A 3-phase, 11 kv, 50 Hz, 200 kW load has a power factor of 0.8 lag. A delta connected 3-phase capacitor is used to improve the power factor to unity. The capacitance perphase of the capacitor in micro-farads is?

1 Answer

0 votes
by

A 3-phase, 11 kv, 50 Hz, 200 kW load has a power factor of 0.8 lag. A delta connected 3-phase capacitor is used to improve the power factor to unity. The capacitance perphase of the capacitor in micro-farads is 1.316.

Related questions

1 answer 46 views

A 100 MVA, 11 KV, 3-phase, 50 Hz, 8—pole synchronous generator has an inertia constant H equal to 4 seconds. The stored energy in the rotor of the generator at synchronous speed will be  A) 100 MJ B) 400 MJ C) 800 MJ D) 12.5 MJ

asked May 20, 2018 in Synchronous machine by Shimroz123
1 answer 42 views

A 50 Hz, 4-pole, 500 MVA, 22 kV turbo-generator is delivering rated megavolt amperes at 0.8 power factor. Suddenly a fault occurs reducing in electric power output by 40%. Neglect losses and assume constant power input to the shaft. The accelerating torque in the generator in MNm at the time of fault will be  (A) 1.528 (B) 1.018 (C) 0.848 (D) 0.509

asked May 25, 2018 in Power system by Shimroz123
1 answer 14 views

A 3-phase 11 kV generator feeds power to a constant power unity power factor load of 100 MW through a 3-phase transmission line. The line-to line voltage at the terminals of the machine is maintained constant at 11 kV. The per unit positive sequence impedance of the line based on 100 MVA and 11 kV is j0.2. The line to line voltage at the ... load to increase the line-to-line voltage at the load terminals to 11 kV is  (A) 100 MVAR (B) 10.1 MVAR (C) -100 MVAR (D) -10.1 MVAR

asked May 25, 2018 in Power system by Shimroz123
1 answer 40 views

A 4000 kVA, 11 kV/132 kV delta-star connected 3-phase transformer has reactance, x1 = 0.12 p.u. The actual value of x1 referred to the low voltage side is (A) 0.85 Ω (B) 3.63 Ω (C) 36.3 Ω (D) 252 Ω

asked Apr 28, 2018 in Power system by Shimroz123
1 answer 23 views

An industrial consumer hall a daily load pattern of 2000 KW, 0.8 lag for 12 Hra and 1000 kW UPF for 1J Hr. The load factor i= _____. 

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 33 views

A 400 V, 50 Hz 30 hp, three-phase induction motor is drawing 50 A current at 0.8 power factor lagging. The stator and rotor copper losses are 1.5 kW and 900 W respectively. The friction and windage losses are 1050 W and the core losses are 1200 W. The air-gap power of the motor will be (A) 23.06 kW (B) 24.11 kW (C) 25.01 kW (D) 26.21 kW

asked May 17, 2018 in Electrical Machine by Shimroz123
1 answer 27 views

A 12 -pole, 440 V, 50 Hz, 3 -phase synchronous motor takes a line current of 100 A at 0.8 pf leading. Neglecting losses, the torque developed will be

asked Apr 25, 2018 in Electrical Engineering by Shimroz123
0 answers 38 views

A balanced Delta connected load supplied with 440 V 50 Hz three phase AC supply has R=10 Ohm and L=0.6 mH in is each arm. Calculate line and phase current, active power.

asked Aug 12, 2018 in Basic electrical and electronics engineering by Quiz
0 answers 54 views

A 1-phase, 7.46 kW motor is supplied from a 400 V, 50 Hz A.C mains. Its efficiency is 85% and power factor is 0.8 lagging. Calculate the KVA input (1) 9.56 kVA (2) 5.4 Kva (3) 10.97 kVA (4) 8.6 kVA 

asked Apr 11, 2018 in Electrical Engineering by Shimroz123
1 answer 35 views

The corona loss in a 50 Hz system is 0.25 kW/ph/km. At a frequency of 60 Hz, the corona loss would be   (a) 0.30 kW/ph/km (b) 0.36 kW/ph/km (c) 028 kW/ph/km (d) 0.21 kW/ph/km

asked May 13, 2018 in Power system by Shimroz123
0 answers 15 views

A 50 Hz, 3—phase induction motor has a full load speed of 1440 rpm. The number of poles of the motor is:   (A)4 (8)6 (0)12  (D)8

asked Apr 9, 2018 in Electrical Engineering by Shimroz123
1 answer 148 views

A 50 Hz, 4 pole turboalternator rated at 20 MVA. 13.2 KV has an inertia constant H = 4 KW sec/KVA. The K.E. stored in the rotor at synchronous speed is

asked May 3, 2018 in Electric Power Transmission by Shimroz123
1 answer 62 views

The corona loss of a 3-phase transmission line is 100 kW at 60 kV/phase and 25 kW at 50 kV/phase. The disruptive critical voltage is (A) 40 kV (B) 43.6 kV (C) 49.6 kV (D) 50 kV

asked Apr 25, 2018 in Electrical Engineering by Shimroz123
0 answers 19 views

A three phase transmission line delivers a load of 5 MW at 0.8 power factor lagging. Resistance of each conductor is 0.5 ohm / km. Receiving end voltage is 33 kV. If the line loss is not to exceed 10%, determine the length of the line.  (A) 7 km (B) 27.9 km (C) 56.8 km (D) 13.9 km

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
0 answers 88 views

A single phase 60 Hz generator supplies an inductive load of 4500kW at a power factor of 0.80 lagging by means of a 20 km long overhead transmission line. The line resistance and inductance are 0.0195 ohm and 0.60 mH per km. The voltage at the receiving end is required to be kept constant at 10.2 kV. Find the voltage regulation of the line.  (A) 12.59% (B) 16.34% (C) 32.68% (D) 41.15% 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 29 views

A 3 phase, 400 volts, 50 Hz, 100 kW, 4 pole squirrel cage induction motor with a rated slip of 2% will have a rotor speed of: (A) 1500 rpm (B) 1470 rpm (C) 1530 rpm (D) 1570 rpm

asked Apr 11, 2018 in Computer Engineering by Shimroz123
0 answers 15 views

A 3-phase, 2 pole, 11 kV, 10000 kVA alternator has earthed neutral through a resistance of 7.0Ω. The machine has current balance protection which operates if out of balance current exceeds 20% of full load. Determine %age of winding protected against earth fault (1) 10.6% (2) 11.6% (3) 10.9% (4) 11.2% 

asked Apr 11, 2018 in Electrical Engineering by Shimroz123
1 answer 16 views

A 400 V, 15 kW, 4-pole, 50 Hz, Y-connected induction motor has full load slip of 4%. The output torque of the machine at full load is  (A) 1.66 Nm (B) 95.50 Nm (C) 99.47 Nm (D) 624.73 Nm

asked May 17, 2018 in Induction Machine by Shimroz123
1 answer 15 views

In a 2 kW, 200 V, 1000 rpm. DC series motor the torque at full load was found to be 0.3 N -m. The torque at half full load in N -m is :

asked Apr 29, 2018 in Electrical Machine by Shimroz123
1 answer 52 views

The corona loss on a particular system at 50 Hz is 1 kw/phase per km. The corona loss on the same system with supply frequency 25 Hz will be?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 16 views

The synchronous speed for the seventh space harmonic mmf wave of a 3-phase, 8-pole, 50 Hz induction machine is  (A) 107.14 rpm in forward direction (B) 107.14 rpm in reverse direction (C) 5250 rpm in forward direction (D) 5250 rpm in reverse direction

asked May 17, 2018 in Induction Machine by Shimroz123
0 answers 45 views

For a balanced three phase star connected load for which line voltage is 230V and per phase resistance and reactance is 6 Ohm and 8 Ohm respectively. Calculate: 1) phase voltage 2) line current 3) power factor 4) total power absorbed

asked Aug 12, 2018 in Basic electrical and electronics engineering by Quiz
1 answer 80 views

The locked rotor current in a 3-phase, star connected 15 , kW 4 , pole 230 V , 50 Hz induction motor at rated conditions is 50 A. Neglecting losses and magnetizing current, the approximate locked rotor line current drawn when the motor is connected to a 236 , V 57 Hz supply is  (A) 58.5 A (B) 45.0 A (C) 42.7 A (D) 55.6 A

asked May 17, 2018 in Electrical Machine by Shimroz123
0 answers 95 views

An auto transformer having a transformation ratio of 0.8 supplies a load of 10 kW. The power transferred inductively from the primary to secondary is (a) 2 kW (b) 4 kW (c) 8 kW (d) 10 kW 

asked May 25, 2018 in Autotransformer by Shimroz123
0 answers 17 views

A three phase 50 Hz, 400 kV transmission line is 300 km long. The line inductance is 0.97 mH/km per phase and capacitance is 0.0115 mF/km per phase. Assume a loss less line. Determine the line wavelength (a line phase constant).  (A) 1250 km (B) 6578 km (C) 4990 km (D) 2445 km 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 26 views

A 500 MW, 3-phase, Y-connected synchronous generator has a rated voltage of 21.5 kV at 0.85 p.f. The line current when operating at full load rated conditions will be  (A) 13.43 kA (B) 15.79 kA (C) 23.25 kA (D) 27.36 kA

asked May 17, 2018 in Synchronous machine by Shimroz123
1 answer 18 views

A generating station has a maximum demand of 50 Mw, a load factor of 60%, a plant capacity factor of 45% and if the plant while running as per schedule, were fully loaded. The daily energy produced will be

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 91 views

A transmission line has 1 P.0 impedance on a base of 11 KV, 100 MVA. On a base of 55 KV. it will have a P.0 impedance of

asked May 3, 2018 in Electric Power Transmission by Shimroz123
0 answers 42 views

If 5000 kW power is transmitted at 220 kV in place of 11 kV, reduction in the value of electric current will be (a) 90% (b) 95% (c) 5% (d) 10% 

asked May 26, 2018 in Electric Power Transmission by Shimroz123
1 answer 14 views

A solar cell of 350 V is feeding power to an ac supply of 440 V, 50 Hz through a 3-phase fully controlled bridge converter. A large inductance is connected in the dc circuit to maintain the dc current at 20 A. If the solar cell resistance is 0.5 Ohm ,then each thyristor will be reverse biased for a period of  (A) 125o (B) 120o (C) 60o (D) 55o

asked May 18, 2018 in Power electronics converters by Shimroz123
1 answer 28 views

The maximum possible power of a 3-phase synchronous motor with synchronous reactance 0.8 p.u. connected to a bus-bar of 1.0 p.u. and excitation adjusted to 1.2 p.u. is (A) 0.5 p.u. (B) 0.96 p.u. (C) 1.5 p.u. (D) 1.8 p.u.

asked Apr 25, 2018 in Electrical Engineering by Shimroz123
0 answers 23 views

A Power system has a total load of 1260 MW at 50 Hz. The load varies 1.5% for every 1% change in frequency. Find the steady state frequency deviation, when a 60 MW load is suddenly dripped if there is no speed control.  (A) 1.667 Hz (B) 50 Hz (C) No change (D) 3.32 Hz 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 32 views

A 60 Hz, 320 km lossless line has Bending end voltage 1.0 p.u, The receiving end voltage on no load is?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 115 views

A 500 MVA, 11 KV synchronous generator has 0.2 p.u. synchronous reactance. The p.u. synchronous reactance on the base values of 100 MVA and 22 KV is  A) 0.16 B) 0.01 C) 4.0 D) 0.25

asked May 17, 2018 in Synchronous machine by Shimroz123
1 answer 118 views

A 60 Hz, 4 pole turbo generator rated 100 MVA, 13.8 KV has an inertia constant of 10 MJ/MVA. Find the stored energy in the rotor at synchronous speed.  (A) 10 MJ (B) 100 J (C) 1000 J (D) 1000 MJ 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
0 answers 69 views

The magnetizing reactance of a 4 kV/ 400 V, 50 Hz single-phase transformer on low voltage side is 35 Ω. The magnetizing reactance on the high voltage side is (A) 0.35 Ω (B) 3.5 Ω (C) 350 Ω (D) 3500 Ω

asked Jun 4, 2018 in Single phase transformer by Shimroz123
1 answer 41 views

The hysteresis and eddy current losses of a single phase transformer working on 200 V, 50 Hz supply are Ph and Pe respectively. The percentage decrease in these when operated on a 160 V, 40 Hz supply are   (a) 32, 36 (b) 20, 36 (c) 25, 50 (d) 40, 80 

asked May 13, 2018 in Transformer by Shimroz123
0 answers 546 views

A 30 MVA, 15 KV, 1500 rpm, 3 phase synchronous generator connected to a power grid has a synchronous reactance of 9 ohm per phase. If the exciting voltage is 12 kV (line to neutral) and the system voltage is 17.3 kV (line to line), Calculate the maximum power that generator can deliver before it falls out of step (losses synchronous).  (A) 39.952 MW (B) 78.349 MW (C) 16.67 MW (D) 112.89 MW

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 18 views

A three-phase, 440 V, 50 Hz ac mains fed thyristor bridge is feeding a 440 V dc, 15 kW, 1500 rpm separately excited dc motor with a ripple free continuous current in the dc link under all operating conditions, Neglecting the losses, the power factor of the ac mains at half the rated speed is  (A) 0.354 (B) 0.372 (C) 0.90 (D) 0.955

asked May 18, 2018 in Power electronics converters by Shimroz123
2 answers 58 views

The synchronous speed of an 8 pole induction motor supplied power from a 50 Hz source will be ?

asked Dec 31, 2017 in Electrical Engineering by Quiz
0 answers 12 views

An induction motor operating at 0.8 pf lagging is consuming 300 kW. A zero real power consuming synchronous motor is connected across the induction motor to raise the pf to 0.92 lagging. The reactive power drawn by the synchronous motor is a. - 352 kVAR b. - 225 kVAR c. - 127.8 kVAR d. - 97.2 kVAR

asked May 24, 2018 in Induction Machine by Shimroz123
1 answer 17 views

A simple phase transformer has a maximum efficiency of 90% at full load and unity power factor. Efficiency at half load at the same power factor is  (A) 86.7% (B) 88.26% (C) 88.9% (D) 87.8%

asked May 17, 2018 in Transformer by Shimroz123
1 answer 27 views

A transformer has negative voltage regulation when its load power factor is   (1) Zero (2) Unity (3) Leading (4) Lagging

asked Apr 30, 2018 in Power system by Shimroz123
0 answers 14 views

One 200 KVA transformer has an iron loss of 1 KW and full load Cu loss of 2 KW. Its load KVA corresponding to maximum efficiency is:  (A) 100 KVA (B) 141.4 KVA (C) 50 KVA (D) 200 KVA 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 13 views

The low voltage winding of a 400/230 V, 1-phase, 50 Hz transformer is to be connected to a 25 Hz, the supply voltage should be

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 10 views

A three phase 50 Hz line consists of three conductors each of diameter 21 mm, The spacing between the conductors all follows: A - B = 3m, B - C = 5m, C - A = 3.6m If the line operates at 132 k V, the reactive voltampere generatd by the line per km is?

asked Mar 27, 2018 in Power system by Shimroz123
0 answers 52 views

A dominant pole compensated op-amp has openloop gain of 100 dB and -3 dB bandwidth of 50 Hz. If it is connected as inverting amplifier for a gain of 20 dB the -3 dB bandwidth is about  A) 500 kHz B) 50 kHz C) 5 kHz D) 500 Hz

asked Apr 5, 2018 in Electronics Engineering by Shimroz123
0 answers 108 views

A single phase transformer rated at 3000 kVA, 69 kV 4.16 kV, 60 Hz has a total internal impedance Zp of 127 ohm, referred to the primary side. Calculate the primary current if the secondary is accidentally short circuited.  (A) 43.5 A (B) 543 A (C) 9006 A (D) 721 A 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 16 views

 A single-phase transmission line of impedance j 0.8 ohm supplies a resistive load of 500 A at 300 V. The sending end power factor is?

asked Mar 27, 2018 in Power system by Shimroz123
0 answers 11 views

A 3-phase, 50 Hz, 500 V induction motor develops 20 hp at slip of 5%. Mechanical losses are 1 hp, and stator loss is 1 kW. The efficiency will be   (a) 95.3% (b) 90.5% (c) 91.3% (d) 85.3% 

asked Apr 10, 2018 in Electrical Engineering by Shimroz123

Welcome to electronics2electrical.com here you can ask questions related to electrical, electronics, mechanical, telecommunication, instrumentation, computer, mathematics, physics etc.
Be respectful to all the members. Do not copy and paste the answers from other websites which have copyright content. While asking question give full details about it.

Categories

Most popular tags

power motor dc circuit transformer voltage current used system phase resistance factor synchronous load ac energy induction electric generator series frequency between speed capacitor use electrical meter line difference control type mosfet transmission magnetic plant high single instrument bjt unit source advantages function diode and machine winding field define torque parallel amplifier supply shunt thyristor motors electricity arduino maximum time relay armature problem value on transformers types coil diagram state flow ratio material three formula starting direction theorem method emf operating efficiency digital wave microprocessor test instruments inductance loss measure operation connected signal low applications effect single-phase network temperature working constant losses different law wattmeter measuring compare controlled breaker drive device logic rc full switch flux wire resistivity disadvantages free of materials machines angle force converter conductor transistor gain open protection scr core measurement number bridge principle generators reactance circuits negative the friction iron loop short pole battery conservation steam resistors hysteresis computer using analog lines secondary station gate a rectifier inverter linear induced relays nuclear capacitance basic characteristics design direct work rotor electronics ammeter forces diesel damping rlc connection factors capacitors minimum insulation moving regulation running self systems air fault range main stability quality starter igbt eddy alternator ideal rl average 3-phase plants arc thermal error fuzzy biasing dielectric pressure balanced superposition errors copper rotation feedback impedance measured electronic electrons charge inductive transfer explain start off back curve over solar is three-phase tariff locomotive peak bias zener engineering commutator surge conductors rating universal potentiometer density permanent mechanical transducer capacity memory adc excitation two fuse pure harmonics application semiconductor inductor internal pmmc reaction welding resonance traction permeability breakers rms designed electromagnetic si generation brushes switching capacitive shaded rate 1 distribution resistor methods delta star oscillator reluctance simplification algebra 8085 boolean weston dynamometer insulating strength installation definition fuel heating earth units

8,450 questions

7,047 answers

132 comments

3,085 users

...