Distribution system 

Till now we have learnt how power at somewhat high voltage (say 33 kV) is received in a substation situated near load center (a big city). The loads of a big city are primarily residential complexes, offices, schools, hotels, street lighting etc. These types of consumers are called LT (low tension) consumers. Apart from this there may be medium and small scale industries located in the outskirts of the city. LT consumers are to be supplied with single phase, 220 V, 40 Hz. We shall discuss here how this is achieved in the substation receiving power at 33 kV. The scheme is shown in figure 2.11.

image

Power receive at a 33 kV substation is first stepped down to 6 kV and with the help of under ground cables (called feeder lines), power flow is directed to different directions of the city. At the last level, step down transformers are used to step down the voltage form 6 kV to 400 V. These transformers are called distribution transformers with 400 V, star connected secondary. You must have noticed such transformers mounted on poles in cities beside the roads. These are called pole mounted substations. From the secondary of these transformers 4 terminals (R, Y, B and N) come out. N is called the neutral and taken out from the common point of star connected secondary. Voltage between any two phases (i.e., R-Y, Y-B and B-R) is 400 V and between any phase and neutral is 230 V(= 400/ 3). Residential buildings are supplied with single phase 230V, 50Hz. So individual are to be supplied with any one of the phases and neutral. Supply authority tries to see that the loads remain evenly balanced among the phases as far as possible. Which means roughly one third of the consumers will be supplied from R-N, next one third from Y-N and the remaining one third from B-N. The distribution of power from the pole mounted substation can be done either by (1) overhead lines (bare conductors) or by (2) underground cables. Use of overhead lines although cheap, is often accident prone and also theft of power by hooking from the lines take place. Although costly, in big cities and thickly populated areas underground cables for distribution of power, are used. 

Version 2 EE IIT, Kharagpur 


Related questions

1 answer 30 views

Distributed under Creative Commons Attribution-ShareAlike - CC BY-SA.

asked Apr 3, 2018 in Lesson 2 Generation, Transmission and Distribution of Electric Power an Overview by Shimroz123
1 answer 24 views

The system of equations x + y+ z = 6, 2 x + y +z = 7, x + 2 y +z=8 has a. A unique solution b. No solution c. An infinite number of solutions d. None of these

asked Apr 12, 2018 in Electronics Engineering by Shimroz123
0 answers 23 views

Name the types of generators (alternators) used in (1) thermal plant and (2) in hydel power plant. 

asked Apr 3, 2018 in Lesson 2 Generation, Transmission and Distribution of Electric Power an Overview by Shimroz123
0 answers 49 views

A high-pass filter has a resistance R = 2 kΩ The lowest input frequency to be passed is 7.5 kHz. The value of suitable coupling capacitor must be: A) 0.001 pico Farad B) 0.01 pico Farad C) 0.1 pico Farad D) 1 pico Farad

asked Jun 4, 2018 in Electrical Engineering by Shimroz123
0 answers 20 views

A 3-phase, 2 pole, 11 kV, 10000 kVA alternator has earthed neutral through a resistance of 7.0Ω. The machine has current balance protection which operates if out of balance current exceeds 20% of full load. Determine %age of winding protected against earth fault (1) 10.6% (2) 11.6% (3) 10.9% (4) 11.2% 

asked Apr 11, 2018 in Electrical Engineering by Shimroz123
0 answers 15 views

Total numbers of ascending runs in the sequence 4 6 7 2 9 1 2 8 9 3 0  (1) 3 (2) 5 (3) 7 (4) 9  

asked Apr 10, 2018 in Computer Engineering by Shimroz123
0 answers 18 views

When the SCR conducts, the forward voltage drop will   (a) 0.7 V at all load current (b) 2 to 2.5 V at all load current (c) increases slightly with load current (d) remains constant with load current 

asked Apr 10, 2018 in Electrical Engineering by Shimroz123
0 answers 18 views

What is a pole mounted substation? At what voltage levels are the found in a power system? 

asked Apr 3, 2018 in Lesson 2 Generation, Transmission and Distribution of Electric Power an Overview by Shimroz123
1 answer 14 views

Distributed under Creative Commons Attribution-ShareAlike - CC BY-SA.

asked Apr 3, 2018 in Lesson 2 Generation, Transmission and Distribution of Electric Power an Overview by Shimroz123
1 answer 659 views

State the working principle and operation of Automatic power factor controller used in Transmission and Distribution system.

asked Oct 3, 2018 in Energy Conservation And Audit by Shimroz123
2 answers 68 views

Explain how technical losses can be reduced by use of energy efficient transformer in Transmission and Distribution system.

asked Oct 3, 2018 in Energy Conservation And Audit by Shimroz123
1 answer 15 views

Explain the following energy conservation techniques: (i) By reducing I2R losses in Trans. system (ii) By optimizing distribution voltage.

asked Oct 3, 2018 in Energy Conservation And Audit by Shimroz123
1 answer 459 views

List out the different technical losses that takes place in Transmission and Distribution system.

asked Oct 3, 2018 in Energy Conservation And Audit by Shimroz123
1 answer 190 views

With neat diagram explain use of “reactive power controller” to reduce technical losses in transmission and distribution system.

asked Sep 22, 2018 in Energy Conservation And Audit by Shimroz123
1 answer 54 views

Explain following techniques related to energy conservation in transmission and distribution system. (i) By balancing phase currents (ii) Variable technical losses (I2R losses).

asked Sep 22, 2018 in Energy Conservation And Audit by Shimroz123
2 answers 29 views

State and explain any four commercial losses in transmission and distribution system.

asked Sep 22, 2018 in Energy Conservation And Audit by Shimroz123
1 answer 12 views

The third generation relays - digital relays - are the basis of distribution system automation because of their: a. Self fault diagnostic capabilities b. Computing capabilities c. Easy interface for remote communication d. All of the above

asked Sep 1, 2018 by Shimroz123
1 answer 14 views

According to the scheme of connection the distribution system is classified as: a. Radial system b. Ring main system c. Inter-connected system d. All of the above 

asked Sep 1, 2018 by Shimroz123
0 answers 96 views

The ‘transportation delays’ occurring in distribution system are detrimental to stability because they produce (a) attenuation (b) phase lag (c) both (a) and (b) (d) transients 

asked May 25, 2018 in Electric Power Distribution by Shimroz123
1 answer 23 views

The permissible voltage variation in transmission and distribution system is:  (A) ± 0.1% (B) ± 1% (C) ±10% (D) ± 25%

asked May 8, 2018 in Electrical Engineering by Shimroz123
1 answer 34 views

The main criterion for selection of the size of a radial distribution system is

asked Apr 29, 2018 in Power system by Shimroz123
1 answer 20 views

In a 3-insulator string voltage distribution system the ratio of capacitance between pin and earth to the self capacitance of each unit is 1/4. If the potential across the top unit is 8 kV, then the string voltage is (A) 22.5 kV (B) 24 kV (C) 26 kV (D) 32.5 kV

asked Apr 25, 2018 in Electrical Engineering by Shimroz123
1 answer 19 views

In a 3-phase 4-wire distribution system three unbalanced but equal magnitude impedances are connected between respective lines and neutral. The magnitude of current in the neutral conductor for RYB and RBY phase sequences are (A) zero (B) same (C) different (D) same in magnitude but differs in phase.

asked Apr 25, 2018 in Electrical Engineering by Shimroz123
0 answers 19 views

Which distribution system is more reliable ?   (a) Ring main system (b) Tree system (c) Radial system (d) All are equally reliable. 

asked Apr 10, 2018 in Electrical Engineering by Shimroz123
1 answer 9 views

Perform following number system conversion : (i) (589)10 = ( )2 (ii) (101101)2 = ( )16 (iii) (413)8 = ( )2 (iv) (5AF)16 = ( )10 (v) (AC8)16 = ( )2 (vi) (106)8 = ( )10

asked Sep 2, 2018 by Shimroz123
1 answer 13 views

Which one most appropriate dynamic system? (1) y(n) + y(n – 1) + y(n + 1) (2) y(n) + y(n – 1) (3) y(n) = x(n) (4) y(n) + y(n – 1) + y(n + 3) = 0 

asked May 28, 2018 in Control System by Shimroz123
1 answer 19 views

For a feedback control system of type 2, the steady error for a rap input is  A) Infinite B) Constant C) Zero D) Indeterminate

asked May 20, 2018 in Control System by Shimroz123
1 answer 19 views

System 1 : The first column of the RH array consists of the terms 6,3,9,-2, and 4. System 2 : The first column of the RH array consists of the terms 3,6,9,2, and -4. The number of unstable poles for system1, and system 2, are respectively, (A) 1,1 (B) none, none (C) 2,2 (D) 2,1

asked Apr 28, 2018 in Control System by Shimroz123
1 answer 13 views

In a system, the damping coefficient is - 2. The system response will be (a) Undamped (b) Oscillations with decreasing magnitude (c) Oscillations with increasing magnitude (d) Critically damped

asked Apr 25, 2018 in Electrical Engineering by Shimroz123
1 answer 22 views

A system has 14 poles and 2 zeros in its open -loop transfer function. The slope of its highest frequency asymptote in its magnitude plot is (a) - 40 dB/dec (b) - 240 dB/dec (c) + 40 dB/dec (d) + 240 dB/dec

asked Apr 25, 2018 in Electrical Engineering by Shimroz123
0 answers 12 views

MS-Excel is a kind of  (1) Accounting software (2) Multimedia software (3) System software (4) Data base management software

asked Apr 10, 2018 in Computer Engineering by Shimroz123
0 answers 59 views

The DFD is  (1) modern version of flowchart (2) mainly used at system specification stage (3) primary output of the system design phase (4) all of these

asked Apr 10, 2018 in Computer Engineering by Shimroz123
1 answer 18 views

In PCM system, if we increase the quantization levels from 2 to 8, the relative bandwidth requirements will:  (1) Be doubled (2) Remain same (3) Be tripled (4) Becomes eight times

asked Apr 9, 2018 in Electronics Engineering by Shimroz123
0 answers 29 views

The dc gain of the system represented by the transfer function G(s)=(s+6)/((s+2)(s+3)) is  A) 1 B) 2 C) 5 D) 6

asked Apr 9, 2018 in Control System by Shimroz123
1 answer 37 views

If the characteristics equation of a closed loop system is s2+2s+2=0, then the system is  (A) Over damped (B) Critically damped (C) Under damped (D) Undamped 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 16 views

The position and velocity errors of a type-2 system are?

asked Mar 27, 2018 in Control System by Shimroz123
1 answer 21 views

The type 2 system has ______at the origin.

asked Mar 27, 2018 in Control System by Shimroz123
1 answer 47 views
0 answers 342 views
0 answers 18 views
0 answers 62 views

The ammeter reading connected across a CT secondary is 3 A and the voltage reading connected across a PT is 90 V. If the specification of the CT and PT are respectively 1000 A/5 A and 6.6 kV/110 V, What is the actual current and voltage of the line? 

asked Apr 3, 2018 in Lesson 2 Generation, Transmission and Distribution of Electric Power an Overview by Shimroz123
0 answers 27 views
0 answers 32 views

With the help of a schematic diagram explain how a overcurrent relay protects a line during short circuit fault. 

asked Apr 3, 2018 in Lesson 2 Generation, Transmission and Distribution of Electric Power an Overview by Shimroz123
0 answers 27 views
0 answers 21 views

Give some typical value of generated voltage in a power station. Why is it necessary to step up the voltage further before transmitting?

asked Apr 3, 2018 in Lesson 2 Generation, Transmission and Distribution of Electric Power an Overview by Shimroz123
0 answers 32 views

In a hydel power station, the number of poles of an alternator is 24. At what rpm the alternator must be driven to produce 50 Hz voltage?

asked Apr 3, 2018 in Lesson 2 Generation, Transmission and Distribution of Electric Power an Overview by Shimroz123
0 answers 18 views

What number of phases and frequency are adopted to generate, transmit and distribute electrical power in modern power system?

asked Apr 3, 2018 in Lesson 2 Generation, Transmission and Distribution of Electric Power an Overview by Shimroz123
1 answer 41 views

Name three conventional ways of generating power. Of these three, which one contributes maximum generation in India.

asked Apr 3, 2018 in Lesson 2 Generation, Transmission and Distribution of Electric Power an Overview by Shimroz123
1 answer 12 views

Distributed under Creative Commons Attribution-ShareAlike - CC BY-SA.

asked Apr 3, 2018 in Lesson 2 Generation, Transmission and Distribution of Electric Power an Overview by Shimroz123

Welcome to electronics2electrical.com here you can ask questions related to electrical, electronics, mechanical, telecommunication, instrumentation, computer, mathematics, physics etc.
Be respectful to all the members. Do not copy and paste the answers from other websites which have copyright content. While asking question give full details about it.

Categories

Most popular tags

power motor dc circuit transformer voltage current used system phase resistance factor synchronous load ac energy induction electric generator series frequency between speed capacitor use electrical meter line difference control type mosfet transmission magnetic plant high single instrument bjt unit source advantages function diode and machine winding field define torque parallel amplifier supply shunt thyristor motors electricity arduino maximum time relay armature problem value on transformers types coil diagram state flow ratio material three formula starting direction theorem method emf operating efficiency digital wave microprocessor test instruments inductance loss measure operation connected signal low applications effect single-phase network temperature working constant losses different law wattmeter measuring compare controlled breaker drive device logic rc full switch flux wire resistivity disadvantages free of materials machines angle force converter conductor transistor gain open protection scr core measurement number bridge principle generators reactance circuits negative the friction iron loop short pole battery conservation steam resistors hysteresis computer using analog lines secondary station gate a rectifier inverter linear induced relays nuclear capacitance basic characteristics design direct work rotor electronics ammeter forces diesel damping rlc connection factors capacitors minimum insulation moving regulation running self systems air fault range main stability quality starter igbt eddy alternator ideal rl average 3-phase plants arc thermal error fuzzy biasing dielectric pressure balanced superposition errors copper rotation feedback impedance measured electronic electrons charge inductive transfer explain start off back curve over solar is three-phase tariff locomotive peak bias zener engineering commutator surge conductors rating universal potentiometer density permanent mechanical transducer capacity memory adc excitation two fuse pure harmonics application semiconductor inductor internal pmmc reaction welding resonance traction permeability breakers rms designed electromagnetic si generation brushes switching capacitive shaded rate 1 distribution resistor methods delta star oscillator reluctance simplification algebra 8085 boolean weston dynamometer insulating strength installation definition fuel heating earth units

8,530 questions

7,129 answers

135 comments

3,090 users

...