A two -winding single phase transformer has a voltage regulation of 4.5% at full - load and unity power -factor. At full -load and 0.80 lagging power-factor, the voltage regulation will be: (A) 4.5% (B) less than 4.5% (C) more than 4.5% (D) none of the above

Know someone who can answer this question ? Share this on Facebook, Twitter, Whatsapp

← Prev Question Next Question →

1 Answer

0 like 0 dislike
by

A two -winding single phase transformer has a voltage regulation of 4.5% at full - load and unity power -factor. At full -load and 0.80 lagging power-factor, the voltage regulation will be: more than 4.5%