A single phase transformer is designed to operate from 50 Hz, 1100 V supply and to have an output voltage of 240 V at no load. The core has mean area of 30 cm2 and the flux density has not to exceed 1.3T. The number of secondary turns will be (a) 1270 (b) 1017 (c) 768 (d) 277  

Your answer

Thanks for your contribution. Feel free to answer this question. Please avoid short answer. Your answer is most welcome. Be genuine.

Upload image or document:

Your name to display (optional):
Privacy: Your email address will only be used for sending these notifications.

1 Answer

0 votes
answered by

E2=e2=4.44*flux*N2*f=240 V


Flux=Flux density* Area



Area=30 cm =30*10-4 m2


Flux= 1.3*30*10-4  Wb=39*10-4 Wb


E=240= 4.44*39*10-4 *N2*50


     N2=277.