A consumer consumes. 600 kWh per day at a load factor of 0.40. If the consumer increases the load factor of 0.70 without increasing the maximum demand, what is the consumption of energy in kWh?

1 Answer

0 votes
by

A consumer consume. 600 kWh per day at a load factor of 0.40. If the coneumer increases the load factor of 0.70 without increasing the maximum demand, 1050 kWh is the consumption of energy in kWh.

Related questions

1 answer 15 views

What is the maximum value of a load which consume 500 KWh per day at a load factor of 0.40, if the consumer increases the load factor of 0.50 without increasing the maximum demand? 

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 23 views

An industrial consumer hall a daily load pattern of 2000 KW, 0.8 lag for 12 Hra and 1000 kW UPF for 1J Hr. The load factor i= _____. 

asked Mar 27, 2018 in Power system by Shimroz123
0 answers 15 views

Voltages phasors at the two terminals of a transmission line of length 70 km have a magnitude of 1.0 per unit but are 180 degree out of phase. Assuming that the maximum load current in the line is 1/5th of minimum 3-phase fault current. Which one of the following transmission line protection schemes ... pick up at 1.25 times the maximum load current (C) Pilot relaying system with directional comparison scheme (D) Pilot relaying system with segregated phase comparison scheme

asked May 25, 2018 in Power system by Shimroz123
0 answers 31 views

A meter whose constant is 600 revolutions/kWh makes 5 revolutions in 20 seconds. Calculate the load in kW. (1) 0.5 kW (2) 1 kW (3) 1.5 kW (4) 2 kW  

asked Apr 11, 2018 in Electrical Engineering by Shimroz123
1 answer 137 views

A 3-phase, 11 kv, 50 Hz, 200 kW load has a power factor of 0.8 lag. A delta connected 3-phase capacitor is used to improve the power factor to unity. The capacitance perphase of the capacitor in micro-farads is?

asked Mar 27, 2018 in Power system by Shimroz123
0 answers 19 views

A three phase transmission line delivers a load of 5 MW at 0.8 power factor lagging. Resistance of each conductor is 0.5 ohm / km. Receiving end voltage is 33 kV. If the line loss is not to exceed 10%, determine the length of the line.  (A) 7 km (B) 27.9 km (C) 56.8 km (D) 13.9 km

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
0 answers 88 views

A single phase 60 Hz generator supplies an inductive load of 4500kW at a power factor of 0.80 lagging by means of a 20 km long overhead transmission line. The line resistance and inductance are 0.0195 ohm and 0.60 mH per km. The voltage at the receiving end is required to be kept constant at 10.2 kV. Find the voltage regulation of the line.  (A) 12.59% (B) 16.34% (C) 32.68% (D) 41.15% 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 42 views

A 50 Hz, 4-pole, 500 MVA, 22 kV turbo-generator is delivering rated megavolt amperes at 0.8 power factor. Suddenly a fault occurs reducing in electric power output by 40%. Neglect losses and assume constant power input to the shaft. The accelerating torque in the generator in MNm at the time of fault will be  (A) 1.528 (B) 1.018 (C) 0.848 (D) 0.509

asked May 25, 2018 in Power system by Shimroz123
0 answers 44 views

The connected load of a consumer is 2 kW and his maximum demand is 1.5 kW. The load factor of the consumer is (a) 0.375 (b) 0.75 (c) 1.33 (d) None of these  

asked May 26, 2018 in Electric Power Transmission by Shimroz123
1 answer 83 views

The input of an A.C. circuit having power factor of 0.8 lagging is 40 kVA The power drawn by the circuit is?

asked Mar 25, 2018 in Electrical Engineering by Shimroz123
1 answer 21 views

A power station supplies the peak load of 60 Mw, 40 MW and 70 MW to three localities. The annual load factor is 0.50 p.u. and the diversity factor of the load at the station is 1.55. The maximum demand on the station and average load respectively will be 

asked Mar 27, 2018 in Power system by Shimroz123
0 answers 23 views

The constant of a given energy meter is 500 revolution/kWh. At the test 4.4 kW full load, meter completes 50 revolutions in 86 seconds. The percentage error of the meter is (a) –4.86% (b) 4.86% (c) 2.0% (d) 3.0%

asked May 26, 2018 in Electrical Measurements and Instrumentation by Shimroz123
0 answers 58 views

An energy meter has a constant of 600 rev/kWh. If the meter makes 10 revolutions in 20 s, what is the load in kW?  (A) 0.75 kW (B) 1.5 kW (C) 3 kW (D) 6 kW 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 117 views

The maximum demand of consumer is 2 kW and his daily energy consumption is 20 units. Its Load Factor is (1) 10.15% (2) 41.6 % (3) 50 % (4) 60% 

asked Apr 11, 2018 in Electrical Engineering by Shimroz123
1 answer 34 views

If the feedback factor of an amplifier is 0.1 and its gain without feedback is 40, then its gain with feedback is (a) – 13.3 (b) 200 (c) 8 (d) 10 

asked May 25, 2018 in Amplifier by Shimroz123
1 answer 32 views

A transformer operates 24 hours day at full -load. It's full -load efficiency is :  (A) equal all day efficiency (B) more than all -day efficiency (C) less than all -day efficiency (D) equal to maximum efficiency

asked Apr 30, 2018 in Electrical Engineering by Shimroz123
1 answer 16 views

The meter constant of a single-phase 230 V induction watt hour meter is 400 revolutions per kWh. The speed of the meter disc for a current of 10 A of 0.9 pf lagging will be

asked Apr 23, 2018 in Electrical Engineering by Shimroz123
0 answers 45 views

For a balanced three phase star connected load for which line voltage is 230V and per phase resistance and reactance is 6 Ohm and 8 Ohm respectively. Calculate: 1) phase voltage 2) line current 3) power factor 4) total power absorbed

asked Aug 12, 2018 in Basic electrical and electronics engineering by Quiz
1 answer 52 views

The corona loss on a particular system at 50 Hz is 1 kw/phase per km. The corona loss on the same system with supply frequency 25 Hz will be?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 43 views

For a short transmission line with r/x ratio of is 1.0, the regulation will be zero when the load power factor is

asked Apr 30, 2018 in Electrical Engineering by Shimroz123
0 answers 430 views

The base kV and base MVA are halved and the per unit impedance new value is 0.5. The per unit impedance of the original circuit element is (A) 0.25 (B) 0.5 (C) 0.625 (D) 1.0 

asked Jun 4, 2018 in Power system by Shimroz123
1 answer 44 views

The per unit impedance ofa circuit element is 0.15. If the base kV and base MVA are halved, then the new value of the per unit impedance of the circuit element will be?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 14 views

A 3-phase 11 kV generator feeds power to a constant power unity power factor load of 100 MW through a 3-phase transmission line. The line-to line voltage at the terminals of the machine is maintained constant at 11 kV. The per unit positive sequence impedance of the line based on 100 MVA and 11 kV is j0.2. The line to line voltage at the ... load to increase the line-to-line voltage at the load terminals to 11 kV is  (A) 100 MVAR (B) 10.1 MVAR (C) -100 MVAR (D) -10.1 MVAR

asked May 25, 2018 in Power system by Shimroz123
1 answer 12 views

A generating st ation has a maximum, demand of 20 mW, load factor of 60%, a plant capacity factor of 50% and a plant Use factor of 72%. What is the reserve capacity of the plant, if the plant, while running as per schedule, were fully loaded?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 17 views

A generating station has a maximum demand of 50 Mw, a load factor of 60%, a plant capacity factor of 45% and if the plant while running as per schedule, were fully loaded. The daily energy produced will be

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 35 views

The corona loss in a 50 Hz system is 0.25 kW/ph/km. At a frequency of 60 Hz, the corona loss would be   (a) 0.30 kW/ph/km (b) 0.36 kW/ph/km (c) 028 kW/ph/km (d) 0.21 kW/ph/km

asked May 13, 2018 in Power system by Shimroz123
0 answers 44 views

A plant with 10 MW installed capacity produces an annual output of 6 × 6 10 kWh and remains in operation for 2000 hours in a year. The Plant Use Factor is (A) 0.33 % (B) 3.33 % (C) 15 % (D) 30 % 

asked Jun 4, 2018 in Power system by Shimroz123
1 answer 22 views

The armature resistance of a permanent magnet dc motor is 0.8 Ohm. At no load, the motor draws 1.5 A from a supply voltage of 25 V and runs at 1500 rpm. The efficiency of the motor while it is operating on load at 1500 rpm drawing a current of 3.5 A from the same source will be  (A) 48.0% (B) 57.1% (C) 59.2% (D) 88.8%

asked May 17, 2018 in Electrical Machine by Shimroz123
0 answers 19 views

The efficiency of a transformer at full load 0.8 p.f lagging is 90%. Its efficiency at full load 0.8 p.f leading will be (1) Less than 90% (2) More than 90% (3) 90% (4) None of these 

asked Apr 11, 2018 in Electrical Engineering by Shimroz123
1 answer 20 views

At an industrial sub-station with a 4 MW load, a capacitor of 2 MVAR is installed to maintain the load power factor at 0.97 lagging. If the capacitor goes out of service, the load power factor becomes (A) 0.85 (B) 1.00 (C) 0.80 lag (D) 0.90 lag

asked May 25, 2018 in Power system by Shimroz123
1 answer 32 views

A 60 Hz, 320 km lossless line has Bending end voltage 1.0 p.u, The receiving end voltage on no load is?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 15 views

The e.m.f. induced in the armature of a shunt generator is 600 V. The armature resistance is 0.1 ohm. If the armature current is 200 A, the terminal voltage will be?

asked Mar 21, 2018 in DC generator by Shimroz123
0 answers 16 views

At maximum efficiency of a single-phase transformer, the load power factor is (A) unity (B) lagging (C) leading (D) zero 

asked Jun 4, 2018 in Single phase transformer by Shimroz123
1 answer 17 views

A simple phase transformer has a maximum efficiency of 90% at full load and unity power factor. Efficiency at half load at the same power factor is  (A) 86.7% (B) 88.26% (C) 88.9% (D) 87.8%

asked May 17, 2018 in Transformer by Shimroz123
1 answer 20 views

In a power generating station the Demand Factor and Load Factor are 0.5 and 0.2, respectively. If the connected load is 400 MW, the average demand is (A) 40 MW (B) 100 MW (C) 140 MW (D) 280 MW

asked Apr 25, 2018 in Electrical Engineering by Shimroz123
1 answer 27 views

A transformer has negative voltage regulation when its load power factor is   (1) Zero (2) Unity (3) Leading (4) Lagging

asked Apr 30, 2018 in Power system by Shimroz123
1 answer 44 views

In an alternator at lagging power factor the generated voltage per phase as compared to that at unity power factor?

asked Mar 18, 2018 in Alternator by Shimroz123
1 answer 15 views

The load of a consumer is generally measured in terms of : (A) Volts (B) Amperes (C) Ampere hour (D) kW

asked May 8, 2018 in Electrical Engineering by Shimroz123
1 answer 33 views

A 400 V, 50 Hz 30 hp, three-phase induction motor is drawing 50 A current at 0.8 power factor lagging. The stator and rotor copper losses are 1.5 kW and 900 W respectively. The friction and windage losses are 1050 W and the core losses are 1200 W. The air-gap power of the motor will be (A) 23.06 kW (B) 24.11 kW (C) 25.01 kW (D) 26.21 kW

asked May 17, 2018 in Electrical Machine by Shimroz123
1 answer 17 views

The load duration curve for unity load factor will be of  (1) Rectangular shape (2) Triangular shape (3) L -shape (4) I -shape

asked Apr 30, 2018 in Power system by Shimroz123
0 answers 31 views

A single phase energy meter has a constant of 1200 revolution/kWh. When a load of 200 W is connected, the disc rotates at 4.2 revolutions per min. If the load is on for 10 hours, the meter records an excess of   (a) 0.1 kWh (b) 0.2 kWh (c) 1.0 kWh (d) 2.0 kWh 

asked Apr 10, 2018 in Electrical Engineering by Shimroz123
2 answers 73 views

A heater takes 4 Amp at 250 volts. How much power does it consume? A. 1 KWatt B. 2 KWatt C. 3 KWatt D. 4 KWatt 

asked Apr 12, 2018 in Electrical Engineering by Shimroz123
0 answers 17 views

A diesel power station spends 0.25 kg/kWh fuel. If the calorific value is 10,000 kcal/kg then overall efficiency of the power station will be   (a) 25% (b) 30% (c) 34.4% (d) 100% 

asked Apr 10, 2018 in Electrical Engineering by Shimroz123
1 answer 13 views

A 500 kVA, 3-phase transformer has iron losses of 300 W and full load copper losses of 600 W. The percentage load at which the transformer is expected to have maximum efficiency is  (A) 50.0% (B) 70.7% (C) 141.4% (D) 200.0%

asked May 17, 2018 in Transformer by Shimroz123
1 answer 15 views

In a 2 kW, 200 V, 1000 rpm. DC series motor the torque at full load was found to be 0.3 N -m. The torque at half full load in N -m is :

asked Apr 29, 2018 in Electrical Machine by Shimroz123
0 answers 18 views

When the SCR conducts, the forward voltage drop will   (a) 0.7 V at all load current (b) 2 to 2.5 V at all load current (c) increases slightly with load current (d) remains constant with load current 

asked Apr 10, 2018 in Electrical Engineering by Shimroz123
1 answer 34 views

In load flow analysis, the load connected at a bus is represented as?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 23 views

The analog signal given below is sampled by 600 samples per second for m(t) = 3 sin 500 pt + 2 sin 700 pt then folding frequency is: (1) 500 Hz (2) 700 Hz (3) 300 Hz (4) 1400 Hz 

asked May 28, 2018 in Analog electronics circuits by Shimroz123

Welcome to electronics2electrical.com here you can ask questions related to electrical, electronics, mechanical, telecommunication, instrumentation, computer, mathematics, physics etc.
Be respectful to all the members. Do not copy and paste the answers from other websites which have copyright content. While asking question give full details about it.

Categories

Most popular tags

power motor dc circuit transformer voltage current used system phase resistance factor synchronous load ac energy induction electric generator series frequency between speed capacitor use electrical meter line difference control type mosfet transmission magnetic plant high single instrument bjt unit source advantages function diode and machine winding field define torque parallel amplifier supply shunt thyristor motors electricity arduino maximum time relay armature problem value on transformers types coil diagram state flow ratio material three formula starting direction theorem method emf operating efficiency digital wave microprocessor test instruments inductance loss measure operation connected signal low applications effect single-phase network temperature working constant losses different law wattmeter measuring compare controlled breaker drive device logic rc full switch flux wire resistivity disadvantages free of materials machines angle force converter conductor transistor gain open protection scr core measurement number bridge principle generators reactance circuits negative the friction iron loop short pole battery conservation steam resistors hysteresis computer using analog lines secondary station gate a rectifier inverter linear induced relays nuclear capacitance basic characteristics design direct work rotor electronics ammeter forces diesel damping rlc connection factors capacitors minimum insulation moving regulation running self systems air fault range main stability quality starter igbt eddy alternator ideal rl average 3-phase plants arc thermal error fuzzy biasing dielectric pressure balanced superposition errors copper rotation feedback impedance measured electronic electrons charge inductive transfer explain start off back curve over solar is three-phase tariff locomotive peak bias zener engineering commutator surge conductors rating universal potentiometer density permanent mechanical transducer capacity memory adc excitation two fuse pure harmonics application semiconductor inductor internal pmmc reaction welding resonance traction permeability breakers rms designed electromagnetic si generation brushes switching capacitive shaded rate 1 distribution resistor methods delta star oscillator reluctance simplification algebra 8085 boolean weston dynamometer insulating strength installation definition fuel heating earth units
...