An industrial consumer hall a daily load pattern of 2000 KW, 0.8 lag for 12 Hra and 1000 kW UPF for 1J Hr. The load factor i= _____. 

Your answer

Thanks for your contribution. Feel free to answer this question. Please avoid short answer. Your answer is most welcome. Be genuine.

Upload image or document:

Your name to display (optional):
Privacy: Your email address will only be used for sending these notifications.
Anti-spam verification:
Are you a robot ? (Y = Yes / N = No)
To avoid this verification in future, please log in or register.

1 Answer

0 votes
by

An industrial consumer hall a daily load pattern of 2000 KW, 0.8 lag for 12 Hra and 1000 kW UPF for 1J Hr. The load factor i= 0.6 

Related questions

1 answer 137 views

A 3-phase, 11 kv, 50 Hz, 200 kW load has a power factor of 0.8 lag. A delta connected 3-phase capacitor is used to improve the power factor to unity. The capacitance perphase of the capacitor in micro-farads is?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 117 views

The maximum demand of consumer is 2 kW and his daily energy consumption is 20 units. Its Load Factor is (1) 10.15% (2) 41.6 % (3) 50 % (4) 60% 

asked Apr 11, 2018 in Electrical Engineering by Shimroz123
0 answers 98 views

An auto transformer having a transformation ratio of 0.8 supplies a load of 10 kW. The power transferred inductively from the primary to secondary is (a) 2 kW (b) 4 kW (c) 8 kW (d) 10 kW 

asked May 25, 2018 in Autotransformer by Shimroz123
1 answer 63 views

A consumer consumes. 600 kWh per day at a load factor of 0.40. If the consumer increases the load factor of 0.70 without increasing the maximum demand, what is the consumption of energy in kWh?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 20 views

At an industrial sub-station with a 4 MW load, a capacitor of 2 MVAR is installed to maintain the load power factor at 0.97 lagging. If the capacitor goes out of service, the load power factor becomes (A) 0.85 (B) 1.00 (C) 0.80 lag (D) 0.90 lag

asked May 25, 2018 in Power system by Shimroz123
0 answers 13 views

An induction motor operating at 0.8 pf lagging is consuming 300 kW. A zero real power consuming synchronous motor is connected across the induction motor to raise the pf to 0.92 lagging. The reactive power drawn by the synchronous motor is a. - 352 kVAR b. - 225 kVAR c. - 127.8 kVAR d. - 97.2 kVAR

asked May 24, 2018 in Induction Machine by Shimroz123
0 answers 47 views

The connected load of a consumer is 2 kW and his maximum demand is 1.5 kW. The load factor of the consumer is (a) 0.375 (b) 0.75 (c) 1.33 (d) None of these  

asked May 26, 2018 in Electric Power Transmission by Shimroz123
1 answer 35 views

The corona loss in a 50 Hz system is 0.25 kW/ph/km. At a frequency of 60 Hz, the corona loss would be   (a) 0.30 kW/ph/km (b) 0.36 kW/ph/km (c) 028 kW/ph/km (d) 0.21 kW/ph/km

asked May 13, 2018 in Power system by Shimroz123
1 answer 17 views

 A single-phase transmission line of impedance j 0.8 ohm supplies a resistive load of 500 A at 300 V. The sending end power factor is?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 22 views

The armature resistance of a permanent magnet dc motor is 0.8 Ohm. At no load, the motor draws 1.5 A from a supply voltage of 25 V and runs at 1500 rpm. The efficiency of the motor while it is operating on load at 1500 rpm drawing a current of 3.5 A from the same source will be  (A) 48.0% (B) 57.1% (C) 59.2% (D) 88.8%

asked May 17, 2018 in Electrical Machine by Shimroz123
0 answers 20 views

The efficiency of a transformer at full load 0.8 p.f lagging is 90%. Its efficiency at full load 0.8 p.f leading will be (1) Less than 90% (2) More than 90% (3) 90% (4) None of these 

asked Apr 11, 2018 in Electrical Engineering by Shimroz123
0 answers 20 views

A three phase transmission line delivers a load of 5 MW at 0.8 power factor lagging. Resistance of each conductor is 0.5 ohm / km. Receiving end voltage is 33 kV. If the line loss is not to exceed 10%, determine the length of the line.  (A) 7 km (B) 27.9 km (C) 56.8 km (D) 13.9 km

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 15 views

In a 2 kW, 200 V, 1000 rpm. DC series motor the torque at full load was found to be 0.3 N -m. The torque at half full load in N -m is :

asked Apr 29, 2018 in Electrical Machine by Shimroz123
1 answer 98 views

The apparent power drawn by an A.C. circuit is 10 kVA and active power is 8 kW. The reactive power in the circuit is?

asked Mar 25, 2018 in Electrical Engineering by Shimroz123
1 answer 42 views

A 50 Hz, 4-pole, 500 MVA, 22 kV turbo-generator is delivering rated megavolt amperes at 0.8 power factor. Suddenly a fault occurs reducing in electric power output by 40%. Neglect losses and assume constant power input to the shaft. The accelerating torque in the generator in MNm at the time of fault will be  (A) 1.528 (B) 1.018 (C) 0.848 (D) 0.509

asked May 25, 2018 in Power system by Shimroz123
1 answer 16 views

An alternator is delivering rated current at rated voltage and 0.8 power-factor lagging. For delivering rated current at rated voltage and 0.8 poWer—factor leading, the required excitation will be:  (A) less  (B) more (C) more or less (D) the same

asked Apr 9, 2018 in Electrical Engineering by Shimroz123
1 answer 28 views

A consumer finds that after running 10 kVA equipment on full load for six hours, his energy consumption was 48 kWH. It can be concluded that (A) The load factor of consumer for the day was unity. (B) The maximum demand of consumer is 10 kW. (C) The equipment was drawing only reactive power. (D) The power factor of equipment was 0.8. 

asked May 13, 2018 in Electrical Engineering by Shimroz123
1 answer 37 views

A 150 kW electric motor has an efficiency of 92 %, when it operates at full load. Calculate the losses in the machine.  (A) 92 kW (B) 150 kW (C) 163 kW (D) 13 kW 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 23 views

 In the case of an instrument reading of 8.3 V with a 0 to 150 voltmeter having a guaranteed accuracy of 1% full scale reading, the percentage limiting error is   (A) 1.810% (B) 0.181% (C)12.45% (D) 0.0018%

asked May 17, 2018 in Electrical Measurements and Instrumentation by Shimroz123
1 answer 85 views

The input of an A.C. circuit having power factor of 0.8 lagging is 40 kVA The power drawn by the circuit is?

asked Mar 25, 2018 in Electrical Engineering by Shimroz123
1 answer 25 views

If the radiated power of AM transmitter is 10 KW, the power in the carrier for modulation index of 0.6 is nearly:  (1) 8.24 KW (2) 9.26 KW (3) 8.47 KW (4) 9.6 KW

asked Apr 9, 2018 in Electronics Engineering by Shimroz123
1 answer 12 views

 An 8 pole lap wound DC shunt generator is supplying 295A to a load. The field current of the generator is 5A. The current per parallel path is: -  a) 300A b) 200A c) 150A d) 37.5A

asked Apr 11, 2018 in Electrical Engineering by Shimroz123
1 answer 59 views

A three-phase, 33 kV oil circuit breaker is rated 1200 A, 2000 MVA, 3 s. The symmetrical breaking current is  (A) 1200 A (B) 3600 A (C) 35 kA (D) 104.8 kA

asked May 25, 2018 in Power system by Shimroz123
1 answer 19 views

If the fault current is 2000 A, the relay setting is 50% and CT ratio is 400:5, the plug setting multiplier will be

asked Apr 29, 2018 in Power system by Shimroz123
1 answer 19 views

The kVA rating required for a transformer that must handle a maximum load current of 8 A with a secondary voltage of 2 kV will be: A. 4 kVA B. 0.25 kVA C. 16 kVA D. 8 kVA

asked Apr 12, 2018 in Electrical Engineering by Shimroz123
1 answer 32 views

A 60 Hz, 320 km lossless line has Bending end voltage 1.0 p.u, The receiving end voltage on no load is?

asked Mar 27, 2018 in Power system by Shimroz123
0 answers 14 views

One 200 KVA transformer has an iron loss of 1 KW and full load Cu loss of 2 KW. Its load KVA corresponding to maximum efficiency is:  (A) 100 KVA (B) 141.4 KVA (C) 50 KVA (D) 200 KVA 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 16 views

The load of a consumer is generally measured in terms of : (A) Volts (B) Amperes (C) Ampere hour (D) kW

asked May 8, 2018 in Electrical Engineering by Shimroz123
0 answers 88 views

A single phase 60 Hz generator supplies an inductive load of 4500kW at a power factor of 0.80 lagging by means of a 20 km long overhead transmission line. The line resistance and inductance are 0.0195 ohm and 0.60 mH per km. The voltage at the receiving end is required to be kept constant at 10.2 kV. Find the voltage regulation of the line.  (A) 12.59% (B) 16.34% (C) 32.68% (D) 41.15% 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 43 views

 An 8-pole alternator runs at 750 rpm and supplies power to a 6-pole induction motor which has a full load slip of 3 percent. The full load speed of the induction motor will be: A) 1000 rpm B) 920 rpm C) 950 rpm D) 970 rpm

asked Jun 4, 2018 in Alternator by Shimroz123
1 answer 43 views

For a short transmission line with r/x ratio of is 1.0, the regulation will be zero when the load power factor is

asked Apr 30, 2018 in Electrical Engineering by Shimroz123
1 answer 67 views

A cylinder rotor generator delivers 0.5 pu power in the steady-state to an infinite bus through a transmission line of reactance 0.5 pu. The generator no-load voltage is 1.5 pu and the infinite bus voltage is 1 pu. The inertia constant of the generator is 5 MW -s MVA / and the generator reactance is 1 pu. The critical clearing angle, in degrees, for a three-phase dead short circuit fault at the generator terminal is  (A) 53.5 (B) 60.2 (C) 70.8 (D) 79.6

asked May 25, 2018 in Power system by Shimroz123
0 answers 51 views

Load flow study of a power system is mainly carried out for (a) fault calculations (b) stability studies (c) system planning and operation (d) load frequency control 

asked May 25, 2018 in Power system by Shimroz123
0 answers 46 views

For a balanced three phase star connected load for which line voltage is 230V and per phase resistance and reactance is 6 Ohm and 8 Ohm respectively. Calculate: 1) phase voltage 2) line current 3) power factor 4) total power absorbed

asked Aug 12, 2018 in Basic electrical and electronics engineering by Quiz
0 answers 19 views

It is desired to illuminate a drawing hall with an average illumination of about 250 lux. The area of hall is 30 m × 20 m. The lamps are to be fitted at 5 m height. Find the number and size of incandescent lamps required for an efficiency of 12 lumen/watt. Utilization factor = 0.4 and maintenance factor = 0.85.   (a) 40 and 1000 W (b) 20 and 500 W (c) 60 and 1000 W (d) None of the above 

asked Apr 10, 2018 in Electrical Engineering by Shimroz123
1 answer 34 views

The Lissajous pattern on the screen of a CRO is an ellipse with major axis in quadrant 2 and quadrant 4. Then the phase difference between two signals Can be :  (A) 270° (B) 210° (C) 180° (D) 300°

asked Apr 30, 2018 in Electrical Engineering by Shimroz123
0 answers 59 views

A Lissajous pattern on an oscilloscope has 5 horizontal tangencies and 2 vertical tangencies. The frequency of the horizontal input is 1000 Hz. What is the frequency of the vertical input?  (A) 400 Hz (B) 5000 Hz (C) 4000 Hz (D) 2500 Hz

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
0 answers 23 views

The constant of a given energy meter is 500 revolution/kWh. At the test 4.4 kW full load, meter completes 50 revolutions in 86 seconds. The percentage error of the meter is (a) –4.86% (b) 4.86% (c) 2.0% (d) 3.0%

asked May 26, 2018 in Electrical Measurements and Instrumentation by Shimroz123
1 answer 16 views

A 400 V, 15 kW, 4-pole, 50 Hz, Y-connected induction motor has full load slip of 4%. The output torque of the machine at full load is  (A) 1.66 Nm (B) 95.50 Nm (C) 99.47 Nm (D) 624.73 Nm

asked May 17, 2018 in Induction Machine by Shimroz123
1 answer 19 views

 If the range of an analog transducer is 0 to 10 V, then for a resolution of 5 mV, the bits of ADC will be _____.

asked May 29, 2018 in Transducers and sensors by Shimroz123
1 answer 17 views

A synchronous motor operates at 0.8 pf lagging. If the field current of the motor is continuously increased  1. The power factor decreases upto a certain value of field current and thereafter it increases.  2. The armature current increases upto a certain value of field current and thereafter it decreases.  3. The power factor increases upto a certain value ... field current and thereafter it, increases.  From these, the correct answer is (a) 1, 2 (b) 3, 4 (c) 1, 3 (d) 2, 4

asked May 13, 2018 in Electrical Engineering by Shimroz123
1 answer 28 views

The maximum possible power of a 3-phase synchronous motor with synchronous reactance 0.8 p.u. connected to a bus-bar of 1.0 p.u. and excitation adjusted to 1.2 p.u. is (A) 0.5 p.u. (B) 0.96 p.u. (C) 1.5 p.u. (D) 1.8 p.u.

asked Apr 25, 2018 in Electrical Engineering by Shimroz123
1 answer 27 views

A 12 -pole, 440 V, 50 Hz, 3 -phase synchronous motor takes a line current of 100 A at 0.8 pf leading. Neglecting losses, the torque developed will be

asked Apr 25, 2018 in Electrical Engineering by Shimroz123
0 answers 13 views

 A single phase, 2000V alternator has armature resistance and reactance of 0.8 ohm and 4.94 ohm respectively. The voltage regulation of the alternator at 100A, 0.8 leading pf is (A) 7% (B) - 8.9% (C) - 6.3% (D) 0%

asked Apr 14, 2018 in Electrical Engineering by Shimroz123
0 answers 16 views

The voltage regulation of an alternator having 0.75 leading p.f. load, no-load induced e.m.f. of 2400V and rated terminal voltage of 3000V is —————————————  A) 20% B) —20% C) 150 D) -26.7

asked Apr 9, 2018 in Electronics Engineering by Shimroz123
1 answer 91 views

An alternator has a phase sequence of RYB for its phase voltage. In case the direction of rotation of alternator is reversed, the phase sequence will become?

asked Mar 27, 2018 in Power system by Shimroz123
0 answers 308 views

Two generating stations G1 and G2 of ratings 10 MVA and 8 MVA respectively are linked by a line rated at 5 MVA, 0.1 Pu reactance. Each station has a reactance of 0.5 pu. If the base MVA is 10 MVA, short-circuit MVA of G1 is

asked May 24, 2018 in Power system by Shimroz123
1 answer 52 views

The corona loss on a particular system at 50 Hz is 1 kw/phase per km. The corona loss on the same system with supply frequency 25 Hz will be?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 41 views

Two synchronous generators G1, G2 are operating in parallel and are equally sharing KVAR (Lag) component of load. To shift part of KVAR from G2 to G1, while keeping terminal voltage fixed, the following action must be done

asked May 3, 2018 in Power system by Shimroz123

Welcome to electronics2electrical.com here you can ask questions related to electrical, electronics, mechanical, telecommunication, instrumentation, computer, mathematics, physics etc.
Be respectful to all the members. Do not copy and paste the answers from other websites which have copyright content. While asking question give full details about it.

Categories

Most popular tags

power motor dc circuit transformer voltage current used system phase resistance factor synchronous load ac energy induction electric generator series frequency between speed capacitor use electrical meter line difference control type mosfet transmission magnetic plant high single instrument bjt unit source advantages function diode and machine winding field define torque parallel amplifier supply shunt thyristor motors electricity arduino maximum time relay armature problem value on transformers types coil diagram state flow ratio material three formula starting direction theorem method emf operating efficiency digital wave microprocessor test instruments inductance loss measure operation connected signal low applications effect single-phase network temperature working constant losses different law wattmeter measuring compare controlled breaker drive device logic rc full switch flux wire resistivity disadvantages free of materials machines angle force converter conductor transistor gain open protection scr core measurement number bridge principle generators reactance circuits negative the friction iron loop short pole battery conservation steam resistors hysteresis computer using analog lines secondary station gate a rectifier inverter linear induced relays nuclear capacitance basic characteristics design direct work rotor electronics ammeter forces diesel damping rlc connection factors capacitors minimum insulation moving regulation running self systems air fault range main stability quality starter igbt eddy alternator ideal rl average 3-phase plants arc thermal error fuzzy biasing dielectric pressure balanced superposition errors copper rotation feedback impedance measured electronic electrons charge inductive transfer explain start off back curve over solar is three-phase tariff locomotive peak bias zener engineering commutator surge conductors rating universal potentiometer density permanent mechanical transducer capacity memory adc excitation two fuse pure harmonics application semiconductor inductor internal pmmc reaction welding resonance traction permeability breakers rms designed electromagnetic si generation brushes switching capacitive shaded rate 1 distribution resistor methods delta star oscillator reluctance simplification algebra 8085 boolean weston dynamometer insulating strength installation definition fuel heating earth units

8,503 questions

7,101 answers

134 comments

3,090 users

...