To limit the short circuit current during fault conditions:

28 views
in Electrical Engineering by
A two -winding single phase transformer has a voltage regulation of 4.5% at full - load and unity power -factor. At full -load and 0.80 lagging power-factor, the voltage regulation will be: (A) 4.5% (B) less than 4.5% (C) more than 4.5% (D) none of the above

1 Answer

0 votes
by

A two -winding single phase transformer has a voltage regulation of 4.5% at full - load and unity power -factor. At full -load and 0.80 lagging power-factor, the voltage regulation will be: more than 4.5%

Related questions

1 answer 17 views

A single-phase, 50 kVA, 250 V/500 V two winding transformer has an efficiency of 95% at full load, unity power factor. If it is re-configured as a 500 V/750 V auto-transformer, its efficiency at its new rated load at unity power factor will be  (A) 95.752% (B) 97.851% (C) 98.276% (D) 99.241%

asked May 17, 2018 in Transformer by Shimroz123
1 answer 17 views

A simple phase transformer has a maximum efficiency of 90% at full load and unity power factor. Efficiency at half load at the same power factor is  (A) 86.7% (B) 88.26% (C) 88.9% (D) 87.8%

asked May 17, 2018 in Transformer by Shimroz123
1 answer 41 views

A 230 V/460 V single-phase transformer operating at 20 A and unity power factor has primary referred resistance of 0.2 Ω and reactance of 0.5 Ω. The approximate primary induced emf is (A) 216 V (B) 226 V (C) 234 V (D) 236 V

asked Apr 28, 2018 in Electrical Engineering by Shimroz123
1 answer 28 views

 A transformer has maximum efficiency at 3/4 full load. The ratio of its iron losses and full load copper loss is : -  a) 16/9 b) 4 / 3 c) 3/4 d) 9 /16

asked Apr 11, 2018 in Electrical Engineering by Shimroz123
0 answers 30 views

The voltage regulation of a transformer, with ohmic drop 2% and reactance drop 5% of the voltage at 0.8 lagging power factor, will be (a) 7% (b) 5.6% (c) 5.3% (d) 4.6%

asked May 25, 2018 in Transformer by Shimroz123
1 answer 30 views

A three-phase synchronous motor connected to ac mains is running at full load and unity power factor. lf its shaft load is reduced by half and field current is held constant then its new power factor will be

asked Apr 28, 2018 in Electrical Machine by Shimroz123
1 answer 5 views

What will be the efficiency when the transformer operates at unity power factor and 60% of full load 

asked Sep 1, 2018 by Shimroz123
0 answers 108 views

A single phase transformer rated at 3000 kVA, 69 kV 4.16 kV, 60 Hz has a total internal impedance Zp of 127 ohm, referred to the primary side. Calculate the primary current if the secondary is accidentally short circuited.  (A) 43.5 A (B) 543 A (C) 9006 A (D) 721 A 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 16 views

In a transformer, zero voltage regulation at full load is   (a)Not possible   (b) Possible at unity power factor load   (c) Possible at leading power factor load   (d) Possible at lagging power factor load

asked May 13, 2018 in Transformer by Shimroz123
0 answers 23 views

A Power system has a total load of 1260 MW at 50 Hz. The load varies 1.5% for every 1% change in frequency. Find the steady state frequency deviation, when a 60 MW load is suddenly dripped if there is no speed control.  (A) 1.667 Hz (B) 50 Hz (C) No change (D) 3.32 Hz 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 27 views

A transformer has negative voltage regulation when its load power factor is   (1) Zero (2) Unity (3) Leading (4) Lagging

asked Apr 30, 2018 in Power system by Shimroz123
1 answer 26 views

The type of single-phase induction motor having the highest power factor at full load is (A) shaded pole type (B) split-phase type (C) capacitor-start type (D) capacitor-run type

asked May 17, 2018 in Induction Machine by Shimroz123
1 answer 20 views

A single-phase ac voltage source has 200 V rms and a system connected consumes an active power of 300 W. What is the reactive power consumed by the system if 2.5 A rms current is drawn ?  (a) 100 VAR (b) 200 VAR (c) 300 VAR (d) 400 VAR

asked Apr 23, 2018 in Electrical Engineering by Zeeshan
0 answers 16 views

At maximum efficiency of a single-phase transformer, the load power factor is (A) unity (B) lagging (C) leading (D) zero 

asked Jun 4, 2018 in Single phase transformer by Shimroz123
1 answer 13 views

A 500 kVA, 3-phase transformer has iron losses of 300 W and full load copper losses of 600 W. The percentage load at which the transformer is expected to have maximum efficiency is  (A) 50.0% (B) 70.7% (C) 141.4% (D) 200.0%

asked May 17, 2018 in Transformer by Shimroz123
0 answers 24 views

A single phase 230 V/ 150 V , 1 kVA, 50 Hz transformer is supplied by 230 V AC supply. Find the full load primary and secondary current. 

asked Sep 1, 2018 by Quiz
0 answers 49 views

A single phase, half-wave, controlled rectifier has 400 sin (314 t) as the input voltage and R as the load. For a firing angle of 60° for the SCR, the average output voltage is   (a) 240/π (b) 400/π (c) 300/π (d) 200/π 

asked Apr 10, 2018 in Electrical Engineering by Shimroz123
1 answer 24 views

A single-phase transformer has a turns ratio of 1 :2 and is connected to a purely resistive load as shown in the figure. The magnetizing current drawn is 1A, and the secondary current is 1A. Ifcore losses and leakage reactances are neglected, the primary current is  A)1.41A B)2A C) 2.24A D)3A

asked May 20, 2018 in Transformer by Shimroz123
1 answer 200 views

A 400/200 volts transformer has pu impedance of 0.05. The HV side voltage required to circulate full load current during short circuit test is

asked Apr 25, 2018 in Electrical Engineering by Shimroz123
1 answer 12 views

Power (P) in a 3 phase circuit with two watt meters at unity power factor is (W1 & W2 = watt meter readings)

asked May 15, 2018 in Electrical Engineering by Shimroz123
1 answer 45 views

A single phase transformer has resistance and reactance of 0.2 pu and 0.6 pu respectively. Its pu voltage regulation at 0.8 pf lagging would he

asked May 3, 2018 in Power system by Shimroz123
0 answers 13 views

 A single phase, 2000V alternator has armature resistance and reactance of 0.8 ohm and 4.94 ohm respectively. The voltage regulation of the alternator at 100A, 0.8 leading pf is (A) 7% (B) - 8.9% (C) - 6.3% (D) 0%

asked Apr 14, 2018 in Electrical Engineering by Shimroz123
1 answer 42 views

 An 8-pole alternator runs at 750 rpm and supplies power to a 6-pole induction motor which has a full load slip of 3 percent. The full load speed of the induction motor will be: A) 1000 rpm B) 920 rpm C) 950 rpm D) 970 rpm

asked Jun 4, 2018 in Alternator by Shimroz123
1 answer 41 views

At full -load of a transformer, the iron loss and copper loss are 3000 W and 4000 W respectively. Then total loss at maximum efficiency is :  (A) 7000 W (B) 6000 W (C) 8000 W (D) 4000 W

asked Apr 30, 2018 in Electrical Engineering by Shimroz123
0 answers 88 views

A single phase 60 Hz generator supplies an inductive load of 4500kW at a power factor of 0.80 lagging by means of a 20 km long overhead transmission line. The line resistance and inductance are 0.0195 ohm and 0.60 mH per km. The voltage at the receiving end is required to be kept constant at 10.2 kV. Find the voltage regulation of the line.  (A) 12.59% (B) 16.34% (C) 32.68% (D) 41.15% 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
0 answers 69 views

The magnetizing reactance of a 4 kV/ 400 V, 50 Hz single-phase transformer on low voltage side is 35 Ω. The magnetizing reactance on the high voltage side is (A) 0.35 Ω (B) 3.5 Ω (C) 350 Ω (D) 3500 Ω

asked Jun 4, 2018 in Single phase transformer by Shimroz123
1 answer 9 views

if the rated voltage from the power lines is applied to the primary of a single-phase transformer which is operated on no-load, then

asked Apr 1, 2018 in Electrical Engineering by Shimroz123
0 answers 45 views

For a balanced three phase star connected load for which line voltage is 230V and per phase resistance and reactance is 6 Ohm and 8 Ohm respectively. Calculate: 1) phase voltage 2) line current 3) power factor 4) total power absorbed

asked Aug 12, 2018 in Basic electrical and electronics engineering by Quiz
1 answer 17 views

A single phase full-wave half-controlled bridge converter feeds an inductive load. The two SCRs in the converter are connected to a common DC bus. The converter has to have a freewheeling diode.  (A) because the converter inherently does not provide for free-wheeling (B) because the converter does not provide for free-wheeling for high ... the AC supply (D) or else if a gate pulse to one of the SCRs is missed, it will subsequently cause a high load current in the other SCR.

asked May 18, 2018 in Power electronics converters by Shimroz123
1 answer 18 views

If a 3-phase, 400V, 50Hz, 4 pole induction motor is running at a slip of 5% then the relative speed of rotor field with respect to stator filed is:

asked May 22, 2018 in Induction Machine by Shimroz123
1 answer 25 views

A single-phase transformer has no-load loss of 64 W, as obtained from an open circuit test. When a short-circuit test is performed on it with 90% of the rated currents flowing in its both LV and HV windings, he measured loss is 81 W. The transformer has maximum efficiency when operated at  (A) 50.0% of the rated current (B) 64.0% of the rated current (C) 80.0% of the rated current (D) 88.8% of the rated current

asked May 17, 2018 in Transformer by Shimroz123
0 answers 14 views

One 200 KVA transformer has an iron loss of 1 KW and full load Cu loss of 2 KW. Its load KVA corresponding to maximum efficiency is:  (A) 100 KVA (B) 141.4 KVA (C) 50 KVA (D) 200 KVA 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 32 views

A 36 slot, 4 -pole, dc machine has a simplex lap winding with two conductors per slot. The back pitch and front pitch adopted could be respectively

asked May 3, 2018 in Electrical Machine by Shimroz123
0 answers 11 views

A 3-phase, 50 Hz, 500 V induction motor develops 20 hp at slip of 5%. Mechanical losses are 1 hp, and stator loss is 1 kW. The efficiency will be   (a) 95.3% (b) 90.5% (c) 91.3% (d) 85.3% 

asked Apr 10, 2018 in Electrical Engineering by Shimroz123
1 answer 47 views

The potential coil of a single phase dynamometer wattmeter has 4840 Ohm resistance. Voltage across the load is 220 V. With the potential coil connected on the load side, the meter indicates 100 W. Approximate percentage error due to wattmeter connection is (A) 11% (B) 9% (C) 1.1% (D) 3%

asked Apr 25, 2018 in Instrumentation and control by Shimroz123
0 answers 11 views

The no~load current of a single phase induction motor is around _____% of full load current.  (1) 10 (2) 20 (3) 40 (4) 80

asked Apr 10, 2018 in Electrical Engineering by Shimroz123
1 answer 7 views

A single-phase, 230 V, 50 Hz ac mains fed step down transformer (4:1) is supplying power to a half-wave uncontrolled ac-dc converter used for charging a battery (12 V dc) with the series current limiting resistor being 19.04 Ohm. The charging current is  (A) 2.43 A (B) 1.65 A (C) 1.22 A (D) 1.0 A

asked May 18, 2018 in Power electronics converters by Shimroz123
1 answer 52 views

A 40 kVA transformer has a core loss of 400 W and a full load copper loss of 800 W. The proportion of full load at maximum efficiency is

asked May 8, 2018 in Electric Power Transmission by Shimroz123
1 answer 12 views

A commercial power supply has a voltage regulation of:  1. 1% 2.5% 3.20% 4.50% 

asked May 13, 2018 in Electrical Engineering by Shimroz123
0 answers 19 views

The efficiency of a transformer at full load 0.8 p.f lagging is 90%. Its efficiency at full load 0.8 p.f leading will be (1) Less than 90% (2) More than 90% (3) 90% (4) None of these 

asked Apr 11, 2018 in Electrical Engineering by Shimroz123
1 answer 37 views

A 150 kW electric motor has an efficiency of 92 %, when it operates at full load. Calculate the losses in the machine.  (A) 92 kW (B) 150 kW (C) 163 kW (D) 13 kW 

asked Apr 5, 2018 in Electrical Engineering by Shimroz123
1 answer 15 views

A single phase CSI has capacitor C as the load. For a constant source current, the voltage across the capacitor is   (A) square wave (B) triangular wave (C) step function (D) pulsed wave

asked May 17, 2018 in Power electronics converters by Shimroz123
0 answers 15 views

A 50 Hz, 3—phase induction motor has a full load speed of 1440 rpm. The number of poles of the motor is:   (A)4 (8)6 (0)12  (D)8

asked Apr 9, 2018 in Electrical Engineering by Shimroz123
0 answers 13 views

 A single phase full -wave half controlled bridge converter feeds an inductive load: The two SCRs in the converter are connected to a common DC bus. The converter has to have a free wheeling diode (A) Because the converter inherently does not provide for free wheeling (B) Because the converter does not provide for free wheeling for high ... the AC supply (D) Or else if a gate pulse to one of the SCRs is missed, it will subsequently cause a high load current in the other SCR

asked Apr 14, 2018 in Electrical Engineering by Shimroz123
1 answer 44 views

In an alternator at lagging power factor the generated voltage per phase as compared to that at unity power factor?

asked Mar 18, 2018 in Alternator by Shimroz123
1 answer 12 views

A three phase induction motor is driving full -load torque which is independent of speed. If the line voltage drops to 90% of the rated value, % increase in motor copper losses  (a) 23% (b) -18% (c) 123% (d) None of these

asked Apr 25, 2018 in Electrical Engineering by Shimroz123
1 answer 16 views

A 400 V, 15 kW, 4-pole, 50 Hz, Y-connected induction motor has full load slip of 4%. The output torque of the machine at full load is  (A) 1.66 Nm (B) 95.50 Nm (C) 99.47 Nm (D) 624.73 Nm

asked May 17, 2018 in Induction Machine by Shimroz123
0 answers 23 views

The constant of a given energy meter is 500 revolution/kWh. At the test 4.4 kW full load, meter completes 50 revolutions in 86 seconds. The percentage error of the meter is (a) –4.86% (b) 4.86% (c) 2.0% (d) 3.0%

asked May 26, 2018 in Electrical Measurements and Instrumentation by Shimroz123
0 answers 31 views

A single phase energy meter has a constant of 1200 revolution/kWh. When a load of 200 W is connected, the disc rotates at 4.2 revolutions per min. If the load is on for 10 hours, the meter records an excess of   (a) 0.1 kWh (b) 0.2 kWh (c) 1.0 kWh (d) 2.0 kWh 

asked Apr 10, 2018 in Electrical Engineering by Shimroz123

Welcome to electronics2electrical.com here you can ask questions related to electrical, electronics, mechanical, telecommunication, instrumentation, computer, mathematics, physics etc.
Be respectful to all the members. Do not copy and paste the answers from other websites which have copyright content. While asking question give full details about it.

Categories

Most popular tags

power motor dc circuit transformer voltage current used system phase resistance factor synchronous load ac energy induction electric generator series frequency between speed capacitor use electrical meter line difference control type mosfet transmission magnetic plant high single instrument bjt unit source advantages function diode and machine winding field define torque parallel amplifier supply shunt thyristor motors electricity arduino maximum time relay armature problem value on transformers types coil diagram state flow ratio material three formula starting direction theorem method emf operating efficiency digital wave microprocessor test instruments inductance loss measure operation connected signal low applications effect single-phase network temperature working constant losses different law wattmeter measuring compare controlled breaker drive device logic rc full switch flux wire resistivity disadvantages free of materials machines angle force converter conductor transistor gain open protection scr core measurement number bridge principle generators reactance circuits negative the friction iron loop short pole battery conservation steam resistors hysteresis computer using analog lines secondary station gate a rectifier inverter linear induced relays nuclear capacitance basic characteristics design direct work rotor electronics ammeter forces diesel damping rlc connection factors capacitors minimum insulation moving regulation running self systems air fault range main stability quality starter igbt eddy alternator ideal rl average 3-phase plants arc thermal error fuzzy biasing dielectric pressure balanced superposition errors copper rotation feedback impedance measured electronic electrons charge inductive transfer explain start off back curve over solar is three-phase tariff locomotive peak bias zener engineering commutator surge conductors rating universal potentiometer density permanent mechanical transducer capacity memory adc excitation two fuse pure harmonics application semiconductor inductor internal pmmc reaction welding resonance traction permeability breakers rms designed electromagnetic si generation brushes switching capacitive shaded rate 1 distribution resistor methods delta star oscillator reluctance simplification algebra 8085 boolean weston dynamometer insulating strength installation definition fuel heating earth units
...