fault current. Which one of the following transmission line protection schemes ... pick up at 1.25 times the maximum load current (C) Pilot relaying system with directional comparison scheme (D) Pilot relaying system with segregated phase comparison scheme

asked May 25, 2018 in Power system by Shimroz123
1 answer 10 views

If an induction machine is run at above synchronous speed, it acts as

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 28 views

The maximum possible power of a 3-phase synchronous motor with synchronous reactance 0.8 p.u. connected to a bus-bar of 1.0 p.u. and excitation adjusted to 1.2 p.u. is (A) 0.5 p.u. (B) 0.96 p.u. (C) 1.5 p.u. (D) 1.8 p.u.

asked Apr 25, 2018 in Electrical Engineering by Shimroz123
1 answer 62 views

If the inertia constant H of a machine of 200 MVA is 2 p.u., its value corresponding to 400 MVA will be   (a) 4 p.u. (b) 2 p.u. (c) 1.0 p.u. (d) 0.5 p.u. 

asked May 13, 2018 in Electrical Engineering by Shimroz123
1 answer 14 views

A three phase, salient pole synchronous motor is connected to an infinite bus. It is operated at no load a normal excitation. The field excitation of the motor is first reduced to zero and then increased in reverse direction gradually. Then the armature current.  (A) Increases continuously (B) First increases and then decreases steeply (C) First decreases and then increases steeply (D) Remains constant

asked May 17, 2018 in Synchronous machine by Shimroz123
1 answer 13 views

A transmission line is operating with a Phase shift of 80° between two ends. If the load is suddenly increased A) The phase displacement will increase B) The phase displacement will decrease C) The phase displacement will not change D) The surge impedance will increase

asked May 24, 2018 in Electrical Engineering by Shimroz123
1 answer 25 views

A loss less transmission line having Surge Impedance Loading (SIL) of 2280 MW is provided with a uniformly distributed series capacitive compensation of 30%. Then, SIL of the compensated transmission line will be (A) 1835 MW (B) 2280 MW (C) 2725 MW (D) 3257 MW

asked May 25, 2018 in Power system by Shimroz123
1 answer 15 views

For a fixed value of complex power flow in a transmission line having a sending and voltage V, the real power loss will be proportional to  A) V B) v2 C) 1/V2 D)1/V

asked May 20, 2018 in Power system by Shimroz123
1 answer 137 views

A 3-phase, 11 kv, 50 Hz, 200 kW load has a power factor of 0.8 lag. A delta connected 3-phase capacitor is used to improve the power factor to unity. The capacitance perphase of the capacitor in micro-farads is?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 42 views

A 50 Hz, 4-pole, 500 MVA, 22 kV turbo-generator is delivering rated megavolt amperes at 0.8 power factor. Suddenly a fault occurs reducing in electric power output by 40%. Neglect losses and assume constant power input to the shaft. The accelerating torque in the generator in MNm at the time of fault will be  (A) 1.528 (B) 1.018 (C) 0.848 (D) 0.509

asked May 25, 2018 in Power system by Shimroz123
0 answers 9 views

If all transmission zeros of a network are at origin, it is a  A) HPF B) LPF C) BPF D) BEF 

asked Apr 9, 2018 in Electronics Engineering by Shimroz123
1 answer 43 views

For a short transmission line with r/x ratio of is 1.0, the regulation will be zero when the load power factor is

asked Apr 30, 2018 in Electrical Engineering by Shimroz123
1 answer 12 views

The transmission line feeding power on either side of the main transmission line is called?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 25 views

An _____________is a network of electrical components used to supply, transfer and use electric power:  (A) Electric power system (B) Electric power (C) All of the above (D) None of the above

asked May 8, 2018 in Power system by Shimroz123
0 answers 42 views

If 5000 kW power is transmitted at 220 kV in place of 11 kV, reduction in the value of electric current will be (a) 90% (b) 95% (c) 5% (d) 10% 

asked May 26, 2018 in Electric Power Transmission by Shimroz123
1 answer 18 views

A transmission line conductor at a river crossing is supported from two towers at height. of 30 m and 90m, above water level. The horizontal distance between the towers is 270m, if the tension in the conductor is 1800 kg and the conductor weight 1 kg/m. What is the clearance between the conductor and the water at a point midway between the towers?

asked Mar 27, 2018 in Power system by Shimroz123

Welcome to electronics2electrical.com here you can ask questions related to electrical, electronics, mechanical, telecommunication, instrumentation, computer, mathematics, physics etc.
Be respectful to all the members. Do not copy and paste the answers from other websites which have copyright content. While asking question give full details about it.

Categories

Most popular tags

power motor dc circuit transformer voltage current used system phase resistance factor synchronous load ac energy induction electric generator series frequency between speed capacitor use electrical meter line difference control type mosfet transmission magnetic plant high single instrument bjt unit source advantages function diode and machine winding field define torque parallel amplifier supply shunt thyristor motors electricity arduino maximum time relay armature problem value on transformers types coil diagram state flow ratio material three formula starting direction theorem method emf operating efficiency digital wave microprocessor test instruments inductance loss measure operation connected signal low applications effect single-phase network temperature working constant losses different law wattmeter measuring compare controlled breaker drive device logic rc full switch flux wire resistivity disadvantages free of materials machines angle force converter conductor transistor gain open protection scr core measurement number bridge principle generators reactance circuits negative the friction iron loop short pole battery conservation steam resistors hysteresis computer using analog lines secondary station gate a rectifier inverter linear induced relays nuclear capacitance basic characteristics design direct work rotor electronics ammeter forces diesel damping rlc connection factors capacitors minimum insulation moving regulation running self systems air fault range main stability quality starter igbt eddy alternator ideal rl average 3-phase plants arc thermal error fuzzy biasing dielectric pressure balanced superposition errors copper rotation feedback impedance measured electronic electrons charge inductive transfer explain start off back curve over solar is three-phase tariff locomotive peak bias zener engineering commutator surge conductors rating universal potentiometer density permanent mechanical transducer capacity memory adc excitation two fuse pure harmonics application semiconductor inductor internal pmmc reaction welding resonance traction permeability breakers rms designed electromagnetic si generation brushes switching capacitive shaded rate 1 distribution resistor methods delta star oscillator reluctance simplification algebra 8085 boolean weston dynamometer insulating strength installation definition fuel heating earth units
...