Can you help by answering this question?

Degaussing is the process of

63 views
in Power system by
The inertia constant of a 100 MVA, 11 kV water wheel generator is 4. The energy stored in the rotor at the synchronous speed is: A) 400 Mega Joule B) 400 Kilo Joule C) 25 Mega Joule D) 25 Kilo Joule

1 Answer

0 votes
by

The inertia constant of a 100 MVA, 11 kV water wheel generator is 4. The energy stored in the rotor at the synchronous speed is: 400 Mega Joule

Related questions

1 answer 118 views

A 60 Hz, 4 pole turbo generator rated 100 MVA, 13.8 KV has an inertia constant of 10 MJ/MVA. Find the stored energy in the rotor at synchronous speed.  (A) 10 MJ (B) 100 J (C) 1000 J (D) 1000 MJ 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 46 views

A 100 MVA, 11 KV, 3-phase, 50 Hz, 8—pole synchronous generator has an inertia constant H equal to 4 seconds. The stored energy in the rotor of the generator at synchronous speed will be  A) 100 MJ B) 400 MJ C) 800 MJ D) 12.5 MJ

asked May 20, 2018 in Synchronous machine by Shimroz123
1 answer 148 views

A 50 Hz, 4 pole turboalternator rated at 20 MVA. 13.2 KV has an inertia constant H = 4 KW sec/KVA. The K.E. stored in the rotor at synchronous speed is

asked May 3, 2018 in Electric Power Transmission by Shimroz123
1 answer 14 views

A 3-phase 11 kV generator feeds power to a constant power unity power factor load of 100 MW through a 3-phase transmission line. The line-to line voltage at the terminals of the machine is maintained constant at 11 kV. The per unit positive sequence impedance of the line based on 100 MVA and 11 kV is j0.2. The line to line voltage at the ... load to increase the line-to-line voltage at the load terminals to 11 kV is  (A) 100 MVAR (B) 10.1 MVAR (C) -100 MVAR (D) -10.1 MVAR

asked May 25, 2018 in Power system by Shimroz123
1 answer 42 views

A 50 Hz, 4-pole, 500 MVA, 22 kV turbo-generator is delivering rated megavolt amperes at 0.8 power factor. Suddenly a fault occurs reducing in electric power output by 40%. Neglect losses and assume constant power input to the shaft. The accelerating torque in the generator in MNm at the time of fault will be  (A) 1.528 (B) 1.018 (C) 0.848 (D) 0.509

asked May 25, 2018 in Power system by Shimroz123
1 answer 89 views

A transmission line has 1 P.0 impedance on a base of 11 KV, 100 MVA. On a base of 55 KV. it will have a P.0 impedance of

asked May 3, 2018 in Electric Power Transmission by Shimroz123
1 answer 115 views

A 500 MVA, 11 KV synchronous generator has 0.2 p.u. synchronous reactance. The p.u. synchronous reactance on the base values of 100 MVA and 22 KV is  A) 0.16 B) 0.01 C) 4.0 D) 0.25

asked May 17, 2018 in Synchronous machine by Shimroz123
0 answers 24 views

What is the energy stored in the magnetic field at a solenoid of 40 cm long and 4 cm diameter wound with 100 turns of wire carrying a current at 20A?  (A) 0.705 Joule (B) 0.789 Joule (C) 0.587 Joule (D) 0.658 Joule 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 62 views

If the inertia constant H of a machine of 200 MVA is 2 p.u., its value corresponding to 400 MVA will be   (a) 4 p.u. (b) 2 p.u. (c) 1.0 p.u. (d) 0.5 p.u. 

asked May 13, 2018 in Electrical Engineering by Shimroz123
1 answer 26 views

A generator is connected through a 20 MVA, 13.8/138 kV step down transformer, to a transmission line. At the receiving end of the line a load is supplied through a step down transformer of 10 MVA, 138/69 kV rating. A 0.72 pu. load, evaluated on load side transformer ratings as base values , is supplied from the above system. For system base values of 10 MVA and 69 kV in load circuit, the value of the load (in per unit) in generator will be (A) 36 (B) 1.44 (C) 0.72 (D) 0.18

asked May 25, 2018 in Power system by Shimroz123
1 answer 42 views

A 100 km long transmission line is loaded at 110 kV.if the loss of line is 5 MW and the load is 150 MVA, the resistance of the line is?

asked Mar 27, 2018 in Power system by Shimroz123
0 answers 23 views

The constant of a given energy meter is 500 revolution/kWh. At the test 4.4 kW full load, meter completes 50 revolutions in 86 seconds. The percentage error of the meter is (a) –4.86% (b) 4.86% (c) 2.0% (d) 3.0%

asked May 26, 2018 in Electrical Measurements and Instrumentation by Shimroz123
0 answers 56 views

A power system network with a capacity of 100 MVA has a source impedance of 10% at a point. The fault level at that point is (a) 1500 MVA (b) 1000 MVA (c) 500 MVA (d) 100 MVA

asked May 25, 2018 in Power system by Shimroz123
0 answers 23 views

If 1 ampere current is flowing through a 100 mH coil, then energy stored in the coil is (a) 0.05 Joules (b) 0.5 Joules (c) 5.0 Joules (d) None of these

asked May 25, 2018 in Electrical Engineering by Shimroz123
1 answer 15 views

The p.u. parameter for a 500 MVA machine on its own base are: inertia, M = 20 p.u. ; reactance, X = 2 p.u. The p.u. values of inertia and reactance on 100 MVA common base, respectively, are (A) 4, 0.4 (B) 100, 10 (C) 4, 10 (D) 100, 0.4

asked May 25, 2018 in Power system by Shimroz123
0 answers 42 views

If 5000 kW power is transmitted at 220 kV in place of 11 kV, reduction in the value of electric current will be (a) 90% (b) 95% (c) 5% (d) 10% 

asked May 26, 2018 in Electric Power Transmission by Shimroz123
1 answer 19 views

A 20-MVA, 6.6-kV, 3-phase alternator is connected to a 3-phase transmission line. The per unit positive-sequence, negative-sequence and zero-sequence impedances of the alternator are j0.1, j0.1 and j0.04 respectively. The neutral of the alternator is connected to ground through an inductive reactor of j0.05 p.u. The per unit positive-, ... The voltage of the alternator neutral with respect to ground during the fault is  (A) 513.8 V (B) 889.9 V (C) 1112.0 V (D) 642.2 V

asked May 25, 2018 in Power system by Shimroz123
1 answer 59 views

A three-phase, 33 kV oil circuit breaker is rated 1200 A, 2000 MVA, 3 s. The symmetrical breaking current is  (A) 1200 A (B) 3600 A (C) 35 kA (D) 104.8 kA

asked May 25, 2018 in Power system by Shimroz123
1 answer 32 views

The eddy current loss in a dc generator is 400 W at 40 Hz frequency of reversal and constant flux density. When frequency is increased to 50 Hz., eddy current loss is :  (A) 256 W (B) 320 W (C) 500 W (D) 625 W

asked Apr 30, 2018 in Switchgear And Protection by Shimroz123
1 answer 137 views

A 3-phase, 11 kv, 50 Hz, 200 kW load has a power factor of 0.8 lag. A delta connected 3-phase capacitor is used to improve the power factor to unity. The capacitance perphase of the capacitor in micro-farads is?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 15 views

A 3-phase star-connected 75 MVA, 25 kV 3-phase synchronous generator has a synchronous reactance of 1.0 p.u. The per unit value to a 90 MVA base and 30 kV is (A) 2/15 p.u. (B) 5/6 p.u. (C) 1.0 p.u. (D) 1.2 p.u.

asked Apr 25, 2018 in Electrical Engineering by Shimroz123
0 answers 430 views

The base kV and base MVA are halved and the per unit impedance new value is 0.5. The per unit impedance of the original circuit element is (A) 0.25 (B) 0.5 (C) 0.625 (D) 1.0 

asked Jun 4, 2018 in Power system by Shimroz123
1 answer 62 views

The corona loss of a 3-phase transmission line is 100 kW at 60 kV/phase and 25 kW at 50 kV/phase. The disruptive critical voltage is (A) 40 kV (B) 43.6 kV (C) 49.6 kV (D) 50 kV

asked Apr 25, 2018 in Electrical Engineering by Shimroz123
1 answer 115 views

A 100 km transmission line is designed for a nominal voltage of 132 kV and consists of one conductor per phase. The line reactance is 0.726 ohm/km. The static transmission capacity of the line, in MW, would be   (a) 240 (b) 132 (c) 416 (d) 720

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 67 views

A cylinder rotor generator delivers 0.5 pu power in the steady-state to an infinite bus through a transmission line of reactance 0.5 pu. The generator no-load voltage is 1.5 pu and the infinite bus voltage is 1 pu. The inertia constant of the generator is 5 MW -s MVA / and the generator reactance is 1 pu. The critical clearing angle, in degrees, for a three-phase dead short circuit fault at the generator terminal is  (A) 53.5 (B) 60.2 (C) 70.8 (D) 79.6

asked May 25, 2018 in Power system by Shimroz123
0 answers 12 views

A transformer when supplying a load, maintained at 11 kV across load terminals. When the load was switched off, the terminal voltage becomes 11550 V, what is the voltage regulation at this load? (1) 11.55 % (2) 5.5% (3) 5% (4) 55%  

asked Apr 11, 2018 in Electrical Engineering by Shimroz123
1 answer 40 views

A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is (A) 0.85 Ω (B) 3.63 Ω (C) 36.3 Ω (D) 252 Ω

asked Apr 28, 2018 in Power system by Shimroz123
0 answers 188 views

A 30 MVA, 13.2 KV synchronous generator has a solidly grounded neutral. Its positive, negative and zero sequence impedances are 0.30, 0.40 and 0.05 pu respectively. What value of reactance must be placed in the generator neutral so that the fault current for a line to ground fault of zero fault impedance shall not exceed the rated line current.  (A) 4.416 ohm (B) 8.8 ohm (C) 2.08 ohm (D) 10.2 ohm 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
0 answers 544 views

A 30 MVA, 15 KV, 1500 rpm, 3 phase synchronous generator connected to a power grid has a synchronous reactance of 9 ohm per phase. If the exciting voltage is 12 kV (line to neutral) and the system voltage is 17.3 kV (line to line), Calculate the maximum power that generator can deliver before it falls out of step (losses synchronous).  (A) 39.952 MW (B) 78.349 MW (C) 16.67 MW (D) 112.89 MW

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
0 answers 76 views

A 3-phase circuit breaker is rated at 1250 A, 2000 MVA, 33 kV, 4s. Its making current capacity will be   (a) 35 kA (b) 89 kA (c) 79 kA (d) 69 kA

asked Apr 10, 2018 in Electrical Engineering by Shimroz123
0 answers 241 views

A three phase breaker is rated at 2000 MVA, 33 kV, its making current is  (A) 70 kA (B) 89 kA (C) 49 kA (D) 35 kA 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
0 answers 20 views

The zero sequence current of a generator for line to ground fault is j 2.4 p.u. The current through the neutral during the fault is (a) j 0.8 p.u (b) j 2.4 p.u. (c) j 0.24 p.u. (d) j 7.2 p.u. 

asked May 25, 2018 in Power system by Shimroz123
1 answer 18 views

If a 3-phase, 400V, 50Hz, 4 pole induction motor is running at a slip of 5% then the relative speed of rotor field with respect to stator filed is:

asked May 22, 2018 in Induction Machine by Shimroz123
1 answer 21 views

An 800 kV transmission line has a maximum power transfer capacity of P. If it is operated at 400 kV with the series reactance unchanged, the new maximum power transfer capacity is approximately (A) P (B) 2P (C) P / 2 (D) P / 4

asked May 25, 2018 in Power system by Shimroz123
1 answer 80 views

The locked rotor current in a 3-phase, star connected 15 , kW 4 , pole 230 V , 50 Hz induction motor at rated conditions is 50 A. Neglecting losses and magnetizing current, the approximate locked rotor line current drawn when the motor is connected to a 236 , V 57 Hz supply is  (A) 58.5 A (B) 45.0 A (C) 42.7 A (D) 55.6 A

asked May 17, 2018 in Electrical Machine by Shimroz123
1 answer 35 views

The number of insulator discs (each rated 11 kV) required in a suspension type insulator string of 220 kV line is 

asked May 8, 2018 in Electric Power Transmission by Shimroz123
0 answers 17 views

The demagnetizing AT/pole of a 4-pole dc generator is 480. The number of conductors is 480 and the current in each conductor is 40 A. Then the required brush shift in mechanical degrees (A) 9° (B) 7° (C) 5° (D) 3° 

asked Jun 4, 2018 in Electrical Machine by Shimroz123
1 answer 26 views

A 500 MW, 3-phase, Y-connected synchronous generator has a rated voltage of 21.5 kV at 0.85 p.f. The line current when operating at full load rated conditions will be  (A) 13.43 kA (B) 15.79 kA (C) 23.25 kA (D) 27.36 kA

asked May 17, 2018 in Synchronous machine by Shimroz123
1 answer 32 views

A 3-phase, 4-pole, 50Hz induction motor runs at a speed of 1440 rpm. The rotating field produced by the rotor rotates at a speed of ________ rpm with respect to stator field. (A) 1500 (B) 0 (C) 1440 (D) 60

asked Apr 28, 2018 in Electrical Machine by Shimroz123
1 answer 20 views

At an industrial sub-station with a 4 MW load, a capacitor of 2 MVAR is installed to maintain the load power factor at 0.97 lagging. If the capacitor goes out of service, the load power factor becomes (A) 0.85 (B) 1.00 (C) 0.80 lag (D) 0.90 lag

asked May 25, 2018 in Power system by Shimroz123
1 answer 15 views

A two conductor 1 - pi line operates at 50 Hz.The diameter of each conductor is 4 cm and are spaced 6 m apart. What is the capacitive susceptance to neutral per km?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 14 views

If the conductive loop on the rotor of a simple two -pole, single-phase generator rotates at the rate of 400 rps. The frequency of the induced output voltage will be: A. 40 Hz B. 100 Hz C. 400 Hz D. indeterminable

asked Apr 12, 2018 in Electrical Engineering by Shimroz123
0 answers 308 views

Two generating stations G1 and G2 of ratings 10 MVA and 8 MVA respectively are linked by a line rated at 5 MVA, 0.1 Pu reactance. Each station has a reactance of 0.5 pu. If the base MVA is 10 MVA, short-circuit MVA of G1 is

asked May 24, 2018 in Power system by Shimroz123
0 answers 22 views

The per unit impedance of a circuit element is 0.30. If the base kV and base MVA are halved, then the new value of the per unit impedance of the circuit element will be:  (A) 0.3 (B) 0.6 (C) 0.003 (D) 0.006 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 20 views

 If shunt generator delivers 100 A at 200 V, and the resistance of the shunt field and armature are 100 ohm and 0.01 ohm respectively, the generated e.m.f. will be : -  a) 212 V b) 205 V c) 210 V d) 201.02 V

asked Apr 11, 2018 in Electrical Engineering by Shimroz123
0 answers 108 views

A single phase transformer rated at 3000 kVA, 69 kV 4.16 kV, 60 Hz has a total internal impedance Zp of 127 ohm, referred to the primary side. Calculate the primary current if the secondary is accidentally short circuited.  (A) 43.5 A (B) 543 A (C) 9006 A (D) 721 A 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
0 answers 15 views

A 3-phase, 2 pole, 11 kV, 10000 kVA alternator has earthed neutral through a resistance of 7.0Ω. The machine has current balance protection which operates if out of balance current exceeds 20% of full load. Determine %age of winding protected against earth fault (1) 10.6% (2) 11.6% (3) 10.9% (4) 11.2% 

asked Apr 11, 2018 in Electrical Engineering by Shimroz123
1 answer 71 views

Which type of generator gives a constant voltage output at all loads?

asked May 14, 2018 in Electrical Machine by Shimroz123
1 answer 29 views

The disc of a single phase Induction-type energy meter makes 60 revolutions in 6 minutes. Meter Constant is 1200 rev/kWh. Power consumption in the load is (A) 1.2 kW (B) 1 kW (C) 600 W (D) 500 W

asked Apr 25, 2018 in Instrumentation and control by Shimroz123
0 answers 20 views

A Phase shift transformer is designed to control 150 MVA on a 230 kV, 3 phase line. The phase angle is variable between zero and 15 deg. Calculate the approximate basic power rating of the transformer.  (A) 150 MVA (B) 56 MVA (C) 75 MVA (D) 750 MVA 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123

Welcome to electronics2electrical.com here you can ask questions related to electrical, electronics, mechanical, telecommunication, instrumentation, computer, mathematics, physics etc.
Be respectful to all the members. Do not copy and paste the answers from other websites which have copyright content. While asking question give full details about it.

Categories

Most popular tags

power motor dc circuit transformer voltage current used system phase resistance factor synchronous load ac energy induction electric generator series frequency between speed capacitor use electrical meter line difference control type mosfet transmission magnetic plant high single instrument bjt unit source advantages function diode and machine winding field define torque parallel amplifier supply shunt thyristor motors electricity arduino maximum time relay armature problem value on transformers types coil diagram state flow ratio material three formula starting direction theorem method emf operating efficiency digital wave microprocessor test instruments inductance loss measure operation connected signal low applications effect single-phase network temperature working constant losses different law wattmeter measuring compare controlled breaker drive device logic rc full switch flux wire resistivity disadvantages free of materials machines angle force converter conductor transistor gain open protection scr core measurement number bridge principle generators reactance circuits negative the friction iron loop short pole battery conservation steam resistors hysteresis computer using analog lines secondary station gate a rectifier inverter linear induced relays nuclear capacitance basic characteristics design direct work rotor electronics ammeter forces diesel damping rlc connection factors capacitors minimum insulation moving regulation running self systems air fault range main stability quality starter igbt eddy alternator ideal rl average 3-phase plants arc thermal error fuzzy biasing dielectric pressure balanced superposition errors copper rotation feedback impedance measured electronic electrons charge inductive transfer explain start off back curve over solar is three-phase tariff locomotive peak bias zener engineering commutator surge conductors rating universal potentiometer density permanent mechanical transducer capacity memory adc excitation two fuse pure harmonics application semiconductor inductor internal pmmc reaction welding resonance traction permeability breakers rms designed electromagnetic si generation brushes switching capacitive shaded rate 1 distribution resistor methods delta star oscillator reluctance simplification algebra 8085 boolean weston dynamometer insulating strength installation definition fuel heating earth units
...