State the nature of protection provided for following types of faults; 1) Over voltage 2) Under voltage 3) High air pressure in air circuit 4) Low air pressure in air circuit

Your answer

Thanks for your contribution. Feel free to answer this question. Please avoid short answer. Your answer is most welcome. Be genuine.

Upload image or document:

Your name to display (optional):
Privacy: Your email address will only be used for sending these notifications.

1 Answer

0 votes
answered by
Ans: 1) Over voltage: Controlled through tap changing, only an alarm needs to be provided for attention of crew. 2) Under voltage: voltage below 17.5 kV is not desirable. A no volt relay is provided which trips the CB and calls for resetting of power and auxiliary circuits. 3) High air pressure in air circuit: Safety valve / PRV (pressure release valve) is fitted in the compressed air circuit to protect against high pressure. 4) Low air pressure in air crcuit: Relay senses low pressure in air circuit and trips the relevant CB.