4 views
in Electronics Engineering by

Your answer

Thanks for your contribution. Feel free to answer this question. Please avoid short answer. Your answer is most welcome. Be genuine.

Upload image or document:

Your name to display (optional):
Privacy: Your email address will only be used for sending these notifications.
Anti-spam verification:
Are you a robot ? (Y = Yes / N = No)
To avoid this verification in future, please log in or register.

1 Answer

0 votes
by

A low-loss transmission line has  R<<ωL; G<<ωC.

Related questions

0 answers 18 views

The power loss in a transmission line depends on (a) current in the line. (b) resistance of the line. (c) length of the line. (d) All of the above 

asked May 26, 2018 in Electric Power Transmission by Shimroz123
1 answer 25 views

A loss less transmission line having Surge Impedance Loading (SIL) of 2280 MW is provided with a uniformly distributed series capacitive compensation of 30%. Then, SIL of the compensated transmission line will be (A) 1835 MW (B) 2280 MW (C) 2725 MW (D) 3257 MW

asked May 25, 2018 in Power system by Shimroz123
1 answer 12 views

The input impedance of a short circuited loss less transmission line of characteristic impedance 50 Ohm is

asked May 23, 2018 in Electric Power Transmission by Shimroz123
1 answer 62 views

The corona loss of a 3-phase transmission line is 100 kW at 60 kV/phase and 25 kW at 50 kV/phase. The disruptive critical voltage is (A) 40 kV (B) 43.6 kV (C) 49.6 kV (D) 50 kV

asked Apr 25, 2018 in Electrical Engineering by Shimroz123
1 answer 47 views

A 100 km long transmission line is loaded at 110 kV.if the loss of line is 5 MW and the load is 150 MVA, the resistance of the line is?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 33 views

The impedance Z offered by transmission line for a travelling wave which damps out the low frequency oscillation rapidly is also called

asked Apr 23, 2018 in Electrical Engineering by Shimroz123
1 answer 25 views

lf a travelling-wave travelling along a loss-less overhead line does not result in any reflection after it has reached the far end, then the far end of the line is

asked Apr 26, 2018 in Switchgear And Protection by Shimroz123
1 answer 11 views

A loss less line terminated with its surge impedance has

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 18 views

A loss less line of characteristic impedance Z0 is terminated in pure reactance of –jZ0 value. VSWR is  (1) 10 (2) 2 (3) 1 (4) Infinity

asked Apr 9, 2018 in Electronics Engineering by Shimroz123
2 answers 53 views

A long transmission line has considerable ……………….. effect. A) series capacitance B) shunt capacitance C) series inductance D) shunt inductance

asked Jun 4, 2018 in Electric Power Transmission by Shimroz123
0 answers 22 views

An overhead transmission line has a span of 260 m. The weight of the conductor is 0.68 kg/m. The maximum allowable tension in the line is 1550 kg. Maximum sag of the line should be (a) 5.8 m (b) 4.6 m (c) 2.7 m (d) 3.7 m 

asked May 25, 2018 in Electric Power Transmission by Shimroz123
1 answer 21 views

An 800 kV transmission line has a maximum power transfer capacity of P. If it is operated at 400 kV with the series reactance unchanged, the new maximum power transfer capacity is approximately (A) P (B) 2P (C) P / 2 (D) P / 4

asked May 25, 2018 in Power system by Shimroz123
1 answer 95 views

A transmission line has 1 P.0 impedance on a base of 11 KV, 100 MVA. On a base of 55 KV. it will have a P.0 impedance of

asked May 3, 2018 in Electric Power Transmission by Shimroz123
1 answer 21 views

A transmission line of 200 km has a certain A, B, C and D parameters. If the length is reduced to 60 km

asked Apr 29, 2018 in Electrical Engineering by Shimroz123
0 answers 119 views

A Transmission line conductor has been suspended freely from two towers and has taken the form of a catenary that has c = 487.68m. The span between the two towers is 152 m, and the weight of the conductor is 1160 kg/km. Calculate the length of the conductor.  (A) 487.68 m (B) 152.614 m (C) 5.934 m (D) 11.9 m 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 21 views

The line conductor of a transmission line has an overall diameter of 19.53 mm, weight 0.844 kg/m and an ultimate breaking strength of 7950 kg. If the factor of safety is to be 2, when conductor has an ice of 1 kg/m and a horizontal wind pressure of 1.5 kg/m. What is the vertical sag, corresponding to this loading for a 300 m span level supports?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 16 views

An overhead transmission line has a span of 240m between level supports. What is the maximum sag if the conductor weight 727 kg/km and has a breaking strength of 6880 kg? Allow the factor of safety of 2. Neglecting wind and ice loading.

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 13 views

A three phase overhead transmission line has its conductors horizontally spaced with spacing between adjacent conductors equal to 'd'. if now the conductors of the line are rearranged to form and the equilateral triangle of sides equal to 'd' then?

asked Mar 27, 2018 in Power system by Shimroz123
1 answer 18 views

The magnitude of the open-circuit and short circuit input impedance of a transmission line are 100 ohm and 25 ohm respectively. The characteristic impedance of line is:  (1) 25 ohm (2) 50 ohm (3) 75 ohm (4) 100 ohm

asked Apr 9, 2018 in Electronics Engineering by Shimroz123
0 answers 63 views

What is the difference between a line voltage and low voltage control system?

asked Mar 10, 2018 in High voltage engineering by Quiz
1 answer 58 views

A 6-pole, 50Hz, 3-φ induction motor is running at 950 r.p.m. and has Cu loss of 5kW. The rotor input is (a) 10 kW (b) 95 kW (c) 100 kW (d) 9.5 kW 

asked May 25, 2018 in Induction Machine by Shimroz123
1 answer 25 views

A single-phase transformer has no-load loss of 64 W, as obtained from an open circuit test. When a short-circuit test is performed on it with 90% of the rated currents flowing in its both LV and HV windings, he measured loss is 81 W. The transformer has maximum efficiency when operated at  (A) 50.0% of the rated current (B) 64.0% of the rated current (C) 80.0% of the rated current (D) 88.8% of the rated current

asked May 17, 2018 in Transformer by Shimroz123
1 answer 53 views

A 40 kVA transformer has a core loss of 400 W and a full load copper loss of 800 W. The proportion of full load at maximum efficiency is

asked May 8, 2018 in Electric Power Transmission by Shimroz123
1 answer 29 views

An 8-pole, 50Hz, three-phase induction motor is running at 705rpm and has a rotor copper loss of 5kW. Its rotor input is (A) 5.06 kW (B) 0.3 kW (C) 100 kW (D) 83.33 kW

asked Apr 28, 2018 in Electrical Machine by Shimroz123
1 answer 28 views

 A transformer has maximum efficiency at 3/4 full load. The ratio of its iron losses and full load copper loss is : -  a) 16/9 b) 4 / 3 c) 3/4 d) 9 /16

asked Apr 11, 2018 in Electrical Engineering by Shimroz123
1 answer 37 views

A ferrite core has less eddy current loss than an iron core because?

asked Mar 25, 2018 in Electrical Engineering by Shimroz123
1 answer 28 views

A low noise amplifier has an effective noise temperature of 50 k. The absolute noise figure is

asked May 23, 2018 in Amplifier by Shimroz123
0 answers 8 views

A generating station which has a high investment cost and low operating cost is usually operated as  A) Peak load station B) Spinning reserve station C) Base load station D) None of the above 

asked Apr 9, 2018 in Electrical Engineering by Shimroz123
1 answer 27 views

Corona loss in transmission lines can be reduced by (A) using small diameter conductors (B) using bundled conductors (C) using less spacing between conductors (D) increasing the transmission line voltage

asked Apr 28, 2018 in Power system by Shimroz123
1 answer 123 views

A 50Ω transmission line is terminated in an impedance of 20-j50. What will be the reflection coefficient? A) 0.69 B) 1.69 C) 6.9 D) 16.9 

asked Jun 18, 2018 in Electrical Engineering by Shimroz123
0 answers 20 views

A synchronous condenser is used at the receiving end of a transmission line for (A) supplying lagging kVA (B) voltage control (C) frequency control (D) maintaining a higher voltage than at the sending end 

asked Jun 4, 2018 in Power system by Shimroz123
1 answer 46 views

A single-line-to-ground fault on a overhead transmission line creates (A) voltage sag (B) voltage swell (C) over voltage (D) voltage flicker 

asked Jun 4, 2018 in Electric Power Transmission by Shimroz123
1 answer 12 views

The standing wave ratio of a 75 Ω transmission line used to feed a 300 Ω resistive load will be _____.

asked May 29, 2018 in Electrical Engineering by Shimroz123
1 answer 30 views

For a transmission line open circuit and short circuit impedances are 20 Ω and 5 Ω. Then characteristic impedance is: (1) 100 Ω (2) 50 Ω (3) 25 Ω (4) 10 Ω

asked May 29, 2018 in Electric Power Transmission by Shimroz123
0 answers 21 views

If diameter of each conductor of a transmission line is ‘d’, then the diameter of n-layer stranded conductor will be (a) (2n – 1) d (b) (2n + 1) d (c) (3n – 1) d (d) (3n + 1) d 

asked May 26, 2018 in Electric Power Transmission by Shimroz123
0 answers 20 views

A transmission line to be reciprocal, the condition is (a) A = D (b) AC – BD = 1 (c) AD – BC = 1 (d) AB – CD = 1  

asked May 25, 2018 in Electric Power Transmission by Shimroz123
1 answer 19 views

A 20-MVA, 6.6-kV, 3-phase alternator is connected to a 3-phase transmission line. The per unit positive-sequence, negative-sequence and zero-sequence impedances of the alternator are j0.1, j0.1 and j0.04 respectively. The neutral of the alternator is connected to ground through an inductive reactor of j0.05 p.u. The per unit positive-, ... The voltage of the alternator neutral with respect to ground during the fault is  (A) 513.8 V (B) 889.9 V (C) 1112.0 V (D) 642.2 V

asked May 25, 2018 in Power system by Shimroz123
1 answer 15 views

Choose two appropriate auxiliary components of a HVDC transmission system from the following P. D.C line inductor Q. A.C line inductor R. Reactive power sources S. Distance relays on D.C line T. Series capacitance on A.C. line  (A) P and Q (B) P and R (C) Q and S (D) S and T

asked May 25, 2018 in Power system by Shimroz123
1 answer 20 views

A 800 kV transmission line is having per phase line inductance of 1.1 mH/km and per phase line capacitance of 11.68 nF/km. Ignoring the length of the line, its ideal power transfer capability in MW is (A) 1204 MW (B) 1504 MW (C) 2085 MW (D) 2606 MW

asked May 25, 2018 in Power system by Shimroz123
1 answer 26 views

A generator is connected through a 20 MVA, 13.8/138 kV step down transformer, to a transmission line. At the receiving end of the line a load is supplied through a step down transformer of 10 MVA, 138/69 kV rating. A 0.72 pu. load, evaluated on load side transformer ratings as base values , is supplied from the above system. For system base values of 10 MVA and 69 kV in load circuit, the value of the load (in per unit) in generator will be (A) 36 (B) 1.44 (C) 0.72 (D) 0.18

asked May 25, 2018 in Power system by Shimroz123
0 answers 50 views

A single phase transmission line and a telephone line are both symmetrically strung one below the other, in horizontal configurations, on a common tower, The shortest and longest distances between the phase and telephone conductors are 2.5 m and 3 m respectively. The voltage (volt/km) induced in the telephone circuit, due to 50 Hz current of 100 amps in the power circuit is (A) 4.81 (B) 3.56 (C) 2.29 (D) 1.27

asked May 25, 2018 in Power system by Shimroz123
0 answers 15 views

Voltages phasors at the two terminals of a transmission line of length 70 km have a magnitude of 1.0 per unit but are 180 degree out of phase. Assuming that the maximum load current in the line is 1/5th of minimum 3-phase fault current. Which one of the following transmission line protection schemes ... pick up at 1.25 times the maximum load current (C) Pilot relaying system with directional comparison scheme (D) Pilot relaying system with segregated phase comparison scheme

asked May 25, 2018 in Power system by Shimroz123
1 answer 13 views

A transmission line is operating with a Phase shift of 80° between two ends. If the load is suddenly increased A) The phase displacement will increase B) The phase displacement will decrease C) The phase displacement will not change D) The surge impedance will increase

asked May 24, 2018 in Electrical Engineering by Shimroz123
1 answer 27 views

To increase power transfer capability of a long transmission line, we should:  (1) Increase line resistance (2) Increase transmission voltage (3) Decrease line reactance (4) Both (2) & (3)

asked May 22, 2018 in Electric Power Transmission by Shimroz123
1 answer 15 views

For a fixed value of complex power flow in a transmission line having a sending and voltage V, the real power loss will be proportional to  A) V B) v2 C) 1/V2 D)1/V

asked May 20, 2018 in Power system by Shimroz123
1 answer 12 views

A transmission line is terminated at its characteristic impedance. The reflection coefficient is  (a) 1 (b) –1 (c) 0 (d) ∞

asked May 16, 2018 in Network Analysis by Shimroz123
1 answer 14 views

Which of the two generalized constants of a transmission line are equal?  (a) B & C (B) A & B (c) A & D (D) B & D

asked May 13, 2018 in Power system by Shimroz123

Welcome to electronics2electrical.com here you can ask questions related to electrical, electronics, mechanical, telecommunication, instrumentation, computer, mathematics, physics etc.
Be respectful to all the members. Do not copy and paste the answers from other websites which have copyright content. While asking question give full details about it.

Categories

Most popular tags

power motor dc circuit transformer voltage current used system phase resistance factor synchronous load ac energy induction electric generator series frequency between speed capacitor use electrical meter line difference control type mosfet transmission magnetic plant high single instrument bjt unit source advantages function diode and machine winding field define torque parallel amplifier supply shunt thyristor motors electricity arduino maximum time relay armature problem value on transformers types coil diagram state flow ratio material three formula starting direction theorem method emf operating efficiency digital wave microprocessor test instruments inductance loss measure operation connected signal low applications effect single-phase network temperature working constant losses different law wattmeter measuring compare controlled breaker drive device logic rc full switch flux wire resistivity disadvantages free of materials machines angle force converter conductor transistor gain open protection scr core measurement number bridge principle generators reactance circuits negative the friction iron loop short pole battery conservation steam resistors hysteresis computer using analog lines secondary station gate a rectifier inverter linear induced relays nuclear capacitance basic characteristics design direct work rotor electronics ammeter forces diesel damping rlc connection factors capacitors minimum insulation moving regulation running self systems air fault range main stability quality starter igbt eddy alternator ideal rl average 3-phase plants arc thermal error fuzzy biasing dielectric pressure balanced superposition errors copper rotation feedback impedance measured electronic electrons charge inductive transfer explain start off back curve over solar is three-phase tariff locomotive peak bias zener engineering commutator surge conductors rating universal potentiometer density permanent mechanical transducer capacity memory adc excitation two fuse pure harmonics application semiconductor inductor internal pmmc reaction welding resonance traction permeability breakers rms designed electromagnetic si generation brushes switching capacitive shaded rate 1 distribution resistor methods delta star oscillator reluctance simplification algebra 8085 boolean weston dynamometer insulating strength installation definition fuel heating earth units

8,480 questions

7,077 answers

134 comments

3,088 users

...