16 views
in Power system by

The charging current per kill of the line is?

1 Answer

0 votes
by

The charging current per kill of the line is 0.497 Amp.

Related questions

1 answer 20 views

A 800 kV transmission line is having per phase line inductance of 1.1 mH/km and per phase line capacitance of 11.68 nF/km. Ignoring the length of the line, its ideal power transfer capability in MW is (A) 1204 MW (B) 1504 MW (C) 2085 MW (D) 2606 MW

asked May 25, 2018 in Power system by Shimroz123
0 answers 15 views

Voltages phasors at the two terminals of a transmission line of length 70 km have a magnitude of 1.0 per unit but are 180 degree out of phase. Assuming that the maximum load current in the line is 1/5th of minimum 3-phase fault current. Which one of the following transmission line protection schemes ... pick up at 1.25 times the maximum load current (C) Pilot relaying system with directional comparison scheme (D) Pilot relaying system with segregated phase comparison scheme

asked May 25, 2018 in Power system by Shimroz123
1 answer 19 views

A 20-MVA, 6.6-kV, 3-phase alternator is connected to a 3-phase transmission line. The per unit positive-sequence, negative-sequence and zero-sequence impedances of the alternator are j0.1, j0.1 and j0.04 respectively. The neutral of the alternator is connected to ground through an inductive reactor of j0.05 p.u. The per unit positive-, ... The voltage of the alternator neutral with respect to ground during the fault is  (A) 513.8 V (B) 889.9 V (C) 1112.0 V (D) 642.2 V

asked May 25, 2018 in Power system by Shimroz123
0 answers 20 views

The zero sequence current of a generator for line to ground fault is j 2.4 p.u. The current through the neutral during the fault is (a) j 0.8 p.u (b) j 2.4 p.u. (c) j 0.24 p.u. (d) j 7.2 p.u. 

asked May 25, 2018 in Power system by Shimroz123
0 answers 45 views

For a balanced three phase star connected load for which line voltage is 230V and per phase resistance and reactance is 6 Ohm and 8 Ohm respectively. Calculate: 1) phase voltage 2) line current 3) power factor 4) total power absorbed

asked Aug 12, 2018 in Basic electrical and electronics engineering by Quiz
1 answer 11 views

A 100 pF capacitor has a maximum charging current of 150 μA.What is the slew rate ? (A) 1.5 V/μs (B) 1.05 V/μs (C) 0.15mV/s (D) 10.5 mV/s

asked Apr 25, 2018 in Electrical Engineering by Shimroz123
1 answer 15 views

What is the maximum value of a load which consume 500 KWh per day at a load factor of 0.40, if the consumer increases the load factor of 0.50 without increasing the maximum demand? 

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 14 views
0 answers 430 views

The base kV and base MVA are halved and the per unit impedance new value is 0.5. The per unit impedance of the original circuit element is (A) 0.25 (B) 0.5 (C) 0.625 (D) 1.0 

asked Jun 4, 2018 in Power system by Shimroz123
1 answer 52 views

The corona loss on a particular system at 50 Hz is 1 kw/phase per km. The corona loss on the same system with supply frequency 25 Hz will be?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 46 views

The per unit impedance ofa circuit element is 0.15. If the base kV and base MVA are halved, then the new value of the per unit impedance of the circuit element will be?

asked Mar 27, 2018 in Power system by Shimroz123
2 answers 73 views

 The no-load current drawn by transformer is usually what per cent of the full-load current ?

asked Mar 27, 2018 in Transformer by Shimroz123
1 answer 40 views

The inductance of single phase two wire power transmission line per km gets doubled when the  (a) Distance between wires is doubled  (b) Distance between the wires is increased four fold  (c) Distance between the wires is increased as square of the original distance  (d) Radius of the wire is doubled

asked May 13, 2018 in Electric Power Transmission by Shimroz123
1 answer 24 views

For 11kV line the inductance per km per phase will be of the order of:  (A) 1 H (B) 0.1 H (C) 1 mH (D) 0.1 mH

asked May 8, 2018 in Electric Power Transmission by Shimroz123
1 answer 18 views

For 11 kV line the capacitance per km per phase will be of the order of:  (A) 1 Farad (B) 0.1 Farad (C) 0.01 Farad (D) 0.01 microF

asked May 8, 2018 in Electric Power Transmission by Shimroz123
1 answer 10 views

How many characters per sec (7 bits + 1 parity) can be transmitted over a 2400 bps line if the transfer is synchronous (1 start bit and 1 stop bit)?  A) 300 B) 240 C) 250 D) 275

asked Apr 11, 2018 in Computer Engineering by Shimroz123
0 answers 17 views

A three phase 50 Hz, 400 kV transmission line is 300 km long. The line inductance is 0.97 mH/km per phase and capacitance is 0.0115 mF/km per phase. Assume a loss less line. Determine the line wavelength (a line phase constant).  (A) 1250 km (B) 6578 km (C) 4990 km (D) 2445 km 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
0 answers 20 views

A synchronous condenser is used at the receiving end of a transmission line for (A) supplying lagging kVA (B) voltage control (C) frequency control (D) maintaining a higher voltage than at the sending end 

asked Jun 4, 2018 in Power system by Shimroz123
0 answers 17 views

The inductance of a line is minimum when (a) GMD is high (b) GMR is high (c) Both (a) and (b) (d) GMD is low, but GMR is high

asked May 25, 2018 in Power system by Shimroz123
1 answer 16 views

The transmission line distance protection relay having the property of being inherently directional is (A) impedance relay (B) MHO relay (C) OHM relay (D) reactance relay

asked May 25, 2018 in Power system by Shimroz123
1 answer 21 views

An 800 kV transmission line has a maximum power transfer capacity of P. If it is operated at 400 kV with the series reactance unchanged, the new maximum power transfer capacity is approximately (A) P (B) 2P (C) P / 2 (D) P / 4

asked May 25, 2018 in Power system by Shimroz123
1 answer 16 views

The concept of an electrically short, medium and long line is primarily based on the  A) Nominal voltage of the line B) Physical length of the line C) Wave length of the line D) Power transmitted over the line

asked May 20, 2018 in Power system by Shimroz123
1 answer 12 views

The transmission line feeding power on either side of the main transmission line is called?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 19 views

The function of the earth wire in an extra high voltage line is to?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 73 views

The X:R ratio of 220 kV line as compared to 400 kV line is?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 20 views

A two conductor 1 - pi line operates at 50 Hz.The diameter of each conductor is 20 mm and the spacing between the conductors is 3m, The height of conductor above the ground is 6 m. The capacitance of the line to neutral will be?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 15 views

A two conductor 1 - pi line operates at 50 Hz.The diameter of each conductor is 4 cm and are spaced 6 m apart. What is the capacitive susceptance to neutral per km?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 11 views

A two conductor 1 - pi line operates at 50 Hz. The diameter of each conductor is 2 cm and are spaced 3m apart. What is the line to line capacitance ?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 47 views

A 100 km long transmission line is loaded at 110 kV.if the loss of line is 5 MW and the load is 150 MVA, the resistance of the line is?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 11 views

The yearly load duration curve of a power plant is a straight line. The maximum load is 750 MW and the minimum load is 600 Mw. The capacity of the plant is 900 MW. What is the capacity factor and utilization factor? 

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 63 views

A consumer consumes. 600 kWh per day at a load factor of 0.40. If the consumer increases the load factor of 0.70 without increasing the maximum demand, what is the consumption of energy in kWh?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 8 views

As per Electricity Act, ____________means any line which is used for carrying electricity for any purpose.  (A) Electric line (B) Transmission line (C) All of the above (D) None of the above

asked May 8, 2018 in Electrical Engineering by Shimroz123
1 answer 21 views

 A power system is subjected to a fault which makes the zero sequence component of current equal to zero. The nature of fault current is: A) Double line to ground fault B) Line to line fault C) Line to ground fault D) Three-phase to ground fault

asked Jun 4, 2018 in Power system by Shimroz123
1 answer 84 views

The skin effect in conductors is due to non uniform distribution of current in it and major portion of current is near the _______ of conductor.  (1) Surface (2) Center (3) Complete cross section area (4) Axis

asked Apr 30, 2018 in Power system by Shimroz123
0 answers 4 views

Surge impedance loading of a line is proportional to  

asked May 25, 2018 in Power system by Shimroz123
1 answer 25 views

A loss less transmission line having Surge Impedance Loading (SIL) of 2280 MW is provided with a uniformly distributed series capacitive compensation of 30%. Then, SIL of the compensated transmission line will be (A) 1835 MW (B) 2280 MW (C) 2725 MW (D) 3257 MW

asked May 25, 2018 in Power system by Shimroz123
1 answer 31 views

A voltage of 1000 kV is applied to an overhead line with its receiving end open. If the surge impedance of the line is 500 ohm, then the total surge power in the line ill

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 115 views

A 100 km transmission line is designed for a nominal voltage of 132 kV and consists of one conductor per phase. The line reactance is 0.726 ohm/km. The static transmission capacity of the line, in MW, would be   (a) 240 (b) 132 (c) 416 (d) 720

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 15 views

Choose two appropriate auxiliary components of a HVDC transmission system from the following P. D.C line inductor Q. A.C line inductor R. Reactive power sources S. Distance relays on D.C line T. Series capacitance on A.C. line  (A) P and Q (B) P and R (C) Q and S (D) S and T

asked May 25, 2018 in Power system by Shimroz123
1 answer 13 views

An HVDC link consist of rectifier, inverter transmission line and other equipments. Which one of the following is true for this link ?  (A) The transmission line produces/ supplies reactive power (B) The rectifier consumes reactive power and the inverter supplies reactive power from/ to the respective connected ... power to/ from the respective connected AC systems (D) Both the converters (rectifier and inverter) consume reactive power from the respective connected AC systems

asked May 25, 2018 in Power system by Shimroz123
1 answer 15 views

For a fixed value of complex power flow in a transmission line having a sending and voltage V, the real power loss will be proportional to  A) V B) v2 C) 1/V2 D)1/V

asked May 20, 2018 in Power system by Shimroz123
1 answer 14 views

Which of the two generalized constants of a transmission line are equal?  (a) B & C (B) A & B (c) A & D (D) B & D

asked May 13, 2018 in Power system by Shimroz123
1 answer 29 views

If an unsymmetrical line to ground fault occurs at the secondary terminals of a delta/star, ungrounded transformer, then  (A) zero sequence currents are present on both sides of the transformer  (B) zero sequence currents are absent on both sides of the transformer  (C) zero sequence currents are present on the secondary side but not on the primary side  (D) zero sequence currents are present on the primary side but not on the secondary side

asked Apr 29, 2018 in Power system by Shimroz123
2 answers 95 views

The sending end and receiving end voltages of a three-phase transmission line are 10 kV/ph and 9.5 kV/ph, respectively. If the resistance drop is 150 V/ph and receiving end power factor is 0.8, the sending end power factor is (A) 0.745 lagging (B) 0.775 lagging (C) 0.8 lagging (D) 0.85 lagging

asked Apr 28, 2018 in Power system by Shimroz123
1 answer 17 views

A two conductor 1 - pi line operates at 50 Hz. The diameter of each conductor is 20 mm and the spacing between conductors is 3m. What is the inductance of each conductor per km?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 21 views

The line conductor of a transmission line has an overall diameter of 19.53 mm, weight 0.844 kg/m and an ultimate breaking strength of 7950 kg. If the factor of safety is to be 2, when conductor has an ice of 1 kg/m and a horizontal wind pressure of 1.5 kg/m. What is the vertical sag, corresponding to this loading for a 300 m span level supports?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 18 views

To increase the visual critical voltage of cporona for an overhead line, one solid phase-conductor is replaced by a "bundle" of four smaller conductors per phase, having an aggregate cross-sectional area equal to that of the solid conductor. If the radius of the solid conductor is 40 mm, then the radius of each of the bundle conductors would be?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 16 views

The conductor of a 10 km long, single phase, two wire line are separated by a distance of 1.5 m. The diameter of each conductor is 1 cm, If the conductors are of copper, the inductance of the circuit is

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 11 views

For enhancing the power transmission in along EHV transmission line, the most preferred method is to connect a  (A) Series inductive compensator in the line (B) Shunt inductive compensator at the receiving end (C) Series capacitive compensator in the line (D) Shunt capacitive compensator at the sending end

asked May 25, 2018 in Power system by Shimroz123

Welcome to electronics2electrical.com here you can ask questions related to electrical, electronics, mechanical, telecommunication, instrumentation, computer, mathematics, physics etc.
Be respectful to all the members. Do not copy and paste the answers from other websites which have copyright content. While asking question give full details about it.

Categories

Most popular tags

power motor dc circuit transformer voltage current used system phase resistance factor synchronous load ac energy induction electric generator series frequency between speed capacitor use electrical meter line difference control type mosfet transmission magnetic plant high single instrument bjt unit source advantages function diode and machine winding field define torque parallel amplifier supply shunt thyristor motors electricity arduino maximum time relay armature problem value on transformers types coil diagram state flow ratio material three formula starting direction theorem method emf operating efficiency digital wave microprocessor test instruments inductance loss measure operation connected signal low applications effect single-phase network temperature working constant losses different law wattmeter measuring compare controlled breaker drive device logic rc full switch flux wire resistivity disadvantages free of materials machines angle force converter conductor transistor gain open protection scr core measurement number bridge principle generators reactance circuits negative the friction iron loop short pole battery conservation steam resistors hysteresis computer using analog lines secondary station gate a rectifier inverter linear induced relays nuclear capacitance basic characteristics design direct work rotor electronics ammeter forces diesel damping rlc connection factors capacitors minimum insulation moving regulation running self systems air fault range main stability quality starter igbt eddy alternator ideal rl average 3-phase plants arc thermal error fuzzy biasing dielectric pressure balanced superposition errors copper rotation feedback impedance measured electronic electrons charge inductive transfer explain start off back curve over solar is three-phase tariff locomotive peak bias zener engineering commutator surge conductors rating universal potentiometer density permanent mechanical transducer capacity memory adc excitation two fuse pure harmonics application semiconductor inductor internal pmmc reaction welding resonance traction permeability breakers rms designed electromagnetic si generation brushes switching capacitive shaded rate 1 distribution resistor methods delta star oscillator reluctance simplification algebra 8085 boolean weston dynamometer insulating strength installation definition fuel heating earth units

8,450 questions

7,047 answers

132 comments

3,085 users

...