2 Answers

0 votes
by

For the parallel operation of single phase transformers, it is necessary that they should have same polarity.

0 votes
by

Necessary conditions required to be satisfied in order to ensure successful parallel operation of single phase transformers: 

1. Only transformers having the same phase displacement between primary and secondary voltage can operate in parallel. The clock-hour which indicate the phase displacement is stamped on the transformer rating plate, e.g. Dyn11, Yd11, 2. Terminals with the same polarity on HV- and LV side shall be connected in parallel, 3. Transformers should have approximately the same voltage ratio, within +-0.05% 4. The short-circuit impedance voltage should be the same, within +-10%, 5. The power rating of the transformers should not deviate more than 1:3, 6. Tap changers should have tap position giving voltage ratios as close as possible. 7. The phase sequence must be followed strictly on HV and LV side connection.

Welcome to Q&A site for electrical and electronics engineering discussion for diploma, B.E./B.Tech, M.E./M.Tech, & PhD study.
If you have a new question please ask in English.
If you want to help this community answer these questions.

...