Two 550 kVA alternator operate in parallel to supply the following loads

I. 250 KW at 0.95 p.f. lagging

II. 100 KW at 0.85 p.f. leading

One machine is supplying 200 KW at 0.9 p.f. lagging. The p.f. of other machine must be

Please log in or register to answer this question.

1 Answer

0 votes
answered by

Two 550 kVA alternator operate in parallel to supply the following loads


I. 250 KW at 0.95 p.f. lagging

II. 100 KW at 0.85 p.f. leading

One machine is supplying 200 KW at 0.9 p.f. lagging. The p.f. of other machine must be 0.89 leading